Beruflich Dokumente
Kultur Dokumente
com
http://electrical-engineering-portal.com/overcurrent-protectiontransformer-nec-450-3? utm_source=Technical+Articles&utm_campaign=9178eec02cRSS_EMAIL_CAMPAIGN&utm_medium=email
Welcome !
Hi and welcome to EEP ! For better and easier navigation through the site you can use portal's Sitemap
Advertisement
Reach clients related to electrical engineering, industry and automation all across the world.More information Download Center
Online Calculators
Online Elect rical Calculat orsfor basic and advanced calculation of single phase, three phase electric current, power, voltage, voltage drop as well as energy consumption...Visit calculators Technical Articles
Resources
Knowledge
Submit your research (project) and share with other readers. Learn about theories and advancing to Ohm's Law, magnetism, machines, AC and DC motors, inspection, maintenance, etc. Video Lectures|PLC Training|Researches, Projects|Theorems
Power Directory
Free submit your site to EEP Directory and make your company's business visible to electrical engineers all across the world. Power Directory|Free submit site Contact
Let's connect!
Technical Articles Home / Technical Articles / Overcurrent Protection of Transformer (NEC 450.3)
Overcurrent Protection of T ransf ormer (NEC 450.3) - Photo by Ef rem Oshinsky @ Flickr
Content
Introduction Overcurrent protection of transformers >600V (NEC450.3A)
1. Unsupervised location of transformer (impedance <6%) 2. Unsupervised location of transformer (impedance 6% to 10%) 3. Supervised location (in primary side only) of transformer 4. Supervised location of transformer (impedance up to 6%) 5. Supervised location of transformer (impedance 6% to 10%) 6. Difference in C.B between supervised & unsupervised Location 7. Sumary of overcurrent protection for more than 600V Overcurrent Protection of Transformers <600V (NEC 450.3B) 1. Only primary side protection of transformer 2. Primary and secondary side protection of transformer 3. Summary of overcurrent protection for less than 600V
Introduction
The overcurrent protection required for transformers is consider for Protection of Transformeronly. Such overcurrent protection will not necessarily protect the primary or secondary conductors or equipment connected on the secondary side of the transformer. When voltage is switched on to energize a transformer, the transformer core normally saturates. This results in a large inrush current which is greatest during the first half cycle (approximately 0.01 second) and becomes progressively less severe over the next several cycles (approximately 1 second) until the transformer reaches its normal magnetizing current. To accommodate this inrush current, fuses are often selected which have time-current withstand values of at least 12 timestransformer primary rated current for 0.1 secondand 25 timesfor 0.01 second. Some small dry-type transformers may have substantially greater inrush currents. To avoid using over sized conductors, overcurrent devices should be selected at about 110 to 125 percentof the transformer full-load current rating. And when using such smaller overcurrent protection, devices should be of the time-delay type (on the primary side) to compensate for inrush currents which reach 8 to 10 times the full-load primary current of the transformer for about 0.1 s when energized initially. Protection of secondary conductors has to be provided completely separately from any primary-side protection. A supervised location is a location where conditions of maintenance and supervision ensure that
only qualified persons will monitor and service the transformer installation. Overcurrentprotection for a transformer on the primary side is typically a circuit breaker. In some instances where there is not a high voltage panel, there is a fused disconnect instead. It is important to note that the overcurrent device on the primary side must be sized based on the transformer KVA rating and not sized based on the secondary load to the transformer. Go to Content
OverCurrent Protection at Primary Side (Primary Voltage >600V): Rating of Pri. Fuse at Point A= 300% of Pri. Full Load Current or Next higher Standard size. or Rating of Pri. Circuit Breaker at Point A= 600% of Pri. Full Load
Unsupervised Location of T ransf ormer (Impedance <6%)
Current or Next higher Standard size. OverCurrent Protection at Secondary Side (Secondary Voltage <=600V): Rating of Sec. Fuse / Circuit Breaker at Point B= 125% of Sec. Full Load Current or Next higher Standard size. OverCurrent Protection at Secondary Side (Secondary Voltage >600V): Rating of Sec. Fuse at Point B= 250% of Sec. Full Load Current or Next higher Standard size. or Rating of Sec. Circuit Breaker at Point B= 300% of Sec. Full Load Current. Example:750KVA, 11KV/415V 3Phase Transformer having Impedance of Transformer 5%
Full Load Current At Primary side = 750000/(1.732X11000) = 39A Rating of Primary Fuse = 3X39A = 118A, So Standard Size of Fuse = 125A. OR Rating of Primary Circuit Breaker = 6X39A = 236A, So standard size of CB = 250A. Full Load Current at Secondary side = 750000/(1.732X415) = 1043A. Rating of Secondary of Fuse / Circuit Breaker = 1.25X1043A = 1304A, so standard size of Fuse = 1600A. Go to Content
OverCurrent Protection at Primary Side (Primary Voltage >600V): Rating of Pri. Fuse at Point A= 300% of Primary Full Load Current or Next higher Standard size.
