Chapter 1 Prerequisites for Operation .......................................................................... 5 Hierarchical Design of the SecuriPro Fire Alarm System ................................................. 5 Chapter 2 Operation and Display Devices .................................................................... 7 The operating devices MIC 732 and MIC 734 ................................................................... 7 The operating device MIC 742 ......................................................................................... 14 The fire brigade operating part of the MIC742 ................................................................. 20 The fire brigade operating device FBM 732 ..................................................................... 21 Chapter 3 Operation and Information .......................................................................... 23 Switching the system to present / absent ........................................................................ 23 Operation on detection areas ........................................................................................... 24 Operation on detection zones .......................................................................................... 26 Operation on detectors ..................................................................................................... 29 Local alarm ....................................................................................................................... 32 Alarm transmission ........................................................................................................... 34 Outputs ............................................................................................................................. 36 Inputs ................................................................................................................................ 38 Time .................................................................................................................................. 40 Changing, reprogramming the operator code .................................................................. 41 Context operation ............................................................................................................. 44 Remote Access ................................................................................................................ 45 Chapter 4 Extended Information .................................................................................. 47 Polling the system status ................................................................................................. 47 Polling the event memory ................................................................................................. 48 Polling the maintenance memory ..................................................................................... 49 Polling the alarm counter ................................................................................................. 49 Chapter 5 Procedure for Alarms and Faults ............................................................... 51 Procedure for alarm signal ............................................................................................... 51 Procedure for fault indication ........................................................................................... 53 Chapter 6 Procedure for Different System States ...................................................... 55 Resetting the alarms ........................................................................................................ 55 Resetting the setting deviations ....................................................................................... 56 Chapter 7 Assistance for Troubleshooting ................................................................. 57 Procedure in case of faults ............................................................................................... 57
Chapter 1
Subjects in this chapter
System Securiton AG Building A DA 00__.__ Office 1st floor DZ 0001.__ Building B DA 01__.__ Staircase DZ 0002.__ Office 104 DET 0001.04 Building C DA 02__.__ Office 2nd floor DZ 0003.__ Office 105 DET 0001.05
Note: A fire alarm system may contain up to 96 detection areas. If several main control units (MCU 211) are networked in a system, each one starts with a new fire detection area.
The display of commands and information in these operating instructions is based on a standard configuration. Therefore it does not necessarily conform to the displays and functions available at your device. The larger and the more complex the fire alarm system, the more pages can be called with the softkey [MORE] and assigned to corresponding functions.
Copyright by Securiton AG
Release 05.00
Chapter 2
Subjects in this chapter
The operating devices MIC 732 and MIC 734 The operating device MIC 742 The fire brigade operating part of the MIC742
With the MIC 732 and MIC 734, you can operate the fire alarm system and call information concerning its status. The figure shows the operation device MIC 734.
Figure
Note: The inscription strip is customer-specific and therefore not binding in these Operating Instructions.
