1. INTRODUCTION:
PROCESS INSTRUMENTATION IMPLIES JUDICIOUS APPLICATION
OF CERTAIN DEVICES, WHICH SUBSTITUTE OR SUPPLEMENT THE COGNITIVE HUMAN CHARACTERISTICS-LIKE PERCEPTUAL, COMMUNICATIVE, INTELLECTUAL OR MANIPULATIVEIN ORDER TO IDENTIFY AND
TO PROVIDE:
MEASUREMENT & CONTROL. ONLINE QUALITY & HIGH PRODUCTIVITY. DOCUMENTATION&REPORT GENERATION. LONGIVITY OF THE PLANT.
31/07/2012 23:12:15
"INSTRUMENTATION" CONNOTES
FACT-FINDING, DISPLAY OF INFORMATION, APPLICATION-ENGINEERING AND AUTOMATIC CONTROL. THE PROGRESS OF MEASUREMENT IS THE PROGRESS OF SCIENCE. LIKEWISE ADVANCEMENT IN THE ART AND
BOILER INSTRUMENTATION
&CONTROLS-TOPIC OF THE DAY
BOILERS PLAY AN IMPORTANT ROLE IN POWER GENERATION AND IN PROCESSINDUSTRIES AS HEATING MEDIUM, AS COMPARED TO ANY OTHER SOURCE AS STEAM ENERGY COSTS LESS.
STEAM PRESSURE, FEED WATER SUPPLY. FUEL QUANTITY, COMBUSTION-AIR QUANTITY AND REMOVAL OF WASTE GASES.
31/07/2012 23:12:16
BOILER-CONTROLS OVERVIEW
1. DRUM LEVEL 2. STEAM FLOW 3. FEED WATER FLOW 4. OUTLET STEAM PRESSURE 5. FUEL FLOW & COMBUSTION 6. S.H STEAM TEMPERATURE 7. FURNACE DRAFT 8. DEAIRATOR LEVAL 9. DEAIRATOR ST. PRESSURE 10.SOOT BLOW ST.PRESSURE 1. SAFETY INTERLOCKS 2. SOOT BLOW INTERLOCKS
8
31/07/2012 23:12:16
BOILER WATER&STEAM
31/07/2012 23:12:16
10
THE AIM OF THIS CONTROL LOOP IS TO MAINTAIN THE DRUM LEVEL AT THE NORMAL OPERATING LEVEL OF THE BOILER DRUM. THE THREE ELEMENTS IN THIS LOOP ARE 1.DRUM LEVEL 2.STEAM FLOW
31/07/2012 23:12:16
31/07/2012 23:12:16
12
DENSITY D CORRECTION:
LP
H-Hm Hm Condensate Pot
Dw WATER DENSITY
Head on LP = H * Da ( Da- Water Density @30*C) Delta p = HP LP =Hm (Dw-Ds) H (Da-Ds) Hm = {delta p + H (Da-Ds)} / (Dw-Ds)
31/07/2012 23:12:16
13
STEAM FLOW SIGNAL IS USED AS A FEED FORWARD SIGNAL TO TAKE CARE OF THE SHRINK & SWELL EFFECT DRUM WATER LEVEL. F.W. AND STEAM SQ-ROOT SIGNALS ARE LENIARIESED AND FED TO FLOW-COMPUTOR
31/07/2012 23:12:16
14
COMPUTED FORMULEA:
DRUM LEVEL CONTROLLER OUTPUT+ STEAM FLOW SIGNAL- 50 % = REMOTE SET POINT FOR FEED WATER FLOW CONTROLLER HENCE FEED WATER FLOW CONTROLLER IS A CASCADE CONTROLLER. ITS OUTPUT ACTUATES THE FEED FLOW CONTROL VALVE- F.V. TO FILL DRUM / TO MAKEUP DRUM LEVEL.
31/07/2012 23:12:16
15
Temperature & Pressure Compensation for any compressible fluid like steam /air.
THE EQUATION FOR COMPENSATION DONE AT FUNCTION BLOCK FX 704 IS AS GIVEN BELOW.
