45 EXTRACTOR
FLEXIBLE DUCT OVER RIGID DUCT WITH METAL BAND, "KRIMP" RIGID DUCT AS REQUIRED
INSULATED FLEXIBLE DUCT (MAXIMUM 8'-0" IN LENGTH)
1" DUCTWRAP INSULATION WITH FOIL VAPOR BARRIER SPIN-IN FITTING WITH INTEGRAL DAMPER AND 45 DEGREE EXTRACTOR (REFER TO SPIN-IN FITTING DETAIL)
FOIL TAPE
STRAINER W/BLOWDOWN
TRIPLE DUTY VALVE OR PROVIDE NON-SLAM CHECK VALVE, FLOW METER AND ISOLATION VALVE.
SHEET METAL PLENUM WITH 1/2" ACOUSTIC LINING. FULL SIZE OF DIFFUSER AND 2" HIGHER THAN NOTED TAP SIZE. SUPPLY TAP SUPPLY TAP
T-BAR DIFFUSER WITH INTERNAL INSULATION (25 NC MAX. @ GIVEN AIR QUANTITIES, SEE PLANS)
SUPPLY INLET
FLEXIBLE CONNECTORS
REDUCERS OR INCREASERS AS REQUIRED PUMP AS SCHEDULED PUMP BASEPLATE CONCRETE HOUSEKEEPING PAD
CEILING LINEAR BAR DIFFUSER SIDE VIEW LENGTH x WIDTH 48"x4"-300 TOTAL CFM END VIEW
SUCTION DIFFUSER
NOTES:
1. USE SPIN-IN FITTING WHERE TAP SIZE IS 2" SMALLER THAN DUCT RAIL DIMENSION. 2. WHERE TAP SIZE IS 3" SMALLER THAN DUCT RAIL DIMENSION BELLMOUTH FITTING MAY BE USED. 3. PROVIDE DAMPER ONLY AT LOCATIONS INDICATED ON THE DRAWINGS WHERE ACCESS IS POSSIBLE.
METAL BANDS (TYPICAL) SUPPLY AIR DUCT
ROUND RIGID SUPPLY DUCT WITH 1" FLEXIBLE DUCT WRAP "KRIMP" END AS REQUIRED
6'-0 " MA XI M UM
SHEET METAL SPACER (DAMPER OPERATOR TO CLEAR INSULATION) RIVET OR SHEET METAL SCREW
INLINE PUMP
STRAINER
VIBRATION ISOLATORS-TYP.
1 PRESSURE GAUGE WITH NEEDLE VALVE AND SNUBBER-TYP. FLOW METER: CIRCUIT SETTER FOR SIZES 2" & SMALLER CIRCUIT SENSOR 2 1/2" & UP
20 GAUGE X 1" METAL STRAP CONNECTED TO STRUCTURE ABOVE (TYPICAL) THROUGH BOLT
ISOLATION VALVE
NOTE:
1. DIFFUSER SHALL BE COMPLETE WITH CENTER "T"-BAR AND OUTER "T"-BAR (ON INLET SIDE).
DRAW THRU UNITS A = STATIC PRESSURE OF AHU IN INCHES OF WATER X 1.25 B = 2 INCHES MINIMUM BLOW THRU UNITS A = 2 INCHES MINIMUM B = STATIC PRESSURE OF AHU IN INCHES OF WATER X 1.25 PLUG
6'-0 "M
AX IMU M
N.C.
FLOW METER: CIRCUIT SETTER FOR SIZES 2" & SMALLER CIRCUIT SENSOR- 21/2" & UP 1/2" GAUGE VALVE CONNECTION - TYP. MANUAL AIR VENT
SPEED WASHER
CLEAN OUT
N.C.
TO TEMPERATURE SENSOR
AIR FLOW
SOUNDLINER DETAIL
TERMINATE SLEEVE FLUSH WITH FINISHED WALL SURFACES SEAL OR CAULK SLEEVES THRU FIRE WALLS IN A SMOKE TIGHT MANNER
WELDED PIN
N.O.