Continued on next page
Copyright by Securiton AG
Release 05.00
D E
Legend
Function description Key-operated switch For enabling display and operation Function keys <F1> to <F5> For entering the functions and softkeys displayed Function key "back" and "clear" respectively Undoes a non-acknowledged entry Moves back stepwise in the menu structure (>2sec to root) Display MIC 731: Display with 4 lines at 40 characters each MIC 734: Display with 8 lines at 40 characters each LED Light-emitting diode Individual inscription strip Inscription of the LED Numerical keyboard [ * ] = Terminate numerical input [ # ] = Discard operator code
Continued on next page
A B C
E F G
Copyright by Securiton AG
Release 05.00
[MORE]
[ZOOM]
Building F Cafeteria
[TO]
For processing several objects from - to within the same higher-order unit (e.g. detector zone)
[ENTER] Securiton AG
F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTION ZONE NO. 0001 [TO ] [MORE]
Copyright by Securiton AG
Release 05.00
1st line: 2nd line: 3rd to 6th lines: 7th line: 8th line:
First event or system name with date and time For several event of the same priority, the last one Assignment of the function keys <F1> to <F4> Temporary check-back signals, waiting instructions (busy) etc. Inscription of the softkeys
Below you find an example with the operator code set in the main menu, with 4 specified deviations
1st 2nd 3rd 4th 5th 6th 7th 7th line line line line line line line line 001.SETTING DEVIATION: DZ0002 office 102 004.SETTING DEVIATION: DZ0005 office 105 F1: SETTING DEVIATIONS F2: OPERATION AND INFO F3: EXTENDED INFORMATION [XXXX] [XXXX] [XXXX] [XXXX] [MORE]
Display of events
The priorities for displaying events are set in descending order as follows: Alarm Pre-alarm Fault Set deviation Disconnections Info The display is composed as follows: 001 Fire DZ0001 1st Floor Corridor
001 Event number Each additional event is incremented by 1 Fire Designation of the event (e.g. criterion) DZ0001 1st Floor Corridor System-related des- Object-related designation of the event ignation of the event (e.g. (e.g. detector zone detector zone 0001) "1st Floor Corridor"
Copyright by Securiton AG
Release 05.00
The display is divided into the following 3 operational levels: Display without key Display with key Display with operator code (key required) Possible display without key
Securiton AG 13.02.02 14:54
Possible display with the key turned to the right (with entering a code)
13.02.02
14:54
CODE:
Possible display with the key turned to the right and after entering a code
13.02.02
14:55
[MORE]
Input of commands
Copyright by Securiton AG
Release 05.00
11
The operator code regulates the authorisation for operating the MIC 732 and MIC 734 and is used to identify persons. It consists of a two-digit operator code ID number plus a freely selectable combination of three to six digits. The two-digit ID number is defined in the operator code profile and cannot be changed.
Securiton AG F1: LAMP TEST 13.02.02 14:54
CODE:
Note: The operator code ID numbers are defined during project planning.
Entering the operator code
CODE:
2.
Enter the ID number and your personal operator code (3 to max. 6 digits) via the numerical keyboard
13.02.02
14:54
CODE: ********
3.
Attention: If you have made a typing error, you can discard the entry with the key [ # ] before acknowledgement. Securiton AG 13.02.02 14:55 Acknowledge the entry with the key [ * ] of the numerical F1: OPERATION AND INFO F2: EXTENDED INFORMATION keyboard
A set operator code can be discarded with the key [ # ] of the numerical keyboard
Copyright by Securiton AG
Release 05.00
CODE:
2.
For 5s all points of the display are actuated, all LED's flash, and the buzzer sounds intermittently
Copyright by Securiton AG
Release 05.00
13
With the MIC 742, you can operate the fire alarm system and call information concerning its status. Included is the Swedish fire brigade operating panel according to SS3654 and SS3654 T1 The figure shows the operation device MIC 742.
Figure
Note: The inscription strip in the right part of the operation panel is customer-specific and therefore not binding in these Operating Instructions.
Continued on next page
Copyright by Securiton AG
Release 05.00
DEF
Legend
B C D
E F G H
Function description Operating part for the fire brigade Elements within the rectangular white frame are according to the to Swedish standard SS3654 and SS3654 T1 for fire brigade panel. Refer to chapter The fire brigade operating part of the MIC742 on page 20 in this document. Key-operated switch For enabling display and operation Function keys <F1> to <F5> For entering the functions and softkeys displayed Function key "back" and "clear" respectively Undoes a non-acknowledged entry Moves back stepwise in the menu structure (>2sec to root) Display Display with 4 lines at 40 characters each LED Light-emitting diode Individual inscription strip Inscription of the LED Numerical keyboard [ * ] = Terminate numerical input [ # ] = Discard operator code
Copyright by Securiton AG
Release 05.00
15
Softkeys
[MORE] [ZOOM]
