Electrical Power from Genset: Nominal Voltage Un: Nominal Current In: Derating factor: Current required on field Cable considered Resistance per km Reactance per km Admisible current by cable selected Checking between *1 vs. *2 Num. of cables in parallel Distance Gen. to DB: Drop Voltage for this feeder Drop Voltage for this feeder %
20 230 50.20 0.53 94.73 185 0.1 0.07 440 Ok 1 100 1.06 0.46%
kVA V A
Check if is electr. Power without any Efficiency factor to have into account. (check if it is 380V)
cable in trench without other ones, only one cable. *1 4 core of Ohm/km Ohm/km A *2 Here u check current capacity considered only 1 feeder cable m V mm2