Beruflich Dokumente
Kultur Dokumente
Close viewer Like Comment Follow Flag o Flag as Promotion o Flag as Job o Flag as Inappropriate More o Reply Privately
3 comments
VUnfollow Follow V V Krishna 1) Compared to Trefoil Fomration derating factor shall be more for cables laid in Flat Formation (This is very General & the specific value depends on No.of Circuits,Spacing between the Ckts etc for the same depth of burial) 2) Flat Formation occupies Space compared to Trefoil Formation 3) Trefoil Formation requires Trefoil Clamps (FRP) at regular intervals (Every 5 mts etc.,) 4 days ago Unlike Like
RudraUnfollow Follow Rudra Rudra Ghosh Both have certain advantage and disadvantage, trefoil formation of cable configuration has the advantage of minimizing the sheath circulating currents induced by the magnetic flux linking the cable conductors and Metallic sheath .But it is not efficient heat dissipation because there is an appreciable mutual heating effect of the three cables. In order to improve the natural heat dissipation from around the cable circuits the three single-core cables could be installed in flat formation. Again sometimes in case trefoil formation if laying is mainly in cable tray during fault condition cable may get twisted unnecessarily due to occurrence of electro-dynamic force in the cable, where force is zero in flat formation 2 days ago Unlike Like
RaviUnfollow Follow Ravi Ravi Prakash TREFOIL CLAMPS ARE USED IN THREE PHASE ALTERNATE CURRENT POWER CABLING TO NULLIFY THE MAGNETIC FIELDS PRODUCED IN THE THREE PHASE CBLES WHEN CURRENT FLOWS.IT ALSO HELPS IN REUDCING THE EDDY CURRENT HEATING IN THE METAL ENCLOSURES OF CABLES. 21 hours ago