Displays detailed information in lists [ALL] [ UP [DOWN] Displays the next element in lists [UP] Displays the previous element in lists [ALL] Executes the function displayed for all elements in lists Note: Appears only at the end of a list [ENTER] Executes the function dis- Securiton AG <OFF> 01/23 DZ-0023 played Building F Cafeteria [TO] For processing several objects from - to within the same higher-order unit (e.g. detector zone)
13.02.02
14:54
[ENTER] [ UP ] [DOWN] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON DETECTION ZONE NO. 0001 [TO ] [MORE]
Copyright by Securiton AG
Release 05.00
First event or system name with date and time For several event of the same priority, the last one Temporary check-back signals, waiting instructions (busy) etc. Assignment of the function keys <F1> to <F4>
Below you find an example with the operator code set in the main menu, with 4 specified deviations
1st 2nd 3rd 4th line line line line 001.SETTING DEVIATION: DZ0002 office 102 004.SETTING DEVIATION: DZ0005 office 105 F1: SETTING DEVIATIONS [XXXX] [XXXX] [XXXX] [XXXX] [MORE]
Display of events
The priorities for displaying events are set in descending order as follows: Alarm Pre-alarm Fault Set deviation Disconnections Info The display is composed as follows: 001 Fire DZ0001 1st Floor Corridor
001 Event number Each additional event is incremented by 1 Fire Designation of the event (e.g. criterion) DZ0001 1st Floor Corridor System-related des- Object-related designation of the event ignation of the event (e.g. (e.g. detector zone detector zone 0001) "1st Floor Corridor"
Copyright by Securiton AG
Release 05.00
17
The display is divided into the following 3 operational levels: Display without key Display with key Display with operator code (key required) Possible display without key Possible display with the key turned to the right (with entering a code) Possible display with the key turned to the right and after entering a code
Securiton AG 13.02.02 14:54
13.02.02
14:54
CODE: Securiton AG 13.02.02 14:55 F1: OPERATION AND INFO F2: EXTENDED INFORMATION [MORE]
Input of commands
Copyright by Securiton AG
Release 05.00
The operator code regulates the authorisation for operating the MIC 742 and is used to identify persons. It consists of a two-digit operator code ID number plus a freely selectable combination of three to six digits. The two-digit ID number is defined in the operator code profile and cannot be changed.
Securiton AG F1: LAMP TEST CODE: 13.02.02 14:54
Note: The operator code ID numbers are defined during project planning.
Entering the operator code
3.
A set operator code can be discarded with the key [ # ] of the numerical keyboard
Procedure
CODE:
For 5s all points of the display are actuated, all LED's flash, and the buzzer sounds intermittently
Copyright by Securiton AG
Release 05.00
19
The fire brigade operating device is an integrated part of the MIC742 and is used for the standardised alarm handling by the fire brigade in Sweden, according to the standards SS3654 and SS3654 T1
B C D E F
G LED Displays
A Brand Indicates that at least one fire detector is in alarm B Slckanlgging aktiverad Indicates the activation of extinguishing systems C Brandventilation aktiverad Indicates the activation of smoke ventilation systems D Styrutgng aktiverad Indicates the activation of fire incident controls E Larmsndare aktiverad Indicates the activation of alarm transmission units F Ingen function This LED is disabled and has no function G FLERA LARM This indicator activates as soon that more than one fire detector is in alarm H FLERA LARM Scrolls down the alarm list in the LCD starting from the most recent alarm I LARMDOM TYST Resets the alarm acoustic devices of the fire alarm system *) J ATERSTALLNING Resets the fire alarm system *) Note: Functions can be carried out only with the fire brigade key in on position
Continued on next page
Buttons:
*)
Copyright by Securiton AG
Release 05.00
The fire brigade operating device is used for the standardised alarm handling by the fire brigade. Depending on customer requirements, the FBM can however also be operated by the operator and/or caretaker. Displays on the FBM 732: K Alarm L Fault M Alarm transmission activated
Functions on the FBM 732: N Switch off alarm devices O Reset fire alarm system. Note: Functions can be carried out only with the standardised key-operated switch SAE 12600.
Figure FBM 732
Copyright by Securiton AG
Release 05.00
21
Error! Use the Home tab to apply berschrift 2 to the text that you want to appear here., continued
Displays and their meaning
Fault
Fire alarm with immediate transmission with a pushbutton alarm (hand-operated fire alarm) or after a delay or inspection period with automatic detector alarm. The fire alarm system recognizes a fault indication (collective display).
und
In this way all buzzers and acoustical alarm devices are switched off.
und
With this procedure the entire fire alarm system is switched back to the normal operating state.
Copyright by Securiton AG
Release 05.00
Chapter 3
Subjects in this chapter
Switching the system to present / absent Operation on detection areas Operation on detection zones Operation on detectors Local alarm Alarm transmission Outputs Inputs Time Changing, reprogramming the operator code Context operation Remote Access
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for System
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
13.02.02
[MORE] 14:54
4.
