GRID

50 51

Label: OG_FORD_PNL CTR: 500/5 TD/Tap: 0.6 / 0.4 Inst. 1: 16 Inst. 2: 20 Label: OG_FORD_PNL CTR: 500/1 TD/Tap: 0.6 / 0.1

Ford

Label: HG Fuse Rating: 100 AMP

50 51

Label: outdoor REJ601 CTR: 200/5 TD/Tap: 0.52 / 0.9 Label: outdoor pnl REJ6 CTR: 200/5 TD/Tap: 0.5 / 0.25

Plant 1
Label: IC_HVPNL_Plant1 CTR: 200/5 TD/Tap: 0.46 / 0.85 Label: IC_HVPNL_Plant1 CTR: 200/5 TD/Tap: 0.45 / 0.2 Label: OG2_TR12 CTR: 100/5 TD/Tap: 0.8 / 1.4 Label: OG2_TR12 CTR: 100/5 TD/Tap: 0.1 / 0.25 Label: OG3_HVPNL_Plant1 CTR: 150/5 TD/Tap: 0.33 / 1.1 Label: OG3_HVPNL_Plant1 CTR: 150/5 TD/Tap: 0.3 / 0.2

50 51

50 51

Label: OG1_TR11 CTR: 100/5 TD/Tap: 0.1 / 1.4 Label: OG1_TR11 CTR: 100/5 TD/Tap: 0.06 / 0.2

50 51

50 51

Label: TR11 1600 kVA

Label: TR12 1600 kVA Label: IC_HVPNL_Plant2 CTR: 150/5 TD/Tap: 0.4 / 1 Label: IC_HVPNL_Plant2 CTR: 150/5 TD/Tap: 0.2 / 0.2 Label: OG1_TR21 CTR: 120/5 TD/Tap: 0.1 / 1.25 Label: OG1_TR21 CTR: 120/5 TD/Tap: 0.1 / 0.2

Plant 2
50 51

Label: LTPNL 11_IC Max A/Plug/Setting: 3200 / 2500 LT PU/D: 1 / 2T-2 ST PU/INT/D: 1.25 / OUT / .02 Inst PU/D: 6 / FIX Label: LT PNL 11_IC Sensor Setting: 2500 Ground Setting: 300 / 0.5 / .1

Label: LTPNL 12_IC Max A/Plug/Setting: 3200 / 2500 LT PU/D: 1 / 2T-2 ST PU/INT/D: 1.5 / OUT / .02 Inst PU/D: 6 / FIX Label: LTPNL 12_IC Sensor Setting: 2500 Ground Setting: 300 / 0.1 / .1

50 51

50 51

Label: OG2_TR22 CTR: 120/5 TD/Tap: 0.8 / 1.25 Label: OG2_TR22 CTR: 120/5 TD/Tap: 0.1 / 0.2

Label: TR21 1600 kVA

Label: TR22 1600 kVA

Label: LT PNL 21_IC Max A/Plug/Setting: 3200 / 2500 LT PU/D: 1 / 2T-2 ST PU/INT/D: 1.25 / OUT / .02 Inst PU/D: 6 / FIX Label: LT PNL21_IC Sensor Setting: 2500 Ground Setting: 300 / 0.1 / .1

Label: LTPNL 22_IC Max A/Plug/Setting: 3200 / 2500 LT PU/D: 1 / 2T-2 ST PU/INT/D: 1.5 / OUT / .02 Inst PU/D: 6 / FIX Label: LTPNL 22_IC Sensor Setting: 2500 Ground Setting: 300 / 0.1 / .1

REV. DATE

ECO#

DWN APP

DESCRIPTION
Your Com pany Na me Address Address P hone an d w eb site

THIS DRAWING IS PROPRIETARY INFORMATION

Electrical One-Line Diagram


DR AWN BY/DATE: ENG. APP ./D ATE: MFG. APP./D ATE: SCALE: DW G SIZE: P AR T N o.: D WG N o.: R EV.

