12MW ALTERNATOR PROTECTION SCHMES AND THEIR SET POINTS

1. Generator Differential -Group 1: Gen Diff Function Gen Difff Is 1 Gen Diff K1 Gen Diff Is2 Gen Diff K2 : : : : : Percentage Bias 100.00 mA 0.000% 1.200 A 150.0%

9.Frequency Protection Under Frequency :F < 1 Status F < 1 Setting F < 1 Time Delay F < 2 Status F < 2 Setting F < 2 Time Delay F < 3 Status F < 4 Status F < Function Link Over Frequency :F > 1 Status F > 1 Setting F > 1 Time Delay F > 2 Status F > 2 Setting F > 2 Time Delay : : : : : : Enabled 52.50 Hz 2.000 s Enabled 53.50 Hz 1.000 s : : : : : : : : : Enabled 47.70 Hz 2.00s Enabled 47.50 Hz 250.00 ms Disabled Disabled 000

2.Power Group 1 Operatig Mode Power 1 Function - P>1 Setting Power 1 Time delay Power 1 Do Timer P 1 Poledead Inch Power 2 Function P < 2 Setting Power 2 Time Delay Power 2 Do Timer P 2 Poledead Inch : : : : : : : : : : : Generating Reverse 4.00w 2.000s 0.000s Enablaed Low Forward 4.00w 2.000s 0.000s Enablaed

3.Over Current I > 1 Functon I > 2 Functin : : Disabled Disabled

10.CB Fail & I < Under current :I < Current Set I N < Current Set I Sef < Current I < CT Source : : : : : : Measured DT 100.00mA 300.00ms 0.000ms Disabled : : : : 700.0 mA 100.0 mA 20.00 mA IA -1,IB -1,IC -1

4.Earth Fault IN > Input IN > 1 Function IN > 1 Current IN > 1 Time Delay IN > 1 Reset IN > 2 Functon

11.NPs Thermal I 2 > 1 Alarm I 2 > 1 Current I 2 > 1 Time Delay I 2 > 2 Trip I 2 > 2 Current Set I 2 > 2 K Setting I 2 > 2 K Reset I 2 > 2 t max I 2 > 2 t min : : : : : : : : : Enabled 80.00 mA 3.000 s Enabled 100.0 mA 15.0 s 15.0 s 1.00k s 250.00 ms

5.SEF/REF Protection Sef/Ref Options I Ref > Is : : Hi > Ref 100.0ms

6.V/Hz Protection 12.System Backup V/Hz Alarm Status V/Hz Alarm Set V/Hz Alarm Delay V/Hz Trip Function V/Hz Trip Set V/Hz Trip Delay : : : : : : Enabled 2.420 V/Hz 1.000s DT 2.500 V/Hz 2.000s Backup Function Vector Rotation V Dep OC Char V Dep OC I > set V Dep OC Delay V Dep OC t Reset V Dep OC V < 1 Set V Dep OC K Reset : : : : : : : : Voltage Controlled None DT 1.110 A 2.000 s 500.0 ms 80.00 v 0.500

7.Dead Machine Dead M/c Status Dead M/c I > Dead M/c V < Dead M/c t pu Dead M/c Do : : : : : Enabled 2.000 A 66.00 v 0.000s 0.000s

13.Field Failure Protection F.Fail Alarm Status F.Fail Alarm Angle F.Fail Alarm Delay F.Fail 1 Status F.Fail 1 Xa1 F.Fail 1 Xab1 F.Fail Time Delay F.Fail Do Timer F.Fail 2 Status F.Fail 2 Xa2 F.Fail 2 Xb2 F.Fail 2 Time Delay F.Fail 2 Do Timer : : : : : : : : : : : : : Enabled 15.00 deg 4.00 s Enabled 9.00 ohms 115.0 ohms 5.000 s 8.000 s Enabled 9.00 ohms 115.0 ohms 5.000 s 8.000 s