13.02.02
14:54
Copyright by Securiton AG
Release 05.00
23
The following functions are present: Switch on and off respectively Poll status Reset
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Detection area
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: RESET DETECTION AREA NO.: __ Securiton AG
13.02.02
[MORE] 14:54
4.
Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired detection area, or first press the softkey [DOWN] if the desired function is not displayed
13.02.02
[MORE] 14:54
F1: DA-00 <ON> Building A F2: DA-01 <ON> Building B F3: DA-02 <ON> Building C [DOWN] [ZOOM] 13.02.02 14:54
5.
Securiton AG
F1: DA-01 <ON> Building B F2: DA-02 <ON> Building C F3: DA-03 <ON> Building D [DOWN] [ZOOM]
Note: Only those detection areas are shown for which the desired function can be executed.
Continued on next page
Copyright by Securiton AG
Release 05.00
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Detection area
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: RESET DETECTION AREA NO.: __ Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: RESET DETECTION AREA NO.: 00 Securiton AG
13.02.02
[MORE] 14:54
4.
Enter the detection area via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit detection areas from - to, and enter the "to" detection area as described above
13.02.02
[MORE] 14:54
5.
F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: RESET DETECTION AREA NO.: 00 ok [MORE]
6.
Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON F3: POLLING STATUS sired function is not displayed F4: RESET
DETECTION AREA NO.: __
14:54
[MORE]
Copyright by Securiton AG
Release 05.00
25
The following functions are present: Switch on and off respectively Switch the smoke part on and off respectively Switch the heat part on and off respectively Poll status Reset
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Detection zone
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
13.02.02
[MORE] 14:54
4.
13.02.02
14:54
5.
DETECTION AREA NO.: __00.00 Securiton AG 13.02.02 F1: DA-00 Building A F2: DA-01 Building B F3: DA-02 Building C
14:54
Copyright by Securiton AG
Release 05.00
7.
F1: DZ-0001 <OFF> Entrance hall F2: DZ-0002 <OFF> Staircase north F3: DZ-0003 <OFF> Staircase south [DOWN] [ZOOM] 13.02.02 14:54
8.
Securiton AG
F1: DZ-0002 <OFF> Staircase north F2: DZ-0003 <OFF> Staircase south F3: DZ-0004 <OFF> Archive [DOWN] [ZOOM] Continued on next page
Copyright by Securiton AG
Release 05.00
27
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Detector zone
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
13.02.02
[MORE] 14:54
4.
Securiton AG
13.02.02
14:54
F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTOR ZONE NO.: ____ Securiton AG 13.02.02 [MORE] 14:54
5.
Enter the detection zones via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit detection zones within a detection area from to, and enter the "to" detector zone as described above
F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTOR ZONE NO.: 0001 Securiton AG [TO] [MORE] 13.02.02 14:54
6.
F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTOR ZONE NO.: 0001 ok [MORE]
7.
Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON F3: SWITCH OFF SMOKE PART sired function is not displayed F4: SWITCH ON SMOKE PART
DETECTOR ZONE NO.: ____
14:54
[MORE]
Copyright by Securiton AG
Release 05.00
Operation on detectors
Standard functions
The following functions are present: Switch off/on Exchange Switch off/on smoke part Switch off/on heat part Poll status Reset Disconnect/Connect
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Detector
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
13.02.02
[MORE] 14:54
4.
13.02.02
14:54
5.
DETECTION AREA NO.: __00.00 Securiton AG 13.02.02 F1: DA-00 Building A F2: DA-01 Building B F3: DA-02 Building C
14:54
6.
Press the function key for the desired detection area, or first press the softkey [DOWN] if the desired function is not displayed
Copyright by Securiton AG
Release 05.00
29
8.
Press the function key for the desired detector zone, or first press the softkey [DOWN] if the desired detector zone is not displayed Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired detector, or first press the softkey [DOWN] if the desired detector is not displayed
Securiton AG
F1: SWITCH OFF F2: SWITCH ON F3: EXCHANGE F4: SWITCH OFF SMOKE PART DETECTOR NO.: 0001.__ Securiton AG 13.02.02 14:54
9.
