Danfoss HPD

Back Channel

Drawing 1
Duct

Drawing 2

Cover

Cover

IP00 IP00

Duct Duct
Cover

SITUATION BEFORE: DRIVE TRIPPING DUE HEATSING OVERHEATING AT FULL LOAD

HLH system sucessfully comissioned in Brazil

3 fans on the top 2 fans on the door Despite all the fans, the drive got tripping in Alarm 29/69 when in full load.

SITUATION AFTER: NO TRIPPING ANYMORE AFTER Back Channel extension

Back Channel Extension

1 fan on the top taking the heating from the Drive`s electronics

Back Channel Extension (made with a cheap metal plate)

The two fans on the top where transferred to the bottom side of the cabinet

Two fans from the top where installed on the bottom adding more air flow inside the drive
This is a spare fan not used

IT SOLVED THE HEATSINK OVERHEATING EFFICIENTLY!!!