ACTUAL STEAM FLOW:= INDICATED STEAM FLOW X SQRT{[(P1+1.209)*(485.0+273)]/[(66.0+1)*(T1+273)]} P1- MEASURED STEAM PRESSURE SIGNAL. T1- MEASURED TEMPERATURE SIGNAL DESIGN PRESSURE (CONSTANT) SAY, 66.0 KG/CM2 &. DESIGN TEMPERATURE (CONSTANT) 485.0 DEG C.
31/07/2012 23:12:16
16
COMBUSTION CONTROL:
INCLUDES:
1. 2. 3. 4. 5. STEAM FLOW OUTLET STEAM PRESSURE O2 % IN FLUE GAS AND PRIMARY AIR FLOW FUEL CHARGING RATE. DRUM LEVEL & FEED FLOW
EXCEPT
31/07/2012 23:12:16
17
31/07/2012 23:12:16
18
Combustion Control
31/07/2012 23:12:16
19
31/07/2012 23:12:16
20
AN INCREASE IN FIRING RATE OF THE BOILER, WHEN IT DROPS; A DECREASE IN FIRING RATE,WHEN IT INCREASES, COMBUSTION CONTROL DOES THIS JOB OF ADJUSTING FIRING RATE BY WAY CONTROLLING FUEL & AIR .
31/07/2012 23:12:16
21
THE STEAM HEADER PRESSURE SIGNAL IS FED TO THE MASTER PRESSURE CONTROLLER.
STEAM FLOW SIGNAL IS FED AS A FEED FORWARD SIGNAL TO THE OUTPUT OF MASTER P.I. C TO COMPUTING BLOCK WHICH ADJUSTS THE OUTPUT w.r.to STEAM FLOW SIGNAL, WHICH IS DISTRIBUTED TO INDIVIDUAL RICE HUSK FEEDER#1 & RICE HUSK FEEDER#2 THROUGH THEIR RESPECTIVE AUTO-MANUAL STATIONS.
BOILER CONTROLS AT "APOGEE-2002" AT BITS PILANI.
22
31/07/2012 23:12:16
THE OUTPUT OF THESE INDIVIDUAL AUTO/MANUAL STATION ARE CONNECTED TO THE RESPECTIVE VARIABLE FREQUENCY DRIVE OF THE RISE HUSK FEEDERS TO CONTROL THE RISE HUSK FEED.
FURTHER THE OUTPUT OF STEAM P.I.C ALSO GOES TO THE AIR-FLOW CONTROLLER AS REMOTE SETPOINT. ON LINE O2 VALUE IS MEASURED BY ANALYSER AND O2 A.I.C OUTPUT CORRECTS THE REMOTE SET POINT VALUE FOR AIR FLOW CONTROLLER IN COMPUTING BLOCK.
31/07/2012 23:12:16
23
AIR FLOW MEASURED BY USING AEROFOIL WHOSE DIFFERENTIAL PRESSURE IS SENSED BY THE AIR FLOW TRANSMITTER SQ. ROOTED IS COMPENSATED TO THE AIR TEMPERATURE AT FUNCTION BLOCK. THE COMPENSATED AIR FLOW ACTS AS PROCESS VARIABLE TO. THE OUTPUT OF FIC POSITIONS THE FD FAN DAMPER ACTUATOR
31/07/2012 23:12:16
24
02 %
2
100%
150%
31/07/2012 23:12:16
25
A WELL MAINTAINED STEAM TEMPERATURE HELPS IN ITS EFFICIENT USAGE DOWN STREAM EITHER TO DRIVE TURBINES OR AS A HEATING MEDIUM.
CONSTANT TEMPERATURE MEANS CONSTANT SPECIFIC VOLUME, THERE BY CONSTANT PRESSURE ON TRANSMISSION OF STEAM THROUGH PIPE LINES.
THE TEMPERATURE OF STEAM IS CONTROLLED BY ATTEMPERATION I.E. BY SPRAYING FEED WATER INTO THE STEAM AFTER THE SUPER HEATER.
31/07/2012 23:12:16
26
HERE S.H I STAGE TIC ACTS AS A FEED FORWARD CONTROLLER. TI FIRST SENSES ANY VARIATION IN TEMPERATURE AND TIC TAKES THE CORRECTIVE ACTION. WHATEVER DEVIATION IS PASSED ON TO, IS SENSED BY I STAGE & II STAGE TEs AND II STAGE TIC WILL TAKE THE CORRECTIVE ACTION BY CHANGING THE OUT PUT,-
- THAT GOES AS REMOTE SETPOINT TO I STAGE S.H.TIC WHICH FURTHER CORRECTS THE TEMPERATURE.