F1: DET-0001.01 <DISCONNECT> front F2: DET-0001.02 <DISCONNECT> middle F3: DET-0001.03 <DISCONNECT> rear [DOWN] [ZOOM] 13.02.02 14:54
10.
Securiton AG
F1: DET-0001.02 <DISCONNECT> middle F2: DET-0001.02 <DISCONNECT> rear [DOWN] [ZOOM] Continued on next page
Copyright by Securiton AG
Release 05.00
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Detector
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
13.02.02
[MORE] 14:54
4.
Securiton AG
13.02.02
[MORE] 14:54
F1: SWITCH OFF F2: SWITCH ON F3: EXCHANGE F4: SWITCH OFF SMOKE PART DETECTOR NO.: ____.__ Securiton AG 13.02.02 [MORE] 14:54
5.
Enter the detector number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit detectors within a detector zone from - to, and enter the "to" detector as described above
F1: SWITCH OFF F2: SWITCH ON F3: EXCHANGE F4: SWITCH OFF SMOKE PART DETECTOR NO.: 0001.01 Securiton AG [TO] [MORE] 13.02.02 14:54
6.
F1: SWITCH OFF F2: SWITCH ON F3: EXCHANGE F4: SWITCH OFF SMOKE PART DETECTOR NO.: 0001.01 ok [MORE]
7.
Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON F3: EXCHANGE sired function is not displayed F4: SWITCH OFF SMOKE PART
DETECTOR NO.: ____.__
14:54
[MORE]
Copyright by Securiton AG
Release 05.00
31
Local alarm
Standard functions
The following functions are present: Switch on and off respectively Poll status Reset Switch maintenance on and off
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Local alarm, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired local alarm, or first press the softkey [DOWN] if the desired function is not displayed
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: __ Securiton AG F1: F2: F3: F4: AE-01 AE-02 AU-03 AU-04
13.02.02
[MORE] 14:54
4.
13.02.02
[MORE] 14:54
BUZZER [OFF] BUZZER ALARM BUZZER [OFF] BUZZER FAULT BUZZER [OFF] BUZZER PREALARM AU [OFF] SIREN 13.02.02 [DOWN] 14:54
5.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: __
Copyright by Securiton AG
Release 05.00
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Local alarm, or first press the softkey [MORE] if the desired function is not displayed Enter the local alarm number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit local alarms from - to, and enter the "to" local alarm as described above
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: __ Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: 01 Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: 01 ok
13.02.02
[MORE] 14:54
4.
13.02.02
[MORE] 14:54
5.
[MORE]
6.
Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON F3: POLLING STATUS sired function is not displayed F4: MAINT. SWITCH ON
LOCAL ALARM NO.: __
14:54
[MORE]
Copyright by Securiton AG
Release 05.00
33
Alarm transmission
Standard functions
The following functions are present: Switch on and off respectively Poll status Reset Switch maintenance on and off
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Alarm transmission, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired alarm transmission, or first press the softkey [DOWN] if the desired function is not displayed
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG
13.02.02
[MORE] 14:54
F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: __ Securiton AG F1: F2: F3: F4: TU-01 TU-02 TU-03 TU-04 TU TU TU TU <OFF> <OFF> <OFF> <OFF> 13.02.02 FIRE FIRE MCP FAULT SC SYSTEM [DOWN] [ZOOM] 13.02.02 14:54 [MORE] 14:54
4.
5.
Securiton AG
F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: __
[MORE]
Copyright by Securiton AG
Release 05.00
Alarm transmission
, continued
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Alarm transmission, or first press the softkey [MORE] if the desired function is not displayed Enter the local alarm transmission number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit alarm transmissions from - to, and enter the "to" alarm transmission as described above
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG
13.02.02
[MORE] 14:54
F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: __ Securiton AG 13.02.02 [MORE] 14:54
4.
F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: 01 [TO] Securiton AG 13.02.02
[MORE] 14:54
5.
F1: SWITCH OFF F2: SWITCH ON F3: POLL STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: 01 ok [MORE]
6. 7.
Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON F3: POLL STATUS sired function is not displayed F4: MAINT. SWITCH ON
ALARM TRANSMISSION NO.: __
14:54
[MORE]
Copyright by Securiton AG
Release 05.00
35
Outputs
Standard functions
The following functions are present: Switch on and off respectively Poll status Switch maintenance on and off
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Outputs, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired function, or first press the softkey [ZOOM] if the desired function is not displayed Press the function key for the desired output, or first press the softkey [ZOOM] if the desired function is not displayed
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: ___ Securiton AG
13.02.02
[MORE] 14:54
4.