Recommended Setting Details for Relay at FORD feeding 8 pole structure


0.0 Panel at FORD Siemens SCOPE OF FUNCTION Address Outgoing to 8 pole Structure Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

Other functions are disabled Power System Data 1 Title Setting CTs CT rated primary CT rated secondary Phase over current Protection: 50/51 Parameter Display FCT 50/51 I>> I>> t>> t >> I> I> t> t> tms ti> IEC Curve 10..50000 A 1A/5A Range ON/OFF 0.05-25 x In 0.03-20 sec 0.2-2.5 x In 0.1-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse Range ON/OFF 0.5-15 x In 0.02-20 sec 0.05-2.5 x In 0.03-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse 500 1 Setting ON 16 0.2 0.4 NA 0.6 Normal Inverse Prim Value
8000 200

Range

Setting

Ground over current Protection: 50N/51 N Parameter Display FCT 50N / 51 N IE>> IE>> tE>> TE>> IE> Ie> tE> tE> tms tiE> IEC Curve

Setting ON NS NS 0.1 NS 0.6 Normal Inverse

Prim Value

50

Setting Details forOutdoor Panel


0.1 Outdoor Panel ABB REJ 601 SCOPE OF FUNCTION Address Incomer 1 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

Other functions are disabled Power System Data 1 Title Setting CTs CT rated primary CT rated secondary Phase over current Protection: 50/51 Parameter Display FCT 50/51 I>> I>> t>> t >> I> I> t> t> tms ti> IEC Curve 10..50000 A 1A/5A Range ON/OFF 0.05-25 x In 0.03-20 sec 0.2-2.5 x In 0.1-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse Range ON/OFF 0.5-15 x In 0.02-20 sec 0.05-2.5 x In 0.03-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse 200 5A Setting ON NS NS 0.9 NA 1.1 Normal Inverse Prim Value Range Setting

180

Ground over current Protection: 50N/51 N Parameter Display FCT 50N / 51 N IE>> IE>> tE>> TE>> IE> Ie> tE> tE> tms tiE> IEC Curve

Setting ON NS NS 0.25 NS 0.35 Normal Inverse

Prim Value

50

Setting Details for 11kV Switchgear Panel in Motherson Plant 1


1.1 11 kV HT Panel C&S IRI-PRO 3i-Ei SCOPE OF FUNCTION Address Incomer 1 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

Other functions are disabled Power System Data 1 Title Setting CTs CT rated primary CT rated secondary Phase over current Protection: 50/51 Parameter Display FCT 50/51 I>> I>> t>> t >> I> I> t> t> tms ti> IEC Curve 10..50000 A 1A/5A Range ON/OFF 0.05-25 x In 0.03-20 sec 0.2-2.5 x In 0.1-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse Range ON/OFF 0.5-15 x In 0.02-20 sec 0.05-2.5 x In 0.03-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse 200 5A Setting ON NS NS 0.85 NA 0.46 Normal Inverse Prim Value Range Setting

170

Ground over current Protection: 50N/51 N Parameter Display FCT 50N / 51 N IE>> IE>> tE>> TE>> IE> Ie> tE> tE> tms tiE> IEC Curve

Setting ON NS NS 0.2 NS 0.45 Normal Inverse

Prim Value

40

1.2 11 kV HT Panel C&S IRI-PRO 3i-Ei SCOPE OF FUNCTION Address

Outgoing to Plant 2 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

Other functions are disabled Power System Data 1 Title Setting CTs CT rated primary CT rated secondary Phase over current Protection: 50/51 Parameter Display FCT 50/51 I>> I>> t>> t >> I> I> t> t> tms ti> IEC Curve 10..50000 A 1A/5A Range ON/OFF 0.05-25 x In 0.03-20 sec 0.2-2.5 x In 0.1-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse Range ON/OFF 0.5-15 x In 0.02-20 sec 0.05-2.5 x In 0.03-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse 150 5A Setting ON NS NS 1.1 NA 0.33 Normal Inverse Prim Value Range Setting

165

Ground over current Protection: 50N/51 N Parameter Display FCT 50N / 51 N IE>> IE>> tE>> IE> tE> tms IEC Curve TE>> Ie> tE> tiE>

Setting ON NA NA 0.2 0.3 NA Normal Inverse

Prim Value

30

1.3 11 kV HT Panel MICOM P111 SCOPE OF FUNCTION Address

Outgoing to Transformers 11 and 12 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

Other functions are disabled Power System Data 1 Title Setting CTs CT rated primary CT rated secondary Phase over current Protection: 50/51 Parameter Display FCT 50/51 I> I> t> t> tms ti> IEC Curve 10..50000 A 1A/5A Range ON/OFF 0.2-2.5 x In 0.1-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse Range ON/OFF 0.05-2.5 x In 0.03-150 sec 0.01-1.5 Normal Inverse 3.0 ,Normal Inverse 1.3,Normal Inverse 0.6 Very Inverse ,Extremely Inverse 100 5A Setting ON 1.4 NA 0.1 Normal Inverse Prim Value
140

