HVAC CONTROL I/O POINT SCHEDULE FOR FLY ASH TRANSFER COMPRESSOR HOUSE(#1,2)
DOCUMENT NO. 31021001/00-T-RPP2-WE-012551 DOCUMENT STATUS:

Approval/Certification Information No. of Pages


Doc No: PB-03414 Rev. :

Rev. No. 0

FOR INFORMATION FOR APPROVAL FOR REVIEW FOR CONSTRUCTION AS BUILT

HVAC CONTROL I/O POINT SCHEDULE


(LEGEND)
FOR CONSTRUCTION

PJT : RABIGH POWER PLANT NO.2


COLUMN NUMBER
1*

DOC NO : 31021001/00-T-RPP2-WE-012551, REV. 0

DESCRIPTION

NO. : This column shows a serial sequence. This number has no relation with the KKS numbers. SIGNAL KKS TAG NO : Signal identification number in KKS numbering system. See detail the KKS identification. SIGNAL SERVICE DESCRIPTION : Service description of each signal DEVICE DISCRIPTION : Service description of field device (Max. 25 digit inc. space) SIGNAL STATUS : Detail signal status from the field device (Max. 6 digit inc. space) DEVICE TYPE : Detail description of field instrument type.
GS : Position Swith i.e. limit switch PDS : Pressure Differential Switch FS : Flow Switch TT : Temperature Transmitter MT : Moisture Transmitter PT : Pressure Transmitter MD : Motorized Damper Actuator MFD : Motorized Fire Damper Actuator Motor 1 : 480V MCC controlled equipment DDC : Direct Digital Controller LCP : Local Control Panel FAP : Fire Alarm Panel TCV : Temperature Control Valve with Actuator MV : Motorized shut-off Valve with Actuator

2*

3*

4*

5*

SIGNAL TYPE : The types of Inputs and Outputs are shown as follows;
AI : Analog Input AO: Analog Output DI : Digital Input DO : Digital Output

PAGE 1 OF 3

HVAC CONTROL I/O POINT SCHEDULE


(LEGEND)
FOR CONSTRUCTION

PJT : RABIGH POWER PLANT NO.2


COLUMN NUMBER
6* SIGNAL LEVEL : The types of output signal of each instrument are shown as follows;
4 ~ 20mA : Analog signal 0 ~ 10V DC : Analog signal 24V DC : Digital signal PT100 : Analog signal for RTD K-Type, E-Type : Analog signal for Thermocouple

DOC NO : 31021001/00-T-RPP2-WE-012551, REV. 0

DESCRIPTION

7*

POWER SOURCE : The types of Power Source required are shown as follows;
I : Internal (the power is supplied by DCS) E : External (the power is supplied by others)

8*

FROM / TO : Signal Traversal


FLD / / FLD : From Field to DDC : From DDC to Field MCC / / MCC : From MCC to DDC : From DDC to MCC FAP / / FAP : From FAP to DDC : From DDC to FAP

9*

CONTACT STATUS : The contact status of binal signal are shown as follows;
NO : Normal Open NC : Normal Close

10 *

PROCESS RANGE : Process measuring range of the analog signal PROCESS UNIT : The measuring units are specified on the Tender specification PROCESS SET POINT : The point of actuation of analog and digital instruments.
HIHI : High High HI : High LOLO : Low Low LO : Low

11 *

12 *

13 *

REFERENCE P&ID NO : P&ID number.

PAGE 2 OF 3

HVAC CONTROL I/O POINT SCHEDULE


(LEGEND)
FOR CONSTRUCTION

PJT : RABIGH POWER PLANT NO.2


COLUMN NUMBER
14 * / 14A *

DOC NO : 31021001/00-T-RPP2-WE-012551, REV. 0

DESCRIPTION
SYSTEM PACKAGE : It is the Unit Automation and Plant Automation classification according to the DCS Function Area Segregation concept. The Common Automation Function Areas are W11, W12, W21, W22, F01, F02, F11, F12, C10 and C20. (Please refer to the DCS segregation concept diagram) The Unit Automation Function Areas 110, 120, 121, 122, 130, 131, 132, 140, 141, 142. (Please refer to the DCS segregation concept diagram) PARTITION : Signal partition requirement on the DCS module.
0 : No redundancy 1, 2, or 3 : Signal redundancy i.e. Signal shall be segregated on the basis of group number.

15 *

16 *

REVISION : The revision a particular entry has been changed.


REV : A, B, C, D ~ for approval, 0, 1, 2, 3 ~ for Construction MOD : A (Added), M (Modified), D (Deleted)

17 *

REMARK : General remarks pertaining to the I/O point.