8.Voltage Protection Under Voltage :V < Measurement mode V < Operating Mode V < 1 Function V < 1 Voltage set V < 1 Time Delay V < 1 Pole dead Inch V < 2 Status V < 2 Voltage Set V < 2 Time Delay V < 2 Pole dead Inch Over Voltage :V > Measurement mode V > Operate Mode V > 1 Function V > 1 Voltage Set V > 1 Time Delay V > 2 Status V > 2 Voltage Set V > 2 Time Delay : : : : : : : : Phase - Phase Any Phase DT 126.0 v 2.000 s Enabled 132.0 v 500.0 ms : : : : : : : : : : Phase - Phase Any Phase DT 97.00 v 2.000s Enabled Enabled 88.0 v 500.00 ms Enabled

SET POINTS

age Controlled

3 MW ALTERNATOR PROTECTION SCHMES AND THEIR SET POINTS

1. Generator Differential -Group 1: Gen Diff Function Gen Difff Is 1 Gen Diff K1 Gen Diff Is2 Gen Diff K2 : : : : : Percentage Bias 100.00 mA 0.000% 1.200 A 150.0%

6.Frequency Protection Under Frequency :F < 1 Status F < 1 Setting F < 1 Time Delay F < 2 Status F < 2 Setting F < 2 Time Delay F < 3 Status F < 4 Status F < Function Link Over Frequency :F > 1 Status F > 1 Setting F > 1 Time Delay F > 2 Status F > 2 Setting F > 2 Time Delay : : : : : : Enabled 52.50 Hz 2.000 s Enabled 51.50 Hz 2.000 s : : : : : : : : : Enabled 47.50 Hz 2.00s Enabled 47.50 Hz 1.000 s Disabled Disabled 000

2.Power Group 1 Operatig Mode Power 1 Function - P>1 Setting Power 1 Time delay Power 1 Do Timer P 1 Poledead Inch Power 2 Function : : : : : : : Generating Reverse 15.00w 2.000s 0.000s Enablaed Disabled

3.Earth Fault IN > Input IN > 1 Function IN > 1 Current IN > 1 Time Delay IN > 1 Reset IN > 2 Functon : : : : : : Measured DT 50.00mA 1.000s 0.000ms Disabled

07.CB Fail & I < Under current :I < Current Set I N < Current Set I Sef < Current I < CT Source : : : : 100.0 mA 100.0 mA 20.00 mA IA -1,IB -1,IC -1

4.V/Hz Protection V/Hz Alarm Status V/Hz Alarm Set V/Hz Alarm Delay V/Hz Trip Function V/Hz Trip Set V/Hz Trip Delay : : : : : : Enabled 2.310 V/Hz 1.000s DT 2.420 V/Hz 1.000s

08.NPs Thermal I 2 > 1 Alarm I 2 > 1 Current I 2 > 1 Time Delay I 2 > 2 Trip I 2 > 2 Current Set I 2 > 2 K Setting I 2 > 2 K Reset I 2 > 2 t max I 2 > 2 t min : : : : : : : : : Enabled 80.00 mA 3.000 s Enabled 100.0 mA 15.0 s 15.0 s 1.00k s 250.00 ms

5.Voltage Protection Under Voltage :V < Measurement mode V < Operating Mode : : Phase - Phase Any Phase

V < 1 Function V < 1 Voltage set V < 1 Time Delay V < 1 Pole dead Inch V < 2 Status V < 2 Voltage Set V < 2 Time Delay V < 2 Pole dead Inch Over Voltage :V > Measurement mode V > Operate Mode V > 1 Function V > 2 Status V > 2 Voltage Set V > 2 Time Delay

: : : : : : : :

DT 90.00 v 2.000s Enabled Enabled 80.0 v 2.000 s Enabled

09.System Backup Backup Function Vector Rotation V Dep OC Char V Dep OC I > set V Dep OC Delay V Dep OC t Reset V Dep OC V < 1 Set V Dep OC K Reset : : : : : : : : Voltage Controlled None DT 1.000 A 2.000 s 500.0 ms 80.00 v 1.000

: : : : : :

Phase - Phase Any Phase Disabled Enabled 126.0 v 1.000 s

10.Field Failure Protection F.Fail Alarm Status F.Fail Alarm Angle F.Fail Alarm Delay F.Fail 1 Status F.Fail 1 - Xa1 F.Fail 1 Xab1 F.Fail Time Delay F.Fail Do Timer F.Fail 2 Status : : : : : : : : : Enabled 15.00 deg 5.00 s Enabled 7.00 ohms 143.0 ohms 5.000 s 8.000 s Disabled