Unsupervised Location of T ransf ormer (Impedance 6% to 10%) Rating of Pri. Circuit Breaker at Point A= 400% of Primary Full Load Current or Next higher Standard size.
OverCurrent Protection at Secondary Side (Secondary Voltage <=600V): Rating of Sec. Fuse / Circuit Breaker at Point B= 125% of Sec. Full Load Current or Next higher Standard size. OverCurrent Protection at Secondary Side (Secondary Voltage >600V): Rating of Sec. Fuse at Point B= 225% of Sec. Full Load Current or Next higher Standard size. Rating of Sec. Circuit Breaker at Point B= 250% of Sec. Full Load Current or Next higher Standard size. Example:10MVA, 66KV/11KV 3Phase Transformer, Impedance of Transformer is 8%
Full Load Current At Primary side = 10000000/(1.732X66000) = 87A Rating of Pri. Fuse = 3X87A = 262A, so next standard size of Fuse = 300A. OR Rating of Pri. Circuit Breaker = 6X87A = 525A, so next standard size of CB = 600A. Full Load Current at Secondary side = 10000000/(1.732X11000) = 525A. Rating of Sec. Fuse = 2.25X525A = 1181A, so next standard size of fuse = 1200A. OR Rating of Sec. Circuit Breaker = 2.5X525A = 1312A, so next standard size of circuit breaker = 1600A. Go to Content
OverCurrent Protection at Primary Side (Primary Voltage >600V): Rating of Pri. Fuse at Point A= 250% of Primary Full Load Current or Next higher Standard size. Rating of Pri. Circuit Breaker at Point A= 300% of Primary Full Load Current or Next higher Standard size. Go to Content
Supervised Location (in Primary side only) of T ransf ormer
OverCurrent Protection at Primary Side (Primary Voltage >600V): Rating of Pri. Fuse at Point A= 300% of Pri. full load current or next lower standard size. Rating of Pri. Circuit Breaker at Point A= 600% of Pri. full load current or next lower standard size.
OverCurrent Protection at Secondary Side (Secondary Voltage <=600V): Rating of Sec. Fuse / Circuit Breaker at Point B= 250% of Sec. Full Load Current or Next higher Standard size. OverCurrent Protection at Secondary Side (Secondary Voltage >600V): Rating of Sec. Fuse at Point B= 250% of Sec. Full Load Current or Next Lower Standard size. Rating of Sec. Circuit Breaker at Point B= 300% of Sec. Full Load Current or Next Lower Standard size. Example:750KVA, 11KV/415V 3Phase Transformer having Impedance of Transformer 5% Full Load Current At Primary side = 750000/(1.732X11000) = 39A Rating of Primary Fuse = 3X39A = 118A, so next lower standard size of fuse = 110A. OR Rating of Primary Circuit Breaker = 6X39A = 236A, so next lower standard size of Circuit Breaker = 225A. Full Load Current at Secondary side = 750000/(1.732X415) =1043A. Rating of Secondary of Fuse / Circuit Breaker = 2.5X1043A=2609A, so standard size of Fuse = 2500A. Go to Content
OverCurrent Protection at Primary Side (Primary Voltage >600V): Rating of Pri. Fuse at Point A= 300% of Pri. full load current or next lower standard size. Rating of Pri. Circuit Breaker at Point A= 400% of Pri. full load current or next lower standard size.
Overcurrent protection at secondary side (Secondary voltage <=600V): Rating of Sec. Fuse / Circuit Breaker at Point B= 250% of Sec. full load current or next higher standard size. Overcurrent protection at secondary side (Secondary voltage >600V): Rating of Sec. Fuse at Point B= 225% of Sec. full load current or next lower standard size. Rating of Sec. Circuit Breaker at Point B= 250% of Sec. full load current or next lower standard size. Example:750KVA, 11KV/415V 3Phase Transformer having Impedance of Transformer 8% Full Load Current At Primary side = 750000/(1.732X11000) = 39A Rating of Primary Fuse = 3X39A = 118A, so next lower standard size of Fuse = 110A. OR Rating of Primary Circuit Breaker = 4X39A = 157A, so next lower standard size of Circuit Breaker = 150A. Full Load Current at Secondary side = 750000/(1.732X415) = 1043A. Rating of Secondary of Fuse / Circuit Breaker = 2.5X1043A=2609A, so standard size of Fuse = 2500A. Go to Content
First notable condition is Primary Overcurrent Protection. In unsupervised location fuse in primary side is 300%of primary current or Next Higher Standard sizeand in supervised location is 300% of primary current or Next Lower Standard size. Here primary overcurrent protection is same in both conditions (300%), but selecting size of Fuse/Circuit Breaker is different. Lets us Check with the Example for 750KVA, 11KV/415V 3Phase Transformer. Full Load Current At Primary side = 750000/(1.732X11000) = 39A In Unsupervised Location: Rating of Primary Fuse = 3X39A = 118A, so next higher standard size = 125A In Supervised Location: Rating of Primary Fuse = 3X39A = 118A, so next lower standard size = 110A Second notable condition is Secondary Overcurrent Protection increased from 125% to 250% for unsupervised to Supervised Location. Go to Content
