SKYCOURTS, DUBAILAND RESIDENTIAL COMPLEX PLOT RC-A-30 METHOD STATEMENT FOR BUS-DUCTS AND ACCESSORIES CONTENTS

1. PURPOSE

2. SCOPE

3. DELIVERY AND STORAGE

4. INSPECTION OF MATERIALS

5. EQUIPMENT/TOOLS

6. INSTALLATION PROCEDURE

7. INDOOR BUSWAY INSTALLATIONS

8. SAFETY

SKYCOURTS, DUBAILAND RESIDENTIAL COMPLEX


Page 1 of 4

PLOT RC-A-30 METHOD STATEMENT FOR BUS-DUCTS AND ACCESSORIES 1. Purpose


This methodology covers the procedure for the installation of Bus ducts and accessories in accordance with the applicable standards, local authority regulations, contract documents and Electrical Specifications Part B Section 6.

2. Scope
This method statement is applicable for installation of Bus-duct to ensure that the supporting works is properly jointed and confirms to the requirement of specifications/drawings.

3. Delivery and Storage


1. Receive the material from the supplier, and check against the ordered, type, quantity and ensure that materials are delivered as per approved material submittal No: SK/CN/06/007/STS-.00900/005. 2. Store the Bus ducts and accessories in designated storage area as per manufacturer recommendations. 3. The storage area must be free from dust and the material should be stacked in proper manner to avoid any damages. 4. Take proper care while moving and handling the above materials. 5. Mark or label damaged or incorrect materials and remove the materials from Site immediately. 6. Obtain approval from the consultant on every batch of materials delivered to the site.

4. Inspection of Materials
1. The project QA/QC Engineer will inspect the received material and make sure that the delivered materials are as per the approved material submittal. 2. After inspection by CSCEC project QA/QC, inspection request along with checklist will be sent to the consultant for further checking and approval. 3. After consultants approval, the material/equipment will be ready for installation.

5. Equipments/Tools
Page 2 of 4

a. b. c. d. e.

Electrical Tool Kit Drill Machine Electric Cutting Machine Step Ladder Continuity Tester

6. Installation Procedure
1. Before installing the bus-way, conduct an insulation resistance test on each busway device to check for possible damage or contamination during shipment or storage. With an insulation resistance tester rated at 500 volts, ensure phase-tophase, phase-to-neutral and ground isolation. 2. The Bus-duct route has to be checked with approved shop drawings and mark accordingly. 3. Mark the points of supports and fix the required support according to the approved detailed shop drawings and specifications. 4. Riser surface must be smooth, aligned, secured and protected well before any installation. 5. All the water curing work must be done earlier to the installation to avoid any leakage on the bus-duct. 6. Provide sufficient horizontal and vertical clearance from walls and ceilings to provide easy access to joints. 7. Level and plumb bus-way (align vertically and horizontally) before the final tightening of all joints. 8. Ensure that all joint contact surfaces are free of contaminants. 9. Align the busbar ends of adjoining sections, verifying proper busbar alignment, before sliding sections together. 10. Refer to manufacturer drawings supplied for proper installation sequence. 11. Verify that the system phasing matches the bus-way phasing 12. During installation pay special attention to riser bus-ways to protect them from moisture from incomplete roofs, walls and so forth.

7. Indoor Busway Installations


Page 3 of 4

1. Remove the bolts form the two joint tie channels before starting. 2. Be sure the bus-ways are aligned properly before attempting to join them. With the rod engaged in the surge clamp, pull to slide the bus-ways together until the bus-way is spaced. 3. Install joint tie channels with supplied bolts. 4. Using a wrench with longer handle, tighten the joint bolt(s) until the outer head breaks off. 5. End cover shall be fixed at the end of last feeder element in vertical/horizontal run. 6. The last joint after the days work shall be covered completely by plastic sheet to prevent any dust/watering entering the busway. 7. The joint cover shall be fixed after installing the complete run. Till then all the joint covers shall be wrapped with plastic sheet to prevent the busway joints.

8. Safety
1. Safety precautions to be strictly followed during installation, testing as well as charging of any electrical equipment. 2. All appropriate safety protective gear, i.e. helmet, safety shoes, gloves, goggles, etc. should be worn by workmen. 3. Check the electrical connections if you are using any electrically operated machine and make sure that the connections are done properly as per the safety regulations. 4. Wear the safety belt while working on a scaffold or step ladders at high levels. 5. Work site should be kept clean and tidy and ensure after the work is completed. 6. Adequate lighting and ventilation should be provided in work area. 7. The safety matrix is attached.

Page 4 of 4