Document No: 1MDV07203-YN Issued: July 2007 Version A Data subject to change without notice NI 40/41 Numerical Three phase Over current and Earth Fault Relay
Contents
Sr. No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Description About this manual The use of the relay Feature application Brief description of operation Connection diagram Power supply module and output relay card HMI features Menu systems Main Menu Group menu, subgroup menu and Parameter menu. Measurements Recorded data Settings Configuration Time current characteristics Technical Data Maintenance & Repair Internal relay failure Dimensions and mounting Ordering Details
Page No. 3 3 3 4 4 6 10 11 14 14 14 15 17 22 27 32 37 41 41 41 42
Features
Protection functions Three-phase over current protection low-set stage (IDMT or DT) Three-phase over current protection, high -set stage (DT) Earth fault protection, low-set stage (IDMT or DT) Earth fault protection, high-set stage (DT) Facility of site selection of IDMT curves for low set stage Four standard IDMT curves (NI, VI, EI, LI) as per IEC standard. Wide and accurate numerical settings with perfect long time stability. Measurement, Monitoring and Recording Function Measuring of 3 Phase current in primary or secondary terms Measurement of Neutral current in primary or secondary terms. Latest Five fault data recording Extensive relay internal self supervision monitoring relay hardware and software. Trip lockout function Display and Indications 16 x 2 Alpha numeric LCD display with backlit Aux. supply on, Fault alarm / trip, Internal Relay Failure indication LED's Display of fault cause indication Inputs and Outputs Four accurate current inputs Normally open heavy duty output contacts Two change over signaling output contacts Freely configurable output contacts Dedicated output contact for relay internal self supervision Low burden on current transformer Relay Design Relay case with a degree of protection according to IP54 Design confirming to requirements of IEC 60255 Design immune to any kind of electromagnetic interference Dimensions: 196 (H) x 166 (W). Depth behind panel only 158 mm. X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X ANSI Code 51 50 51N 50N X X X X NI40 X MODEL NI41 X X X X X X X
Application
This composite relay facilitates combined three phase over current and neutral current relay functions for use with selective short-circuit and time-over current protection of distribution feeders. It can also be applied to feeder earth fault protection in solidly earthed, resistance earthed and isolated neutral networks. As multi-function solutions, these relays can be flexibly adapted to different kind of incoming and outgoing feeders in varying substation environments. The NI 40/41 series of relays can be used for protection of feeders of utility and industrial applications. With its compact size and unique technical features, NI 40/41 is an ideal relay for retrofit, small switchgear and switchgear with limited space. A small mounting depth makes it possible to install the relay in places where space is money and every millimeter counts.
IL1
TRIP
IL2
THREE PHASE INVERSE TIME OR DEFINITE TIME LOW SET OVER CURRENT PROTECTION
51
SIGNAL 1
IL3
THREE PHASE INVERSE TIME OR DEFINITE TIME LOW SET EARTH FAULT PROTECTION
SIGNAL 2 51N
Io
IRF
Figure 1: Protection function of Three phase over current and earth fault relay Type NI 40
IL1
THREE PHASE INVERSE TIME OR DEFINITE TIME LOW SET OVER CURRENT PROTECTION
TRIP 51
IL2
THREE PHASE INSTANTANEOUS OR DEFINITE TIME HIGH SET OVER CURRENT PROTECTION
SIGNAL 1 50
IL3
THREE PHASE INVERSE TIME OR DEFINITE TIME LOW SET EARTH FAULT PROTECTION
SIGNAL 2 51N
Io
THREE PHASE INSTANTANEOUS OR DEFINITE TIME HIGH SET EARTH FAULT PROTECTION
IRF 50N
Figure 2: Protection function of Three phase over current and earth fault relay Type NI 41
Connection diagram
Figure 3
Connection diagram for three phase Numerical overcurrent and earth fault relay type NI 40/41 with core balance CT for earth fault.
IRF
Connection diagram
Figure 4
Connection diagram for three phase Numerical overcurrent and earth fault relay type NI 40/41 with residual connection of CTs for earth fault.
