Sie sind auf Seite 1von 2

MinutesofMeeting

Subject: MeetingDate: Location: InviteesPresent: CEB SitesurveyforControlandprotectionpanel132/33kVGSS,AmparaSS,CEB 13.12.2011,14.12.2011,16.12.2011 Ampara,Colombo,SriLanka

ABBLtd.,

Mr.Nishantha,PM(TSSEPP) Mr.Kuruppu,EE(TSSEPP) Mr.Jeewagan,EE(TSSEPP) Mr.MohanS Mrs.MeghaD

TopicsdiscussedandSiteObservations
1 Lineupforcontrolpanelsfor132kVand33kVshallbeinlinewithSLD Pleasefindproposedlineupenclosed.Finallineupshallbeprovidedinthedetaileddesign. Annunciatorwindowsshallbeprovidedintheexistingannunciatorpanelforthenewfeeders.Incaseofnon availabilityofspacenewannunciationpanelshallbeprovided.Thisshallmatchwiththeexistingpanel.Spare 2 faciasshallbeprovidedforfuturerequirement. 3 Synchronizing Synchronizingsocketsimilartotheexistingoneshallbeprovidedinprotectionpanelsforsynchronizing dependingonavailabilityofsamesocketornewarrangementshallbeproposedwiththetrolley. 4 Raise/lowercommandsandAuto/manualselectionfortapchangingtobeprovided. 5 Parallelingofthreetrafoshallbeprovidedwithnecessaryinterlocks 6 LocalbreakerfailureON/OFFswitchprovisionshallbemadeineachrelaypanelincludingexistingpanel 7 PaintshadeshallbeRAL7032(asperexisting)interiorandexterior Plugsocket(AMPmake)arrangementisprovidedinexistingControlandSCADAinterfacepanelonly.Typeof terminationfornewpanelsshallbeconfirmedbyABBltd.,iftheexistingPlugandsocketisnotavailablenew 8 plugsocketshallbeproposed. 9 Capacitorcontrol&protectionpanel(includingannunciationandmimic)shallbeoffrontaccess. 10 ETandauxtrafotobeincludedinthemimicfornewpanel. 11 MimicsshalbestickerstypeforAmparaSS. Auxvoltagesare48vDC(foundinalarms+Tapchanger),220vDC(forcontrol).Aux.voltagerequirementshall 12 coordinatedwiththeexistingreferencetakenfromCEB 13 CEBrequestedforsimilarswitch(descrepancy,rotary),metersandindicationaspertheexistingpanel. Sincecounterforautotripandmanualtripisnotprovidedinexistingpanelandduetospaceconstraintsame 14 shallnotbeprovidedinAmparaSS.ButthesecoutersshallbeprovidedinValachnaiSS SSS(synchronizingselectorswitch)andAutomanualswitchshallbeprovidedforsynchronizing.Sameshallbe finalizedinthedetaileddesign 15 Auto/reclosingswitchisprovidedintheexistingGISpanelandthesameshallbeprovidedinnewpanelas 16 well. 17 LoadsheddingrelayandloadsheddingON/OFFswitchshallbeprovidedinexistingaswellasnewpanels. 18 ValachnaiSSpanelshallbesuitableforSCADAinterface. 19 ValachnaiSSpanelshallbeconventionalcontrolandBCUcontrol ValachnaiSSSeparateSCADAInterfacepanelshallbeprovidedsimilartoAmparaSS.TobeFreezedasperthe 20 requirement. 21 ValachnaiSS33kVcontrolandprotectionpanelshallbefrontaccess. 22 ValachnaiSS132kVcontrolpanelincludingannunciatorforeachbayshallbefrontaccess. ValachnaiSSMeteringpanelshallbeprovidedseparatelyonefortariffmetering(TRANSCO)andonefor 23 checkmetering(DISCO) 24 Alarmsoundsshallbedifferentincapacitorpanelsandannunciationpanel.

ProposedlineupforcontrolpanelsforAmparaSS Existinglineup f2 f3 newspaceavailable=1400mm trafo3 f7 f8 f9

ann.Facia blank

blank

trafo1

b/s1

trafo2

line

blank

blank

blank

f1

t1

b/s2

t2

f4

f5

f6

blank

blank

blank

b/s3

f10

cap3

trafo3

cap1

132kvlineup

33kvlineup

cap2

33kVlineup