13.02.02
[MORE] 14:54
F1: OUT-001 [OFF] IOM LB1 ACTIVATED F2: OUT-002 [OFF] IOM LB1 ACTIVATED F3: OUT-003 [OFF] IOM LHT ACTIVATED [DOWN] [ZOOM] 13.02.02 14:54
5.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: ___
Copyright by Securiton AG
Release 05.00
Outputs , continued
Procedure with numerical entries
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Outputs, or first press the softkey [MORE] if the desired function is not displayed Enter the output number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit outputs from - to, and enter the "to" output as described above
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: ___ Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: 001 Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: 001 ok
13.02.02
[MORE] 14:54
4.
13.02.02
[MORE] 14:54
5.
[MORE]
6. 7.
Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON F3: POLLING STATUS sired function is not displayed F4: MAINT. SWITCH ON
OUTPUT NO.: ___
14:54
[MORE]
Copyright by Securiton AG
Release 05.00
37
Inputs
Standard functions
The following functions are present: Switch on and off respectively Poll status
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Inputs, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired function, or first press the softkey [ZOOM] if the desired function is not displayed Press the function key for the desired input, or first press the softkey [DOWN] if the desired function is not displayed
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: ___
13.02.02
[MORE] 14:54
4.
Securiton AG
13.02.02
[MORE] 14:54
F1: IN-001 [OFF] Extinguisher released F2: IN-002 [OFF] Extinguisher fault
5.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: ___
Copyright by Securiton AG
Release 05.00
Inputs , continued
Procedure with numerical entries
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Inputs, or first press the softkey [MORE] if the desired function is not displayed Enter the input number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit inputs from - to, and enter the "to" input as described above
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: ___
13.02.02
[MORE] 14:54
4.
Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: 001 Securiton AG F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: 001 ok
13.02.02
[MORE] 14:54
5.
[TO]
[MORE]
6. 7.
Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON F3: POLLING STATUS sired function is not displayed
INPUT NO.: ___
14:54
[MORE]
Copyright by Securiton AG
Release 05.00
39
Time
Standard functions
Procedure
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Time, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Time input
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
13.02.02
[MORE] 14:54
4.
Securiton AG F1: TIME INPUT F2: DATE INPUT TIME INPUT: 14:54:49
13.02.02
14:54
5.
Enter the correct time via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the function key for Date input
13.02.02
14:54
6.
Securiton AG F1: TIME INPUT F2: DATE INPUT DATE INPUT: 13.02.02
13.02.02
14:54
7.
Enter the correct date via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard
13.02.02
14:54
Copyright by Securiton AG
Release 05.00
2.
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTION ZONE DETECTOR
13.02.02
14:54
3.
Press the function key for Code, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Change
13.02.02
[MORE] 14:55
4.
13.02.02
14:55
5.
Enter the new operator code without operator code ID (3 to max. 6 digits) via the numerical keyboard
13.02.02
14:55
6.
Attention: If you have made a typing error, you can discard the entry with the key <CLEAR> before acknowledgment. Securiton AG 13.02.02 14:55 Acknowledge the entry with the key [ * ] of the numerical F1: CHANGE keyboard
CONFIRM PCODE
------
7.
13.02.02
14:55
Copyright by Securiton AG
Release 05.00
41
Copyright by Securiton AG
Release 05.00
To reprogram an operator code, proceed stepwise as follows: Note: You need the appropriate authorisation to reprogram an operator code.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG F1: OPERATION AND INFO F2: EXTENDED INFORMATION 13.02.02 14:55
2.
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTION ZONE DETECTOR
13.02.02
14:54
3.
Press the function key for Code, or first press the softkey [MORE] if the desired function is not displayed Press the function key for New programming
13.02.02
[MORE] 14:55
4.
13.02.02
14:55
5.
Enter the existing operator code ID and the new operator code (3 to max. 6 digits) via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard
13.02.02
14:55
6.
13.02.02
14:55
7.