Auxiliary voltage Output relays Self-supervision (Internal relay failure) Trip output relay Signal on operation of the overcurrent / Earth fault unit Signal on operation of the overcurrent / Earth fault unit Power On indication IRF indication Start / Trip Indication
Figure 5 Terminal arrangement of Numerical three phase over current and earth fault relay Type NI 40/41
The energizing currents of the over current unit are connected to terminals R1-R2, Y1-Y2 & B1B2 The relay can also be used in single-phase or two-phase applications simply by leaving one or two energizing inputs unoccupied. The energizing current for the earth-fault unit is connected to terminals E1-E2. The auxiliary supply voltage of the relay is connected to terminals 14-16. At d.c. supply the positive lead is connected to terminal 16. The level of the voltage to be applied to the terminals depends on the type of power supply module . Available levels are 18-80v DC or 80-265v AC/DC. For further details earth see the description of the power supply module. The permitted auxiliary voltage range of the relay is marked on the relay front panel. Output relay Tr is a heavy-duty trip relay capable of controlling most circuit breakers. The operate signals of the different protection stages are routed to the trip relay by selecting relay configuration inside the main menu of the relay and routing the desired relay for that
protection function. On delivery from the factory all the protection stages are routed to the trip relay. A latching of the output relay Tr can be selected by setting the configuration of TRIP as HR (Hand Reset). Output relays S1 and S2 can be used for signaling on operation of the relay module. The signals to be routed to the output relays S1 and S2 is carried out by selecting relay configuration submenu in Configuration menu and then routing over current or earth fault for desired signaling relays S1& S2 Both signaling relays, S1 & S2 are configured for signaling on operation of the over current unit and earth fault unit which is the default setting of the relay on delivery from the factory. Output relay IRF functions as output relay for the self-supervision system of the protection relay. The relay IRF is energized under normal operating conditions and contact gap 27-28 is closed. If a fault is detected by the selfsupervision system, or on loss of auxiliary supply, the output relay drops off and the NO contact 28-29 closes.
Signal Diagram
Figure 6
The figure below schematically illustrates how the trip and control signals can be configured to obtain required protection function.
10
Signal Abbreviation
Energizing current of phase L1, L2 & L3 Neutral Current (Residual Current) Trip relay Signal Relay 1 Signal Relay 2 Internal relay Failure
7.
A green LED indicator POWER ON on the system front panel is lit when the power supply module is in operation. The supervision of the voltages supplying the electronics is located in the power supply module. If a secondary voltage differs too much from its rated value, a self-supervision alarm will be generated. An alarm is also issued on loss of auxiliary supply. There are two versions of power supply modules available. For both types, the secondary sides and the relay driver circuits are identical, but the input voltage ranges differ.
Insulation test voltage between the primary and secondary side and the protective earth 2 kV, 50 Hz, 1 min Rated power Pn 5W Voltage ranges of the power supply modules : 1. Uaux = 80...265 V dc/ac 2. Uaux = 18...80 V dc The power supply module for 80...265v can be fed from either an ac source of a dc source. The 18...80V power supply module is designed for dc supply only. The permitted auxiliary voltage range of the relay is marked on the relay system front panel.
11
HMI features
Front panel
The front panel of the protection relay includes: An alphanumeric 16 x 2 characters LCD (Liquid crystal display) with backlight which makes the local use of the relay safe and easy. Three indicator LEDs (Green, Red, Green/Red) An HMI push button section with four arrow buttons and buttons for clear/cancel and enter
1 2 3
Figure 8 Front view of Numerical three phase overcurrent and earth fault relay Type NI 40/41 1 2 3 LCD HMI push button section Indicator LEDs: 4 Top: Power On (green) Middle: IRF (Red) Bottom: Alarm (Green) / Trip (red)*
Voltage rating, Current rating, Article No., Relay Serial No. details
Figure 9
* In order to reset the trip indicating LED press Enter Key [E] and left arrow button [ ]for three seconds after entering the main menu.
12
The next table gives short explanations of the push-buttons and their functions. Table 1. Push Button functions
Key Functions
Left Key - Used to come out of the given sub-menu - Also used to change the digit location to left in settings mode
Up Key - Used to scroll up in the menu/sub menu - Also used to increment the value of the digit in settings menu Down Key - Used to scroll down in the menu/sub-menu - Also used to decrement the value of the digit in settings menu
Right Key - Used to go inside the given menu/sub-menu - Also used to change the digit edit location to right in settings mode
Escape Key - Used to come at the top of the menu from anywhere
Password Key - Used to enter the edit mode in Settings and Configuration menu
13
Display modes
When the display is in idle mode, the dynamic values of phase and earth current will be displayed in secondary terms per unit values.
Figure 10 Display in idle mode When the display is in the view mode, you can only view the parameters. The below figure shows current in phase L1 in primary terms.
When the display is in the setting mode, you can also edit the settings.