C. B.
C. B.
Any location
600%(NH)
400%(NH) 300%(NH)
300%(NH) 250%(NH)
Any
Less than 6%
600%
300%
400%
300%
250%
225%
250%
OverCurrent Protection at Primary Side (Less than 2A): Rating of Pri. Fuse / C.B at Point A = 300% of Pri. full load current or next lower standard size. Example: 1KVA, 480/230 3Phase transformer, full load current at Pri. side = 1000/(1.732X480) = 1A Rating of Primary Fuse = 3X1A = 3A, so next lower standard size of Fuse = 3A. OverCurrent Protection at Primary Side (2A to 9A): Rating of Sec. Fuse / C.B at Point A = 167% of Pri. full load current or next lower standard size. Example: 3KVA, 480/230 3Phase transformer, full load current at Pri. side = 3000/(1.732X480) = 4A Rating of Primary Fuse = 1.67X4A = 6A, so next lower standard size of Fuse = 6A. OverCurrent Protection at Primary Side (More than 9A): Rating of Pri. Fuse / C.B at Point A = 125% of Pri. full load current or next higher standard size.
Only Primary side Protection of T ransf ormer
Example: 15KVA, 480/230 3Phase transformer, full load current at Pri. side = 15000/(1.732X480) = 18A Rating of Primary Fuse = 1.25X18A= 23A, so next higher standard size of Fuse = 25A. Go to Content
OverCurrent Protection at Primary Side (Less than 2A): Rating of Pri. Fuse / C.B at Point A = 250% of Pri. full load current or next lower standard size. OverCurrent Protection at Primary Side (2A to 9A):
Rating of Sec. Fuse / C.B at Point A= 250% of Pri. full load current or next lower standard size. OverCurrent Protection at Primary Side (More than 9A): Rating of Pri. Fuse / C.B at Point A= 250% of Pri. Full Load Current or Lower Higher Standard size. Example: 25KVA, 480/230 3Phase Transformer, Full Load Current at Pri. Side=125000/(1.732X480)=30A Rating of Primary Fuse = 2.50X30A= 75A, So Next Lower Standard Size of Fuse =70A. OverCurrent Protection at Secondary Side (Less than 9A): Rating of Pri. Fuse / C.B at Point B= 167% of Sec. Full Load Current or Lower Standard size. Example: 3KVA, 480/230 3Phase Transformer, Full Load Current at Sec. Side=3000/(1.732X230)=8A
Rating of Primary Fuse = 1.67X8A= 13A, So Next Lower Standard Size of Fuse =9A. OverCurrent Protection at Secondary Side (More than 9A): Rating of Pri. Fuse / C.B at Point A= 125% of Pri. Full Load Current or Higher Standard size. Example: 15KVA, 480/230 3Phase Transformer, Full Load Current at Sec. Side=15000/(1.732X230)=38A Rating of Primary Fuse = 1.25X38A= 63A, So Next Higher Standard Size of Fuse =70A. Go to Content
167%
Not required
250%
250%
250%
125%(NH)
jiguparmar- Electrical engineer having more than 11 years experience in Power Transmission -Power Distribution-Electrical Maintenance-Electrical ProjectsPlanning-Designing-coordination-Execution.Currently associate with one of the leading business group as a Asst.Manager at Ahmedabad,India. Freelancer Programmer of Advance Excel. Design useful Excel Sheets of Electrical Engineering as per IS,NEC,IEC,IEEE codes. Technical Author for "Electrical Mirror" and "Electrical India" Magazines. Technical Blogger. Familiar with English, Hindi, Gujarati, French languages. Share experience and knowledge and help technical enthusiasts to find suitable solutions and updating themselves on various Engineering Topics. Write for EEP, become contributor | Introduce yourself to huge number of our readers and followers
Engineering T rainings