Feeder cable calculation

Electrical Power from Genset: Nominal Voltage Un: Nominal Current In: Derating factor: Current required on field Cable considered Resistance per km Reactance per km Admisible current by cable selected Checking between *1 vs. *2 Num. of cables in parallel Distance Gen. to DB: Drop Voltage for this feeder Drop Voltage for this feeder %

20 230 50.20 0.53 94.73 185 0.1 0.07 440 Ok 1 100 1.06 0.46%

kVA V A

Check if is electr. Power without any Efficiency factor to have into account. (check if it is 380V)

cable in trench without other ones, only one cable. *1 4 core of Ohm/km Ohm/km A *2 Here u check current capacity considered only 1 feeder cable m V mm2

out other ones, only one cable.

Current Carrying Capacity XLPE Insulated 0.6/1kV


Cable Size 50 70 95 120 150 185 240 300 400 500 630 In air 30C 3/4 core A 193 245 302 351 399 460 564 649 In ground 20C 3/4 core A 212 259 310 353 392 440 517 585 0.39 0.27 0.19 0.15 0.12 0.1 0.0988 0.080 0.070 0.070 0.070 0.070 0.070 0.070 0.077 0.077 r (at 90C) ohm/km x (50 Hz) ohm/km