Figure 12 Display in setting mode Display backlight Normally the backlight of the display is off. The backlight is lit in approx 5 sec. after pressing any arrow button on the HMI. This displays ABB on the LCD. If the HMI panel is not used for approximately ten seconds, the backlight will be turned off automatically, and relay will resume idle mode.
14
9.
Menu system
The menus are used for reading and setting the parameters, reading recorded values, and so forth. The menu system is divided into three or four levels (depending on the parameters): MAIN MENU Group menu Subgroup menu Parameter menu
10.
Main menu
The main view is the MAIN MENU, which is followed by the hierarchical structure of group, subgroup and parameter menus. In all menu levels, the first row of the display is dedicated for the header text that shows the name of the current menu. The main menu contains four main groups: MEASUREMENTS RECORDED DATA SETTINGS CONFIGURATION To enter the main menu press the down arrow button for approximately 5 seconds after back light is displayed.
Figure 13 The display shows one of the main menu group To navigate between the main menu groups, use UP and Down arrow keys. To return the display to the top of all menu press [C] button The display will be returned to the idle mode on expiration of the time out.
11.
Figure 14 The display showing the first group menu of the main menu recorded data
15
Figure 15 The display showing the first sub group menu of group menu. Recorded data-current.
Figure 16 The display showing the first parameter menu of first subgroup & group menu of recorded data menu. 1 To enter a Group or sub group menu, press right arrow key & to return back / exit, press Left arrow key. 2 To navigate between the main levels in the submenus, use up or down arrow keys. 3 On entering group/subgroup menu, use right arrow key to enter parameter menu. 4 To navigate between the levels in the parameter menu, use up or down arrow keys. 5 Press [C] push button to return the display to the top of main menu. 12. MEASUREMENTS You can monitor all measured values via MEASUREMENTS in the HMI menu. In the measurement menu, the values on phases L1, L2, L3 & neutral current are displayed in Secondary term per unit values Primary terms To access the measured values on phases L1, L2, L3 and Io via the HMI menu 1. 2. 3. 4. 5. 6. 7. Press the down arrow button to access the main menu. The first main menu is the Measurement Press the right arrow key to enter the group menu. The first group menu is the "Nominal". Use of right arrow key allows you to enter the parameter menu directly, which has 4 parameters showing the current of phases L1, L2, L3 and Earth fault current Io in secondry terms. From the group menu nominal push the down arrow button to go the next Group menu of measurement menu. This is the second & the last group menu "AMPERE". Use of right arrow key allows you to enter the parameter menu directly, which shows 4 parameters, the currents of Phase L1, L2, L3 and Earth fault current Io in primary terms respectively.
Nominal group displays the PU value of currents in secondary terms. The 'Ampere' group menu displays the current in primary terms, e.g. when the relay is connected to 300/5A CT & the current of 150 A is flowing, the current displayed in nominal measurement is 0.50 and the current in Ampere will be 150A*
16
The below figure represents measurement main, group and parameter menu
Main Menu
M E A S U R E M E N T
Group Menu
M E A S U R E M E N T N O M I N A L
N
Parameter Menu
M E A S U R E M E N T
O M L 1 : X X . X X
M E A S U R E M E N T
N O M L 2 : X X . X X
M E A S U R E M E N T
N O M L 3 : X X . X X
M E A S U R E M E N T
N O M I 0 : X X . X X
M E A S U R E M E N T A M P E R E
M E A S U R E M E N T
A m p L 1 : X X X X X A
M E A S U R E M E N T
A m p L 2 : X X X X X A
M E A S U R E M E N T
A m p L 3 : X X X X X A
M E A S U R E M E N T
A m p I 0 : X X X X X A
17
13.
Recorded Data
The menu displays stored event values of the protection functions I>, I>>, Io> & Io>> stored duration between start and unit trip situation of the protection functions I>, I>>, Io> & Io>> registers number of trips of I>, I>>, Io> & Io>> The parameter values measured at the trip instance are recorded in the registers. The recorded data, in the event list will keep rolling with first in first out principle. The data are stored in the registers even if the auxiliary voltage supply to the relay is interrupted. All settings and fault records are maintained in a non - volatile memory. How to monitor recorded data Press an arrow button to access the main menu. Use DOWN arrow key to select RECORDED DATA which is the second in the main menu. Press right arrow to enter the first group menu "Current". Use right arrow key to enter into the sub group menu "Event 1" of the submenu Current. Further use of right arrow key displays the Parameter menu showing Current value in phase L1 during that particular event. 6. Use Down arrow keys to view current value in phases L2, L3 and Earth current. 7 In order to return to the event 1 press left arrow key 8. Using the navigation keys currents of previous 4 events can be viewed as described above. 9. On returning to Current menu Use Down arrow to go to other group menu "Time" and "Trip Count" 10. Similarly Duration of start to unit trip situation of I>, I>>, Io> & Io>> can be viewed in event subgroup menu of Time group menu & trip counts of individual fault in "Trip count" group menu. Main Menu Group Menu 1. 2. 3. 4. 5.