13.02.02
14:55
Copyright by Securiton AG
Release 05.00
43
Context operation
Procedure
Context operation, also called alternative operation, is a form of operation meant to facilitate switch on, switch off, disconnect and connect operations. This means: If one tries to again switch off an already switched off detector zone, the system proposes to switch on this detector zone. If one tries to again switch on a detector zone with bad AR (e.g. smashed pushbutton glass), the system proposes partial switching off of this detector zone. Note: You need the appropriate authorisation to reprogram an operator code.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG F1: OPERATION AND INFO F2: EXTENDED INFORMATION 13.02.02 14:55
2.
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTION ZONE DETECTOR
13.02.02
14:55
3.
Try to switch on a zone (or a detector) which is already switched on. Press <F1> [COMMAND] Press <F1> [ENTER] in order to carry out the context operation
Securiton AG 01/01 DZ-0001 ALREADY ON BUILDING A STAIRCASE NORD DETECTION ZONE-NO: 0001 [COMMAND] Securiton AG 01/01 DZ-0001 ALREADY ON BUILDING A STAIRCASE NORD DETECTION ZONE-NO: 0001 [ENTER]
4.
13.02.02 14:55
Copyright by Securiton AG
Release 05.00
Remote Access
Standard functions
The following functions are present: Release remote access Delete Installer Password
Procedure
Step 1.
Procedure Turn the key to the right Enter your personal operator code
Process/reading on display
Securiton AG F1: OPERATION AND INFO F2: EXTENDED INFORMATION 13.02.02 14:54
2.
Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Remote Access, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG F1: F2: F3: F4: SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR
13.02.02
14:54
3.
Securiton AG
13.02.02
[MORE] 14:54
4.
Securiton AG
13.02.02
14:54
Copyright by Securiton AG
Release 05.00
45
Chapter 4
Subjects in this chapter
Extended Information
Polling the system status Polling the event memory Polling the maintenance memory Polling the alarm counter
The following functions are present: Polling the pre-alarm, alarm and fault lists Polling the setting deviations Polling the disconnections Polling In maintenance Polling bad switch-on check Polling bad arming readiness
Procedure
2.
3.
4.
Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG
[MORE] 14:54
01/02 DZ-0001 SETTING DEVIATION entranc 02/02 DZ-0003 SETTING DEVIATION stairca
[ZOOM]
Copyright by Securiton AG
Release 05.00
47
The following functions are present: Polling Print all Print alarms Print faults Print on/off switchings Print last 100 events
Procedure
2.
Press the function key for Extended information, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Event memory
Securiton AG F1: F2: F3: F4: SYSTEM STATUS EVENT MEMORY ALARM MEMORY MAINTENANCE MEMORY
13.02.02
14:54
3.
Securiton AG F1: F3: F3: F4: POLLING PRINTS ALL PRINTS ALARMS PRINTS FAULTS
13.02.02
14:54
4.
Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG 01: 02: 03: 04 DZ-0006 DZ-0005 DZ-0004 DZ-0003 SWITCHED SWITCHED SWITCHED SWITCHED ON ON ON ON
[P-DOWN][ UP ]
[DOWN]
[ZOOM]
Copyright by Securiton AG
Release 05.00
2.
Press the function key for Extended information, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Maintenance memory
Securiton AG F1: F2: F3: F4: SYSTEM STATUS EVENT MEMORY ALARM MEMORY MAINTENANCE MEMORY
13.02.02
14:54
3.
Securiton AG
13.02.02
14:54
2.
Press the function key for Extended information, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Alarm counter
Securiton AG F1: SYSTEM STATUS F2: EVENT MEMORY F3: ALARM COUNTER
13.02.02
14:54
3.
Securiton AG
13.02.02
14:54
Copyright by Securiton AG
Release 05.00
49
Chapter 5
Subjects in this chapter
During this lag phase, it is possible to effect another delay of 5 minutes by pressing the corresponding function key INSPECTION. Alarm messages from hand-operated fire alarms are always transmitted to the fire brigade directly and without delay.
Continued on next page
Copyright by Securiton AG
Release 05.00
51
If an alarm is signaled in the "Present" state, i.e. without immediate transmission to the fire brigade, proceed stepwise as described below. Display on the FBM 732: Attention: Also mind the indications on the PIM 731 and the group alarm indication on the PIM 734.