31/07/2012 23:12:16
27
THE TRANSFER SWITCH WHEN SELECTED, ENABLES THE OUTPUT OF T.I.C -TO TRACK THE SIGNAL WHEN THE S.H. OUT LET TEMP. IS < THAN THE RATED TEMPERATURE, SO AS TO AVOID TIC SIGNAL GOING >100%. THE FEED WATER FLOW FOR ATTEMPERATION IS MEASURED & INDICATED IN FI. THE TOTALISER FQ INDICATES THE TOTALISED FLOW.
31/07/2012 23:12:16
28
IT IS ESSENTIAL TO MAINTAIN THE BALANCE BETWEEN FURNACE PRESSURE CAUSED BY COMBUSTION AND SUCTIONAL FORCE GENERATED BY ID/ EXHAUST FAN TO TAKE THIS FLUE GAS OUT OF BOILER. THE MEASURED SIGNAL IS FED TO PRESSURE CONTROLLER.
THE OUTPUT OF CONTROLLER GOES TO THE I.D. FAN DAMPER ACTUATOR AND THE OPERATION OF ID FAN FINALLY CONTROLS THE FURNACE DRAFT. THIS LOOP CONCERNS WITH THE SAFETY OF BOILER& TO PREVENT FURNACE EXPLOSION OR BUCKLING
BOILER CONTROLS AT "APOGEE-2002" AT BITS PILANI.
29
31/07/2012 23:12:16
TO REMOVE THIS O2, WATER IS BOILED IN THE DEAIRATOR BEFORE FEEDING IN TO BOILER.
31/07/2012 23:12:16
30
31/07/2012 23:12:16
31
THE HEATING STEAM PRESSURE IS MAINTAINED BY A CONTROLLER . ITS OUTPUT ACTS ON THE DEAERATOR PRESSURE CONTROL VALVE . .
TO MAINTAIN A CONSTANT LEVEL OF WATER INSIDE THE DEAERATOR IS A MUST FOR EJECTING OUT THE LIBERATED O2 FULLY.
32
SOOT OR CARBON DEPOSITS WASTAGE OF FUEL & COMBUSTION LOSSES AND ESCAPING OF MORE HEAT TO ATMOSPHERE SO, FOR PERIODICAL REMOVAL OF DEPOSITS ON THE SAID PARTS, STEAM IN A CONTROLLED PRESSURE IS USED TO DE-DUST DRUM, W. TUBES, S.H. TUBES. ETC.
BOILER CONTROLS AT "APOGEE-2002" AT BITS PILANI.
33
31/07/2012 23:12:16
PT SIGNAL TO SOOT BLOWER PRESSURE CONTROLLER, MEASURES THE SOOT BLOWER PRESSURE. THE OUTPUT OF PIC ACTS ON THE SOOT BLOWER PRESSURE CONTROL VALVE.
ACTION OF SOOT BLOWER PRESSURE CONTROL VALVE IS AIR TO OPEN TYPE. FAILSAFE ACTION IS CLOSE.
31/07/2012 23:12:16
34
IMPORTANT ASPECTS:
RECRUITMENT OF PROPER INSTRUMENTPERSONNALS TRAINING IN MODERN TECHNIQUES, ON SPECIALISED INSTRUMENTS CALIBRATION & TESTING FELICITIES AND METHODS. DESIGNING AND EQUIPPING WITH A GOOD INSTRUMENT
PREVENTIVE MAINTENANCE TO PREVENT LOSS OF PRODUCTIONS, BREAK DOWN LOSSES AND OTHER WASTAGE.
PREDICTIVE MAINTENANCE SYSTEM, DERIVING THE BENEFIT OUT OF SCADA SYSTEMS AND ITS POTENTIAL TO GENERATE DETAILED ANALYSIS OF PLANT AND PROCESS RELATED EVENTS ON SCREEN.
REMEMBER:
COUNTDOWN TO LAUNCH IS ENSURED BY SAFE LOGIC CONTROLS!!