Figure 18 The below figure represents the main menu "Recorded Data" and its group menu's
18
Group Menu
Figure 19 The below figure represents the group menu "Recorded data - Current" and its Subgroup menu's "Events 1-5"
19
Parameter Menu
Figure 20 The below figure represents the subgroup menu "Event 1" and its parameter menu's showing the value of current L1, L2, L3 & Io for event 1. In the same manner Each Current Events (Event 2- Event 5) have recorded data of Three phase currents and earth current
20
Main Menu
Group Menu
Figure 21 The below figure represents the group menu "Recorded data - Time" and its Subgroup menu's Events 1-5"
21
Parameter menu
Figure 22 The below figure represents the subgroup menu "Event 1" of Time group menu and its parameter menu's t>, t>>, to>, to>> Similarly each time events (Event 2- Event 5) have recorded data of three phase currents and earth current duration between start & trip of unit.
Group menu
Parameter menu
Figure 23The below figure represents the group menu "Recorded data - trip count" and its parameter menu's
22
14.
Settings
This menu is used to change the value of primary and secondary* currents and setting of overcurrent and earth fault lowset and higset** values. In order to secure all parameters, all settings and values are recorded in non volatile memory. If for any reason, the content of memory are disturbed, all default setting from the DSP controller are written in the memory. If the memory is damaged the relay will set an alarm signal through IRF output relay and will display IRF code on LCD screen. How to change the setting values. 1. 2. 3. Press an arrow button to access the main menu. Use DOWN arrow key to select SETTINGS which is the third in the main menu. Pressing right key shows group menu "Primary CT ratio" Main Menu Group Menu
Figure 24 The display shows first group menu of main menu "Settings 4. 5. further use the right key to enter the parameter menu. The first parameter menu is for setting the primary current Group Menu Parameter Menu
Figure 25 The display shows first parameter menu for setting primary of group menu "Primary Settings" 6. 7. 8. 9. In order to change the value first press Enter key [E] and then [C] with E key still pressed. Releasing the keys will show that the cursor on right hand side of LCD blink. Use up or down keys to select the appropriate digits and left and right arrows to move between digits thereby set the desired value of primary current #. Press Enter key to save the setting.
10. The second parameter menu is for setting secondary CT ratio 1 or 5 Amps.
* The secondary current rating 1A / 5A of the relay is fixed as per article no/name plate. Relay is programmed with default factory setting of 100A primary and 1 A secondary. The relay should be ordered such to have In = 1A or 5A in line with CT specification. "I primary" & I secondary should be set accordingly in order to observe correct measurement in measurement parameter menu. ** For NI 41 only
#
Maximum primary current that can be set is 1600A. (Primary current for measurement purpose only)
23
Figure 26 The display shows second parameter menu for setting secondary current
11. In order to change the value first press Enter key [E] and then [C] with E key still pressed 12. Releasing the key will show the cursor on right hand side of LCD blink. 13. Use up or down keys to choose between 1 or 5 Amp. 14. Press Enter key [E] to save the setting. 15 The next group menus are settings for Low and High** set of Over current and earth fault i.e. I>,I>>, Io>, Io>>.
**
For NI 41 only
24
Main Menu
Group menu
Figure 27 The display shows group menus in order for Main menu "Settings
25
The low set stage of the overcurrent unit and the low set stage of the earth fault unit may be given definite time or inverse definite minimum time (IDMT) characteristic. When the IDMT characteristic is chosen four time/current curves are available. These curves comply with the BS 142 and IEC 60255 and are named "Normal inverse", "Very inverse", "Extremely inverse" and "Long-time inverse". The high set stage (for NI 41 only) can be used for instantaneous application by keeping the minimum setting of 50ms or for DMT with Maximum time duration of 64 Seconds. How to set a parameter for I>, Io> 1. The first parameter menu for I> or Io> is the selection of Characteristic Curve*. Group menu Parameter Menu
Figure 28 The display shows parameter menus for selection of setting curve. 2. 3. 4. 5. 6. In order to select/change, first press Enter key [E] and then [C] with E key still pressed else the screen will return to top of all menu. Releasing the key will show the cursor on right hand side of LCD blink. Use up or down keys to choose between DMT and other different types of curves. Press [E] key to save the selected curve. The next parameter menu is for setting the value of I> (or Io>). Group menu Parameter Menu
Group menu
Parameter Menu
All new characteristics curve, if added in future, shall be located at the end of existing curves in parameter menu.