NO SCALE
NOTES:
1. FLEXIBLE DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM RECTANGULAR DUCT CONNECTION BEFORE BENDING. 2. FLEXIBLE DUCT SHOULD NOT EXCEED 6'-0" IN LENGTH. USE RIGID ROUND DUCTWORK WHEN RUNOUTS EXCEED 6'-0".
STRAINER
3/4" HOSE END DRAIN VALVE TWO WAY AUTOMATIC TEMP. CONTROL VALVE 8 FT. MAX P.D. 4 FT. MIN P.D.
Project Number:
NO SCALE
A0601
Date:
NOTE:
SUPPLY AIR DIFFUSER
NOTE:
PIPE AND INSULATION TO BE CENTERED IN SLEEVE - DO NOT SUPPORT PIPE FROM SLEEVE INTERIOR WALLS
PROVIDE INTERMEDIATE DRAIN PAN FOR MULTIPLE (STACKED) COOLING COILS. PIPE INTERMEDIATE DRAIN PAN TO BOTTOM DRAIN PAN
COMBINATION REDUCING/RELIEF VALVE WITH BUILT IN STRAINER AND CHECK VALVE. PROVIDE FAST FILL FEATURE.
RIGID DUCT WITH INSULATION SAME SIZE AS FLEX DUCT. LENGTH NECESSARY TO MEET MAXIMUM FLEX DUCT LENGTH REQUIREMENTS FLEX DUCT (6'-0" MAX) EXTERNALLY INSULATED HOSE CLAMPS (TYP. 2 PL)
1. HEATING WATER SUPPLY CONNECTION SHALL BE UPSTREAM OF AIR FLOW. 2. PROVIDE A THREE WAY CONTROL VALVE ON THE LAST FAN COIL UNIT IN EACH PIPING LOOP. 3. THIS DETAIL APPLIES TO FAN COIL UNITS 6 THRU 10 CHILLED WATER COILS ONLY, SEE "TYPICAL FAN COIL CONNECTION DETAIL" FOR ALL OTHER COIL CONNECTIONS.
FINISHED ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENING (FOR EXPOSED CONDITIONS)
EXTERIOR WALL
04.03.07
Revisions:
1
06.06.07
BRANCH DUCT
END BEARING
3/8" SQUARE ROD VOLUME DAMPER WITH LOCKING TYPE INDICATOR QUADRANT AND SADDLE TO CLEAR INSULATION
Drawn By:
DH
Key Plan:
45
PROVIDE ADJ. 90 26 GA. ELBOW WITH INSULATED FLEX COVER. SEAL JOINTS OF ELBOW
3"
TO SYSTEM FROM SYSTEM CS
P-6 CS
3"
3"
CR
P/T PLUG TYP. STAINLESS STEEL BRAIDED HOSE W/ SWIVEL CONNECTORS - TYP.
1
ISOLATION VALVE TEMPERATURE SENSOR CWS / RFHWS FLOW METER TYP.
TO SYS TEM
1"
LEFRAK RESIDENCE
Sheet:
FLOW METER: CIRCUIT SETTER FOR SIZES 2" & SMALLER CIRCUIT SENSOR- 21/2" & UP
N.C.
HEAT PUMP
UNION TYP.
CWR / RFHWR
STRAINER TWO WAY AUTOMATIC TEMP. CONTROL VALVE 8 FT. MAX P.D. 4 FT. MIN P.D.
MECHANICAL DETAILS
CR
TO TEMPERATURE SENSOR
AIR FLOW
FLOOR
NOTE:
PIPING SCHEMATIC DIAGRAM
NO SCALE
NOTE:
1. HEATING WATER SUPPLY CONNECTION SHALL BE UPSTREAM OF AIR FLOW. 2. PROVIDE A THREE WAY CONTROL VALVE ON THE LAST FAN COIL UNIT IN EACH PIPING LOOP. 3. SEE "FAN COIL UNIT 6 THRU 10 CHILLED WATER COIL CONNECTION DETAIL" FOR PIPING REQUIREMENTS OF FAN COIL UNITS 6 THRU 10 CHILLED WATER COILS. THIS DETAIL DOES NOT APPLY TO THOSE COILS.
M1.1
COPYRIGHT C
2006
INC
SUPPLY DUCT
FROM SYSTEM
TO SYSTEM
TORCHIO
ARCHITECTS