PAGE 3 OF 3

` (HVAC CONTROL SYSTEM)


PJT : RABIGH POWER PLANT NO.2
1 NO 2 SIGNAL KKS TAG NO UNIT LVL1 LVL2 LVL3 3 SIGNAL SERVICE DECRIPTION DEVICE DESCRIPTION
SIGNAL STATUS

4 DEVICE TYPE

5 SIGNAL TYPE

6 SIGNAL LEVEL

7 PWR SRC

8 FROM /TO

9 CONTACT

10 PROCESS RANGE

11 PROCESS UNIT

12 PROCESS SETPOINT LOLO LO HI HIHI

13 REFERENCE P&ID NO

14 SYSTEM PACKAGE

FOR CONSTRUCTION DOC NO : 31021001/00-T-RPP2-WE-012551, REV. 0 16 14A 15 17 REVISION LOCATION PARTITION REMARKS REV MOD

[I/O SCHEDULE FOR F22-1] 1 C00 1SAL22 AN001 2 C00 1SAL22 AN001 3 C00 1SAL22 AN001 4 C00 1SAL22 AN001 5 C00 1SAL22 AN001 6 C00 1SAL22 AN001 NEW C00 1SAL22 AN001 7 C00 1SAL22 AN002 8 C00 1SAL22 AN002 9 C00 1SAL22 AN002 10 C00 1SAL22 AN002 11 C00 1SAL22 AN002 12 C00 1SAL22 AN002 NEW C00 1SAL22 AN002 NEW C00 1SAL22 GH001 NEW C00 1SAL22 AN001S NEW C00 1SAL22 AN002S

YB01 YB02 XB01 XB02 XB48 XB42 XB41 YB01 YB02 XB01 XB02 XB48 XB42 XB41 XB01 XB15 XB15

MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 FIRE ALARM HAND SWITCH FOR AN001S HAND SWITCH FOR AN002S

ON OFF REM STA ON STA OFF STA FAULT TEST STA ON OFF REM STA ON STA OFF STA FAULT TEST STA ALARM ON/OFF ON/OFF

Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 FAP HS HS

DO DO DI DI DI DI DI DO DO DI DI DI DI DI DI DI DI

24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC

E E I I I I I E E I I I I I I I I

/ MCC / MCC MCC / MCC / MCC / MCC / MCC / / MCC / MCC MCC / MCC / MCC / MCC / MCC / FAP / FLD / FLD /

NO NO NO NO NO NC NO NO NO NO NO NO NC NO NC NO NO

31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550

HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP

F11 F11 F11 F11 F11 F11 F11 F11 F11 F11 F11 F11 F11 F11

1 1 1 1 1 1 1 2 2 2 2 2 2 2 0 0 0

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

M M M M M M A M M M M M M A A A A

NOTE : ALL ABOVE I/O SHALL BE ASSIGNED IN F77&101 DDC PANEL (C00SAAE101GH001) FAN WILL BE OPERATED BY HAND SWITCH LOCALLY AND BY BMS REMOTELY.

[I/O SCHEDULE FOR F22-2] 1 C00 2SAL22 AN001 2 C00 2SAL22 AN001 3 C00 2SAL22 AN001 4 C00 2SAL22 AN001 5 C00 2SAL22 AN001 6 C00 2SAL22 AN001 NEW C00 2SAL22 AN001 7 C00 2SAL22 AN002 8 C00 2SAL22 AN002 9 C00 2SAL22 AN002 10 C00 2SAL22 AN002 11 C00 2SAL22 AN002 12 C00 2SAL22 AN002 NEW C00 2SAL22 AN002 NEW C00 2SAL22 GH001 NEW C00 2SAL22 AN001S NEW C00 2SAL22 AN002S

YB01 YB02 XB01 XB02 XB48 XB42 XB41 YB01 YB02 XB01 XB02 XB48 XB42 XB41 XB01 XB15 XB15

MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN001 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 MCC FOR AN002 FIRE ALARM HAND SWITCH FOR AN001S HAND SWITCH FOR AN002S

ON OFF REM STA ON STA OFF STA FAULT TEST STA ON OFF REM STA ON STA OFF STA FAULT TEST STA ALARM ON/OFF ON/OFF

Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 Motor 1 FAP HS HS

DO DO DI DI DI DI DI DO DO DI DI DI DI DI DI DI DI

24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC

E E I I I I I E E I I I I I I I I

/ MCC / MCC MCC / MCC / MCC / MCC / MCC / / MCC / MCC MCC / MCC / MCC / MCC / MCC / FAP / FLD / FLD /

NO NO NO NO NO NC NO NO NO NO NO NO NC NO NC NO NO

31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550 31021001-T-RPP2-WD-012550

HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP HCP

F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101 F77&F101

1 1 1 1 1 1 1 2 2 2 2 2 2 2 0 0 0

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

M M M M M M A M M M M M M A A A A

NOTE : ALL ABOVE I/O SHALL BE ASSIGNED IN F11 DDC PANEL (C00SAC11GH001) FAN WILL BE OPERATED BY HAND SWITCH LOCALLY AND BY BMS REMOTELY.