26
The relay can be set for 0.50 - 2.00 in step of 0.01for Overcurrent i.e. I> and 0.10 - 0.80 of In in steps of 0.01 for Earth fault. 7. 8. 9. In order to change the setting, first press Enter key [E] and then [C] with E key still pressed else the screen will return to top menu. Releasing the key will show the cursor on right hand side of LCD to blink. Use up or down keys to choose between values and left - right arrows for selecting digits.
10. Press [E] key to save the selected value. 11. The next parameter menu is for setting of time (t> to to>) for DMT curve, if selected, or TMS Factor 'K' incase any IDMT curve is selected. The relay will only show t> (for I>) or t0> (for I0>) or "k" based on the type of curve characteristic selected. Parameter Menu for I> setting 1st parameter Parameter Menu for Io> setting
2nd parameter
Figure 31 The display shows parameter menus for setting of t> to to> when DMT characterisitics is selected. 13. t0 can be set between 0.05 sec - 64 Sec. The method of changing the time in sec for t> to to> is the same as that of setting the Values of I> & I0> as shown above. (Steps 7-10)
Figure 32 The display shows parameter menus for setting of k> when any IDMT curve is selected. The setting range of time multiplier 'k' is 0.05, 0.1-1.0 in the steps of 0.1. In order to change the value of K , simply use up or down key after entering the edit mode. How to set parameter for I>> & Io>> 1. The first parameter menu of group menu High set I>> or High set I0>> is for setting the value of I>> or I0>>.
Figure 33 The display shows parameter menus for setting of I>> & Io>> The setting range of I>> is from 50-2000% of In (In = 1 or 5A). The setting range of Io>> is from 10-1000% of In (In = 1 or 5A). 2. The next parameter menu is the time 't>' or 'to>'.
27
Figure 34 The display shows parameter menus for setting of t> and to>>. The setting range of time 't>' & 'to>' is 0.05 to 64Sec. The procedure of changing the the Values of I>> & Io>> and time t> & to> is the same as mention above.
15.
Configuration
This menu is used for l Blocking of particular protection l Assigning Hand reset (HR) or Self reset (SR) to trip relay Tr. l Relay configuration - to route particular protection to trip and/or signaling relay.
Configuration Blocking
The first group menu of the configuration menu is "Blocking Main menu Group menu
Figure 35 The display shows the first group menu Blocking of the main menu "Configuration". How to enable blocking of protection function. 1. 2. 3. 4. 5. Press an arrow button to access the main menu. Use DOWN arrow key to select CONFIGURATION which is the last in the main menu. Pressing right key shows group menu "Blocking" Further use the right key to enter the parameter menu. The first parameter menu is for blocking the Low-set over current. Group menu Parameter Menu
Figure 36 The display shows first parameter group for blocking of I>. 6. 7. As a company default setting all the protection funcitons are unblocked.
In order to change the value first press Enter key [E] and then [C] with E key still pressed else will return out of all menus 8. Releasing the keys will show that the cursor on right hand side of LCD to blink. 9. Use up or down keys to select 'YES' for blocking or 'NO' to keep protection in USE. 10. Press Enter key to save the setting. 11. Use the down arrow to go to next parameter menu(s).
28
Figure 37 The display shows second parameter group for blocking of I>>**.
Figure 38 The display shows third parameter group for blocking of Io>
Figure 39 The display shows fourth and last parameter group for blocking of Io>>** The procedure of blocking of I>>, Io>, Io>> is same as mentioned above for blocking I>.
Configuration Trip
The second group menu of the configuration menu is "Trip Main menu Group menu
Figure 40 The display shows the second group menu "TRIP" of the main menu "Configuration". This menu is used to latch (the output relay remains picked up after operation ) the trip relay Tr on a fault, although the energizing current falls below the start current. The trip signal is to be manually rest by pushing the push button [E] and left arrow key ( )simultaneously after accessing main menu. How to latch & reset the trip relay Tr. 1. 2. 3. 4. Press an arrow button to access the main menu. Use DOWN arrow key to select CONFIGURATION which is the last in the main menu. Press right key to enter group menus. Press down arrow for"Trip" which is second in the group menu. Use the right key to enter the parameter menu.