Range

Setting

Ground over current Protection: 50N/51 N Parameter Display FCT 50N / 51 N IE> Ie> tE> tE> tms tiE> IEC Curve

Setting ON 0.2 0.06 NA Normal Inverse

Prim Value
20

Setting Details for 11kV Switchgear Panel in Motherson Plant 2


2.1 11 kV HT Panel Easun Reyrolle 2TJM 10 SCOPE OF FUNCTION Address Incomer Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

Other functions are disabled Power System Data 1 Title Setting CTs CT rated primary CT rated secondary Phase over current Protection: 50/51 Parameter Display FCT 50/51 I> I> tms ti> Ground over current Protection: 50N/51 N Parameter Display FCT 50N / 51 N IE> Ie> tms tiE> 2.2 11 kV HT Panel Easun Reyrolle 2TJM 10 SCOPE OF FUNCTION Address Setting Title Fault Records Function 50/51 Function 50N/51N Other functions are disabled Power System Data 1 Title Setting CTs CT rated primary CT rated secondary Phase over current Protection: 50/51 Parameter Display FCT 50/51 I> I> tms ti> Ground over current Protection: 50N/51 N Parameter Display FCT 50N / 51 N IE> Ie> tms tiE> 10..50000 A 1A/5A Range ON/OFF 2.5,3.75,5,6.25,7.5,8.75,10 0.05-1.0 Range ON/OFF 1,1.5,2,2.5,3,3.5,4 0.05-1.0 Outgoing to Transformers 21 and 22 Setting Range Enabled/Disabled Setting Enabled 150 5A Setting ON 5 0.4 Setting ON 1 0.2 Prim Value
150

Range

Setting

Prim Value
30

Range 10..50000 A 1A/5A Range ON/OFF 2.5,3.75,5,6.25,7.5,8.75,10 0.05-1.0 Range ON/OFF 1,1.5,2,2.5,3,3.5,4 0.05-1.0

Setting 120 5A Setting ON 6.25 0.1 Setting ON 1 0.1 Prim Value


150

Prim Value
24

1000

10000

HG Fuse

LTPNL 11_IC outdoor REJ601 100

OG1_TR11 IC_HVPNL_Plant1

OG_FORD_PNL

Time in Seconds

10

TR11 1600.0 KVA Transformer A

.01

.1

INRUSH

.5

10

100 Current in Amperes X 10 Time-Current Characteristic Curves

1000

10000 08-16-2013 20:06:28 newmotherson070813

11000 Volt Phase 1 - PATH1:SOURCE1-LTPNL11

1000

10000

HG Fuse Relay IC_HVPNL_Plant2 PU = 150 Relay OG3_HVPNL_Plant1 PU = 165 OG_FORD_PNL outdoor REJ601 LT PNL 21_IC OG3_HVPNL_Plant1

Relay OG1_TR21 PU = 150 100

OG1_TR21 IC_HVPNL_Plant1 10 IC_HVPNL_Plant2 Time in Seconds

TR21 1600.0 KVA A Transformer

.01

.1

in rush

.5

10

100 Current in Amperes X 10

1000

10000 08-16-2013 19:54:40 newmotherson070813

11000 Volt Phase Time-Current Characteristic Curves 2 - Path2: Source1-hvpnl1-hvpnl2-tr21-ltpnl21

1000

10000

LT PNL 11_IC

100

OG_FORD_PNL

outdoor pnl REJ6 IC_HVPNL_Plant1

OG1_TR11

.01

.1 .5

Time in Seconds

10

10

100 Current in Amperes X 10 Time-Current Characteristic Curves

1000

10000 08-16-2013 20:07:28 newmotherson070813

11000 Volt Ground 1 - PATH1:SOURCE1-LTPNL11

1000

10000

LT PNL21_IC Relay OG1_TR21 PU = 24 Relay IC_HVPNL_Plant2 PU = 30

100

OG_FORD_PNL outdoor pnl REJ6

IC_HVPNL_Plant1

OG3_HVPNL_Plant1 OG1_TR21 IC_HVPNL_Plant2

.01

.1 .5

Time in Seconds

10

10

100 Current in Amperes X 10

1000

10000 08-16-2013 20:09:27 newmotherson070813

11000 Volt Ground Time-Current Characteristic Curves 2 - Path2: Source1-hvpnl1-hvpnl2-tr21-ltpnl21