Possible reading on the MIC 732 or MIC 734 display
001 FIRE DZ0002 1ST FLOOR CORRIDOR F1: SWITCH OFF BUZZER F2: ALARM LIST
Step 1.
Process/reading on display
001 FIRE DZ0002 1ST FLOOR CORRIDOR F1: F2: F3: F4: INSPECT ALARM LIST ABSENT LAMP TEST [MORE]
2.
3.
Note: The delay period of 3 minutes counts from the triggering of the alarm until its transmission to the fire brigade Press the function key for Inspect Go to the source of the fire Note: The inspection time lasts 5 minutes The alarm is transmitted immediately. If the alarm is genuine: Press the nearest pushbutton 001 FIRE DZ0002 1ST FLOOR CORRIDOR If the alarm is false: F1: INSPECT Turn the key to the right F2: RESET SYSTEM F3: ALARM LIST Enter your personal operator F4: OPERATION AND INFO code
[MORE]
Copyright by Securiton AG
Release 05.00
If a fault is indicated, proceed stepwise as follows. Display on the FBM 732: Attention: Also pay attention to the group fault indication on the PIM 731 On the FBM, faults cannot be acknowledged!
Possible reading on the MIC 732 or MIC 734 display
001 FIRE DZ0002 1ST FLOOR CORRIDOR F1: SWITCH OFF BUZZER F2: FAULT LIST
Step 4.
Process/reading on display
001 FAULT DZ0099 SYSTEM FAULT F1: F2: F3: F4: SWITCH OFF REMOTE ALARM RESET SYSTEM FAULT LIST OPERATION AND INFO [MORE]
Copyright by Securiton AG
Release 05.00
53
Chapter 6
Subjects in this chapter
The following functions are possible: Switch off buzzer (without operator code) Inspect (without operator code) Switch off local alarm Switch off alarm transmission Reset system Poll pre-alarm Poll alarm Poll fault list Info list Maintenance list
Procedure
2.
Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed The system is reset
001. Fire: DZ0001 Entrance hall F1: RESET SYSTEM F2: ALARM LIST F3: OPERATION AND INFO F4: EXTENDED INFORMATION DA-00 ACKNOWLEDGED Securiton AG F1: OPERATION AND INFO F2: EXTENDED INFORMATION 13.02.02 14:54
Copyright by Securiton AG
Release 05.00
55
2.
Press the function key for Setting deviations, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired set deviation, or first press the softkey [DOWN] if the desired set deviation is not displayed
001. SETTING DEVIATION: DZ0001 Entrance 004. SETTING DEVIATION: DZ0004 Archive F1: DZ0001 <ON> Entrance hall F2: DZ0002 <ON> Staircase north F3: DZ0003 <ON> Staircase south [DOWN] [ZOOM] 001. SETTING DEVIATION:: DZ0001 Entrance hall 004. SETTING DEVIATION:: DZ0004 Archive F1: DZ0002 <ON> Staircase north F2: DZ0003 <ON> Staircase south F3: DZ0004 <ON> Archive [ZOOM]
Copyright by Securiton AG
Release 05.00
Chapter 7
Subjects in this chapter
The table below shows a list of frequently occurring faults and offers help for their correction: Note: If the fault cannot be corrected by these means, call your service company.
Kind of fault Fault of a specific detector Possible cause Detector optics defective Defective electronics Battery defective or not charged Power failure > 1 hour Correction Replace detector Wait 5 minutes Reset fault Call Service
Short to earth
Communication fault
Fault SI300 (FA) SI302 (DIVERS) SI302 (OA1) SI303 (OA1) SI303 (OA2) SI304 (LAN1)
Wait until power is switched on again Reset fault Circuit breaker activated Switch circuit breaker on Reset fault Power supply unit defective Call Service Short-circuit to earth, e.g. Call Service Water in a detector Leakage currents by soiling Electromagnetic disturCall Service bances System overload Defective LAN device Fuse faults in MCU Call Service
SI305 (LAN2)
Continued on next page
Copyright by Securiton AG
Release 05.00
57
LAN channel A fault LAN channel B fault System cannot be reset following an alarm Common alarm LED alarm is not reset
Copyright by Securiton AG
Release 05.00