Figure 41 The display shows parameter menu for selecting Trip relay Tr. for Hand or Self reset.
29
5. 6. 7. 8.
As a company default setting the trip relay Tr. is set as SR or self reset. In order to change the mode of reseting the trip relay Enter key [E] and then [C] with [E] key still pressed else will return out of all menus Releasing the keys will show that the cursor on right hand side of LCD to blink. Use up or down keys to select 'HR' for selecting trip relay Tr. in latched mode or 'SR' or self reset which allows the trip relay Tr. to reset as soon as energizing input goes below setting level. Press Enter key [E] to save the setting.
9.
10. In order to reset the Tr. relay when latched, press any key and wait till the backlight glows. Then press left arrow key with E key pressed for 3 seconds.
Relay Configuration
Relay configuration' is the third and last group menu of 'Configuration' menu. Main Menu Group Menu
Figure 42.The display above shows the group menu 'Relay configuration' in configuration menu. How to route desired protection to trip and/or signal relay 1. 2. 3. 4. Press an arrow button to access the main menu. Use DOWN arrow key to select CONFIGURATION which is the last in the main menu. Press right key to enter group menus. Press down arrow for "Relay config." which is third/last in the group menu. Use the right key to enter the sub group menu. Group Menu Sub group menu
Figure 43 The display shows subgroup menu for routing Over current protection. 5. Further use of right arrow key button allows us to enter into the parameter menu. The first parameter menu is for routing low set overcurrent stage to desired relay.
30
Parameter Menu
Figure 44 The display shows Parameter menu for routing Lowset overcurrent protection 6. 7. 8. 9. As a company default setting all the protection trip are routed to trip and signalling relay. In order to change the desired relay for routing this protection, press the Enter key [E] and then [C] with [E] key still pressed. Releasing the keys will show that the cursor on right hand side of LCD to blink. Use up or down keys to select individual or group of relays.
Figure 45 The display shows the various selection available for routing protection to desired relay or group of relays. 10. Press Enter key [E] to save the setting. 11. Use the down arrow key for routing Highset overcurrent to desired relay.
Figure 46 The display shows the parameter menu for configuration of overcurrent protection. 12. The High set stage of over current is routed to trip and/or signal relay in similar manner. 13. The second subgroup menu is for routing earth fault to trip or signal relay.
31
Group Menu
Figure 47 The display shows the group & subgroup menu for configuration of earth fault protection Sub-Group Menu Parameter menu
Figure 48 The display shows the parameter menu for configuration of Earth fault protection.
14. Navingation and selection of relay for the E/F protection is same as mentioned above for Overcurrent.
32
16
Time/current characteristic
The operation of the low-set overcurrent stage I> and the low-set earth-fault stage I0> is based on definite time or inverse time characteristic, as selected by the user. The operation characteristic is selected with selection of configuration of curve for the low set overcurrent stage I> and low set earth-fault stage I0> (refer How to change parameters for I> or I0>)
When IDMT characteristic has been selected, the operate time of the stage will be a function of the current; the higher the current, the shorter the operate time. The stage includes four time/current curve sets - four according to the BS 142 and IEC 60255 standards
The stope of the time/current curve sets is determined by the constants a and b as follows :
IDMT characteristic
Four standard curves named extremely inverse, very inverse, normal inverse and longtime inverse are available. The relationship between current and time complies with the BS 142. 1966 and IEC 60255-3 standards and can be expressed as follows :
Slope of the time/ current curve set Normal inverse Very inverse Extremely inverse Long-time inverse
t [s] =
kxb I a -1 I>
where t = operate time in seconds k = time multiplier I = measured current value I> = set start current value The relay includes four time/current curve sets according to BS 142. 1966 and IEC 60255-3.
According to the standard BS 142.1966 the normal current range is defined as 2...20 times the set start current. Additionally the relay must start at the latest when the current exceeds 1.3 times the set start current, when the time/current characteristic is normal inverse, very inverse or extremely inverse. At long-time inverse characteristic, the normal range is 2...7 times the set start current and the relay must start when the current exceeds 1.1 times the setting.
