Sie sind auf Seite 1von 10

Coordinated protections of motor Starters

Direct-on-line starter Normal start with Miniature Circuit Breaker


400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 1

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41
55

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50
63

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650
819

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50
S803S-KM63

Limitor

Contactor

Overload Relay

Max

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

0,16 - 0,25
0,25 - 0,4
0,4 - 0,63
0,4 - 0,63
0,63 - 1,0
1,0 - 1,4
1,3 - 1,8
1,7 - 2,4
2,2 - 3,1
2,8 - 4,0
4,5 - 6,5
4,5 - 6,5
7,5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
29 - 42
45 - 63

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

0.25
0.40
0.63
0.63
1
1.35
1.75
2.35
3.75
3.75
6.25
6.25
10.5
12.5
16.0
20
30.5
39
39
61.5

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
A30
A50
A50
A63

Type
TA25DU0,25
TA25DU0,40
TA25DU0,63
TA25DU0,63
TA25DU1,0
TA25DU1,4
TA25DU1,8
TA25DU2,4
TA25DU3,1
TA25DU4,0
TA25DU6,5
TA25DU6,5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA75DU42
TA75DU42
TA75DU63

MC4050NSL1.1

Coordinated protections of motor Starters


Direct-on-line starter Normal start with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 2

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41
55

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50
63

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650
819

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50
S803S-KM63

Limitor

Contactor

Overload Relay

Max

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

0,16 - 0,25
0,25 - 0,4
0,4 - 0,63
0,4 - 0,63
0,63 - 1,0
1,0 - 1,4
1,3 - 1,8
1,7 - 2,4
2,2 - 3,1
2,8 - 4,0
4,5 - 6,5
4,5 - 6,5
7,5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
29 - 42
45 - 63

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

0.25
0.40
0.63
0.63
1
1.35
1.75
2.35
3.75
3.75
6.25
6.25
10.5
12.5
16.0
20
30.5
39
39
61.5

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A30
A30
A50
A50
A63

Type
TA25DU0,25
TA25DU0,40
TA25DU0,63
TA25DU0,63
TA25DU1,0
TA25DU1,4
TA25DU1,8
TA25DU2,4
TA25DU3,1
TA25DU4,0
TA25DU6,5
TA25DU6,5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA75DU42
TA75DU42
TA75DU63

MC4050NSL2.1

Coordinated protections of motor Starters


Direct-on-line starter Normal start with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 1

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41
55

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50
63

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650
819

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50
S803S-KM63

Limitor

Contactor

Overload Relay

Max

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

0,1 - 0,32
0,1 - 0,32
0,3 - 1,0
0,3 - 1,0
0,3 - 1,0
0,9 - 2,7
0,9 - 2,7
0,9 - 2,7
2 - 6,3
2 - 6,3
2 - 6,3
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
9 - 30
15 - 45
15 - 45
15 - 45
27 - 80

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

0.32
0.32
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
25
32
40
45
63

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A26
A30
A40
A40
A63

Type
E16DU0,32
E16DU0,32
E16DU1,0
E16DU1,0
E16DU1,0
E16DU2,7
E16DU2,7
E16DU2,7
E16DU6,3
E16DU6,3
E16DU6,3
E16DU18,9
E16DU18,9
E16DU18,9
E16DU18,9
E45DU30
E45DU45
E45DU45
E45DU45
E80DU80

MC4050NSLE1.1

Coordinated protections of motor Starters


Direct-on-line starter Normal start with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 2

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41
55

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50
63

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650
819

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50
S803S-KM63

Limitor

Contactor

Overload Relay

Max

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

0,1 - 0,32
0,1 - 0,32
0,3 - 1,0
0,3 - 1,0
0,3 - 1,0
0,9 - 2,7
0,9 - 2,7
0,9 - 2,7
2 - 6,3
2 - 6,3
2 - 6,3
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
9 - 30
15 - 45
15 - 45
15 - 45
27 - 80

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

0.32
0.32
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
25
32
40
45
63

A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A12
A26
A26
A26
A26
A30
A40
A50
A50
A63

Type
E16DU0,32
E16DU0,32
E16DU1,0
E16DU1,0
E16DU1,0
E16DU2,7
E16DU2,7
E16DU2,7
E16DU6,3
E16DU6,3
E16DU6,3
E16DU18,9
E16DU18,9
E16DU18,9
E16DU18,9
E45DU30
E45DU45
E45DU45
E45DU45
E80DU80

