OF GENARATORS AND
EXCITERS
PROBABLE REASONS
MOSTLY DUE TO MECHANICAL DAMAGE OF INSULATION DURING ASSEMBLY AND DISASSEMBLY, OVERHAULING ETC. LOOSE CORE VIBRATION LEADING TO RUBBING OF INSULATION LOOSE / DAMAGED CORE LEADING TO INTENSE LOCALISED HEATING AND CHARRING OF INSULATION
PROBABLE REMEDIES
CARE SHOUD BE TAKEN DURING ASSEMBLY AND DISASSEMBLY TO AVOID ANY MEACHANICAL DAMAGE TO WINDING ATTENDING TO LOOSE CORE DURING OVERHAULING MONITORING OF ALL WINDING AND CORE TEMPERATURES SUDDEN SHORT CORCUIT PROTECTION
CRACK DAMAGE OF TROUGHS OR DAMAGE OF INSULATION UNDER REATINING RINGS LEADING TO ROTOR EARTH FAULT
PROBABLE REASONS
SHIFTING OF INTERTURN INSULATION CRACK / CHARRING OF INSULATION DUE TO MECHANICAL DAMAGE / OVERHEATING
PROBABLE REMEDIES
MONITORING OF ROTOR IMPEDENCE VALUES AT REGULAR INTERVALS REMOVAL OF RETAINING RINGS AND RECTIFICATION
PROBABLE RASONS
HIGHER SCRAPPER FINS CLEARANCES
PROBABLE REMEDIES
PROPER ADJUSTMENT OF SCRAPER FIN CLEARANCES DURING OVERHAULING AS PER DESIGN VALUES
REPLACEMENT OF WORN OUT SCRAPERS
PROBABLE REASONS
HIGHER BEARING CLEARANCES DAMAGE IN BEARING BABBIT ROTOR BALANCE GOT DIATURBED
PROBABLE REMEDIES
ADJUST BEARING CLEARANCES, REPLACE IN CASE OF BABBIT DAMAGE
ABNORMAL OPERATION
PROBLEM
ABNORMAL OPERATIONS LIKE MOTORING, PRESENCE OF FOREGN OBJECTS INSIDE THE GENERATOR
PROBABLE REASONS
ACCIDENTAL CLOSURE OF GENERATOR CB LEADING TO MOTORING
PROBABLE REMEDIES
PROPER MAINTENANCE OF CB THOROUGH INSPECTION OF GENERATOR STATOR AND ROTOR BEFORE CLOSING OF END COVERS FOR POSSIBILITY OF PRESENCE OF FOREIGN OBJECTS
EXCITER PROBLEMS
PROBLEM
LOOSENING OF PMG STATOR FROM THE YOKE
PROBABLE REASONS
INSUFFICIENT LOCKING OF PMG
OVERVOLTAGE ACROSS DIODES MECHANICAL DAMAGE OF WINDING
PROBABLE REMEDIES
PROPER LOCKING OF PMG REPLACEMENT OF DIODE / FUSE