The following requirements with regard to operate time tolerances are specified in the standard (E denotes accuracy in per cent, - = not specified):
I/I> 2 5 7 10 20
The actual operate time of the relay, presented in the graphs in Fig. 4043, includes an additional filter and detection time plus the operate time of the trip output relay. When the operate time of the relay is calculated using the mathematical expression above, these additional times of about 30 ms in total have to be added to the time received.
33
If the set start current exceeds 2.5 x In, the maximum permitted continuous current carrying capacity of the energizing inputs (4 x In) must be observed.
At inverse time characteristic the effective setting range of the low-set overcurrent stage is 0.52.5 x In, although start current settings within the range 2.55.0 x In can be set on the relay. At inverse time characteristic any start current setting above 2.5 x In of the low-set stage will be regarded as being equal to 2.5 x In.
t/s 70 60 50 40 30
20
10 9 8 7 6 5 4 3
1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 k 0.2 1.0 0.8 0.6 0.1 0.09 0.08 0.07 0.06 0.05 0.04 0.05 0.03 0.1 0.4 0.3 0.2
0.02 1 2 3 4 5 6 7 8 9 10 20 I/I>
34
t/s 70 60 50 40 30
20
10 9 8 7 6 5 4 3
0.2 0.2
0.1
0.05
0.02
6 7 8 9 10
20 I/I>
35
t/s 70 60 50 40 30
20
10 9 8 7 6 5 4 3 k 1.0 0.9 0.8 0.7 0.6 0.5 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.1 0.2 0.4 0.3
0.2
0.02 1 2 3 4 5 6 7 8 9 10 20 I/I>
36
200
100 90 80 70 60 50 40 30
20
10 9 8 7 6 5 4 3
0.3
0.1
0.2 1 2 3 4 5 6 7 8 9 10 20 I/I>
37
17
Technical Data
Energizing quantities, rated values & limits
Type designation Energizing Inputs Rated Current In Thermal Withstand a) Continuous b) For 1 Second Dynamic current withstand Input impedance 4A 100 A 250 A <100mW 20 A 500 A 1250 A <20mW 1A 5A NI 40/41
Indications
Relay supply healthy Protection start Protection trip Relay internal failure Relay display Green LED Green LED Red LED Red LED 16 x 2 Alpha numeric LCD display with backlit
Over current and earth fault relay settings Over Current Protection
Low Set (I>) Stage a) Current Range b) Operate time at DMT mode c) Item/current characteristic at IDMT mode (site-selectable)
50-200% of In in steps of 1% 0.05 - 64 Sec in steps of 0.01 sec Normal Inverse Very Inverse Extreme Inverse Long-time Inverse*
d) Time Multiplier K High Set (I>>) State a) Current Range b) Operate time at Inst. mode c) Operate time at DMT mode
* Any new characteristic curve shall be added at the end of the existing list.
38
Low Set (I0>) Stage a) Current Range b) Operate time at DMT mode c) Item/current characteristic at IDMT mode (site-selectable)
10-80% of In in steps of 1% 0.05 - 64 Sec in steps of 0.01 sec Normal Inverse Very Inverse Extreme Inverse Long-time Inverse*
d) Time Multipier l k High Set (Io>>) State a) Current Range b) Operate time at Inst. mode c) Operate time at DMT mode
0.05, 0.1 to 1.0 in steps of 0.1 10-1000% of In in steps of 1% 50 m Sec 0.05 - 64 Sec in steps of 0.01 sec
Rated Voltage Continuous Carrying capacity Make and Cary 3.0 sec Make and carry 0.5 sec voltage a) 220V DC b) 110V DC c) 48V DC
30 A Breaking capacity for DC when control circuit time constant L/R <40 ms and at 1A 3A 5A
Rated Voltage Continuous Carrying capacity Make and Cary 3.0 sec Make and carry 0.5 sec voltage a) 220V DC b) 110V DC c) 48V DC
250V AC/DC 5A 8A 10 A
Breaking capacity for DC when control circuit time constant L/R <40 ms and at
0.15 A 0.25 A 1A
* Any new characteristic curve shall be added at the end of the existing list.
