MAIN POWER SUPPLY CHARACTERISTICS 1 2 3 4 5 6 7 8 INCOMING SUPPLY VOLTAGE SUPPLY FREQUENCY COMBINED VARIATION MAX SHORT CIRCUIT LEVEL

AT 11KV MIN SHORT CIRCUIT LEVEL AT 11KV MAX ALLOWABLE VOLTAGE DIP MAX HARMONIC CONTENT MINIMUM POWER FACTOR METHOD OF STARTING POWER REQUIREMENT OF LARGEST MOTOR MOTOR POWER FACTOR MOTOR LOCKED ROTOR CURRENT IN % AUTO TRANSFORMER TAP SETTING IN % MAGNETISING INRUSH MULTIPLIER FOR AUTO TRANSFORMER (a) VALUE OF "e" 33 50 10 15 7.8 3.50 1 2 17531 KW 0.98 450 % 70 % 0.2 2 KV Hz KA / 3sec KA % + 10% + 5%

9 10 11 12 13

CALCULATIONS 1 SYSTEM MIN SHORT CIRCUIT MVA (S) 2 SYSTEM MAX SHORT CIRCUIT MVA 3 MOTOR FULL LOAD CURRENT 4 MOTOR BASE MVA (Mb) 5 TAP POSITION OF AUTO TRANSFORMER (Z) 6 STARTING CURRENT MULTIPLIER (y) 7 VOLTAGE DIP WHILE STARTING LARGEST MOTOR USING AUTOTRASFORMER WILL BE (Vd) =

445.83 857.37 939 17.89 0.7 4.5

MVA MVA A MVA

1 1+ S / [Mb (a + Z e y)] 8.80 %

Please recalculate, Dip exceeds limits specified