MC4050NSLE2.1

Coordinated protections of motor Starters


Direct-on-line starter Normal start with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 1

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41
55

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50
63

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650
819

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50
S803S-KM63

Limitor

Contactor

Overload Relay

Max

Type

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A26
A30
A40
A40
A63

UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP

0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50
63

MC4050NSLU1.1

Coordinated protections of motor Starters


Direct-on-line starter Normal start with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 2

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41
55

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50
63

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650
819

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50
S803S-KM63

Limitor

Contactor

Overload Relay

Max

Type

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A12
A26
A26
A26
A26
A30
A40
A50
A50
A63

UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP

0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50
63

MC4050NSLU2.1

Coordinated protections of motor Starters


Direct-on-line starter Heavy Duty 20s with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 1

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50

Limitor

Contactor

Overload Relay

Max

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

0,1 - 0,32
0,1 - 0,32
0,3 - 1,0
0,3 - 1,0
0,3 - 1,0
0,9 - 2,7
0,9 - 2,7
0,9 - 2,7
2 - 6,3
2 - 6,3
2 - 6,3
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
9 - 30
15 - 45
15 - 45
15 - 45

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

0.32
0.32
0.63
0.63
1
1.6
1.6
2.5
2.5
4
6.3
12.5
12.5
16
16
25
32
40
50

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
A30
A40
A50
A63

Type
E16DU0,32
E16DU0,32
E16DU1,0
E16DU1,0
E16DU1,0
E16DU2,7
E16DU2,7
E16DU2,7
E16DU6,3
E16DU6,3
E16DU6,3
E16DU18,9
E16DU18,9
E16DU18,9
E16DU18,9
E45DU30
E45DU45
E45DU45
E45DU45

MC4050HDLE1.1

Coordinated protections of motor Starters


Direct-on-line starter Heavy Duty 20s with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 2

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50

Limitor

Contactor

Overload Relay

Max

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

0,1 - 0,32
0,1 - 0,32
0,3 - 1,0
0,3 - 1,0
0,3 - 1,0
0,9 - 2,7
0,9 - 2,7
0,9 - 2,7
2 - 6,3
2 - 6,3
2 - 6,3
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
9 - 30
15 - 45
15 - 45
15 - 45

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

0.32
0.32
0.63
0.63
1
1.6
1.6
2.5
2.5
4
6.3
12.5
12.5
16
16
25
32
40
50

A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A12
A26
A26
A26
A26
A40
A50
A50
A63

Type
E16DU0,32
E16DU0,32
E16DU1,0
E16DU1,0
E16DU1,0
E16DU2,7
E16DU2,7
E16DU2,7
E16DU6,3
E16DU6,3
E16DU6,3
E16DU18,9
E16DU18,9
E16DU18,9
E16DU18,9
E45DU30
E45DU45
E45DU45
E45DU45

MC4050HDLE2.1

Coordinated protections of motor Starters


Direct-on-line starter Heavy Duty 20s with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 1

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50

Limitor

Contactor

Overload Relay

Max

Type

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
A30
A40
A50
A63

UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP

0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50

MC4050HDLU1.1

Coordinated protections of motor Starters


Direct-on-line starter Heavy Duty 20s with Miniature Circuit Breaker
400 V, 50 kA, 50/60 Hz, AC-3, EN/IEC 60947-4-1, type 2

Motor

Miniature Circuit-Breaker

Rated
Output
[kW]

Rated
Current [A]

Rated
Current [A]

Magnetic trip
Current [A]

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.2
22
29
35
41

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50

2.44
3.9
6.14
6.14
11.5
11.5
11.5
27.5
40
40
78.7
78.7
135
187.5
240
300
416
520
650

Type
MO325-0,25
MO325-0,40
MO325-0,63
MO325-0,63
MO325-1,00
MO325-1,60
MO325-1,60
MO325-2,50
MO325-4,00
MO325-4,00
MO325-6,3
MO325-6,3
MO325-9
MO325-12,5
MO325-16,0
MO325-25
S803S-KM32
S803S-KM40
S803S-KM50

Limitor

Contactor

Overload Relay

Max

Type

Type

Current
setting range
[A]

Trip Class

allowed
setting
current [A]

A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A12
A26
A26
A26
A26
A40
A50
A50
A63

UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP
UMC22-FBP

0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63
0.1 - 63

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

0.25
0.40
0.63
0.63
1
1.6
1.6
2.5
4
4
6.3
6.3
9
12.5
16
20
32
40
50

MC4050HDLU2.1

Das könnte Ihnen auch gefallen