39
Electrical Tests
Insulation Requirement
Dielectric test voltage (IEC 60255-5) Impulse test voltage (IEC 60255-5) Insulation resistant (IEC 60255-5)
2.0 kV. 50 Hz.1 min 5.0 kV. 1.2/50 ms. 0.5J >100 MW, 50 Vdc
Interference Test
High Frequency (1 MHz) disturbance test (IEC 60255-22-1), common mode High Frequency (1 MHz) disturbance test (IEC 60255-22-1), differential mode Fast transient (IEC 60255-22-4, class III and IEC 801-4, level 4), power supply port Fast transient (IEC 60255-22-4, class III and IEC 801-4, level 4), other ports Electrostatic discharge (IEC 60255-22-2 and IEC 801-2, Class III), air discharge RF electromagnetic field test (IEC 61000-4-3 and ENV 50140) Conducted RF disturbance test (IEC 61000-4-5 and ENV 50141) Surge immunity test (IEC 60255-22-5 and IEC 61000-4-5), common mode Surge immunity test (IEC 60255-22-5 and IEC 61000-4-5), differential mode Conducted and radiated RF emission test (IEC 60255-25, EN55011-CISPRII), conducted emission (main) Conducted and radiated RF emission test (IEC 60255-25, EN55011-CISPRII), conducted emission (main) Power frequency magnetic field immunity test (IEC 61000-4-8), continuous Power frequency magnetic field immunity test (IEC 61000-4-8), Short duration
100 A/m 300 A/m Class A 2.5 kV 1.0 kV 4 kV, 2.5 kHz, 50W 2 kV, 2.5 kHz, 50W 8 kV 10 V/m, f=80...1000MHz 10 Vm, f=150 kHz .... 1000 Mhz 2 kV, 1.2/50ms, 12W 1 kV, 1.2/50ms, 2W Class A
Electrostatic discharge (IEC 60255-22-2 and IEC 801-2, Class III), contact discharge 6 kV
40
Mechanical Tests
Seismic test (ANSI/IEEE C37.98-1987), operating basis earthquake test Seismic test (ANSI/IEEE C37.98-1987), safe shut down earthquake test Vibration response and endurance test (IEC 60255-2-1) Shock response and endurance test (IEC 60255-21-2) Bump test (IEC-60255-21-2)
0.5...5.25 g 0.5...7.5g 2...13.2 Hz, + 1.0 mm 13.2...100 Hz, + 0.7g Class 1, 11 ms 20g. 1000 bumps/direction
Environmental test
Service temperature range Transport and storage temperature range (IEC 60068-2-48) Dry heat test, (IEC 60068-22-2) Cyclic (12+12 hour cycle) damp heat test, (IEC 60068-2-30) Cold heat test, (IEC 60068-22-1) Corrosion test Degree of protection by enclosure, IP test (IEC 60529)
-10 0C....+550C -40 0C....+700C -55 0C....+700C <95%, +40 C, 96% Rh -10 C....-20 C Battelle test IP 54
0 0 0
41
18
19
20
42
21 Ordering details
Relay Type NI 40 NI 40 NI 40 NI 40 NI 41 NI 41 NI 41 NI 41 Current Input 1A 5A 1A 5A 1A 5A 1A 5A Aux Supply 80-265 V AC/DC 80-265 V AC/DC 18-80 V AC/DC 18-80 V AC/DC 80-265 V AC/DC 80-265 V AC/DC 18-80 V AC/DC 18-80 V AC/DC Article No. 1MYN742837-A 1MYN742837-B 1MYN742837-C 1MYN742837-D 1MYN742838-A 1MYN742838-B 1MYN742838-C 1MYN742838-D
ABB Limited Distribution Automation Products Maneja, Vadodara 390 013 India Tel. : +91 265 2604385/86 +91 265 2604394/97 Fax : +91 265 2638922 Emai: aicds@in.abb.com
No. 14, Mathura Road P.O. Amar Nagar Faridabad 121 003 Tel : +91 129 2275592 2279627, 5049000 Fax : +91 129 2279692/5019
ABB House Dr. S.B. Path Ballard Estate Mumbai 400 038 Tel. +91 22 56318231-39 Fax: +91 22 56318276-77
Embassy Star, 1st Floor, No. 8, Place Road, Vasanth Nagar Bangalore 560 052 Tel: +91 80-22949779 Fax: +91 80 22949808
www.abb.co.in
4th Floor No. 9 Elgin Road Kolkatta 700 020 Tel.: +91 33 22832906/8 Fax: +91 33 22832990
4th & 5th Floor, Maruti Heights, Amanaka, G.E. Road Raipur 492 099 Chhattisgarh Tel: +91 771 4701016/17-18 Fax: +91 771 4701019/20
Century Plaza Nos. 3C, 3D and 3F, 3rd Floor, 561 / 562, Anna Salai Teynampet (Mount Road) Chennai 600 018 Tel. +91-44 24340201 Fax: +91 44 24340282
1MDV070203-YN 07 - 2007