Lampiran Evaluasi kinerja Condensor E-2201

EVALUASI KINERJA CONDENSOR E-2201


A. Data Pengamatan (actual)
Tanggal

Tin=T2210

Tout=T2215

tin = T2941

tout=T2942
o

Wcw=F2216

(ton/hr)

12/07/09

70,00

46,10

26,30

30,50

81,40

13/07/09

70,00

45,00

26,70

30,50

71,20

14/07/09

70,00

45,00

26,60

27,80

73,70

15/07/09

70,00

50,00

27,10

31,00

70,40

16/07/09

70,00

50,70

27,30

31,50

71,00

Rata-rata

70,00

47,36

26,80

30,30

73,54

Pengambilan Data Pada Pukul 10.00-11.00


22T302(
o
C)

22FC304
(T/Hr)

22FC305(T/
Hr)

T2941
(oC)

22FC308(T/
Hr)

22T30417(
o
C)

Data
Thermogun
CWR (10.30)
(oC)

52.6

11.02

4.391

29.9

6.598

52.2

46

6.629

52.6

11.01

3.971

30.2

6.199

52.1

46

7.039

52.75

11.335

3.987

30.55

6.314

52.25

46

7.348

52.6

10.99

3.512

6.698

52.3

46.5

7.478

52.6375

11.08875

3.96525

30.4
30.262
5

6.45225

52.2125

46.125

125.9825

115.025

/8/20

126.747
5

86.472
5

7.1235

7123.5
Qlatent =
1374329.25
Qsensible=

B. Top Reactor gas analisis (14/07/09)


Komponen
H2

Vessel/time
% mol

D-2201
5,11

Laporan Kerja Praktek PT PERTAMINA(PERSERO) RU III

Lampiran Evaluasi kinerja Condensor E-2201

C1
C2
C2+
C3
C3+

% mol
% mol
% mol
% mol
% mol

NIL
3,27
NIL
2,49
87,14

C. Perhitungan
Overhead Condensor (fluida panas)

Tin (T1)

= 52.6375 oC = 126.7475oF

Tout (T2)

= 52.2125oC = 125.9825oF

Cooling Water (fluida dingin)

tin (t1)

= 30.2625oC = 86.4725oF

tout (t2)

= 46.125oC = 115.025oF

Wair

= 73,54 Ton/hr = 162.155,70 lb/hr

Data Design
Shell
ID : 1350 mm = 53,1496 in

Tube
Jumlah tube (Nt) : 647

Baffle Space (B) = 270 mm = 10,6 in

Panjang (L) : 6.096 m = 20 ft

Passes : 1

OD : 25,40 mm = 1 in
BWG : 12
Pitch : 32 mm = 1,26 inchi
Passes : 6

Penentuan Tdew
komponen
H2
C1
C2
C2=
C3
C3=

A
13,6333
0,0000
15,6637
0,0000
15,7260
15,7027

B
164,90
0,00
1511,42
0,00
1878,46
1807,53

C
3,19
0,00
-17,16
0,00
-25,16
-26,15

T
174,40504
174,40504
174,40504
174,40504
174,40504
174,40504

LNPO
PO
P
Ki
yi
xi
12.7047 329319. 36.7782 8954.19
0.0511 5.70682E-06
8
3
8

Laporan Kerja Praktek PT PERTAMINA(PERSERO) RU III

Lampiran Evaluasi kinerja Condensor E-2201

0
6.05182
3
0
3.13958
5
3.51066
9

1
424.886
8
1
23.0942
8
33.4706
6

36.7782
36.7782
36.7782
36.7782
36.7782

0.02719
11.5526
8
0.02719
0.62793
4
0.91006
8

0
0.0327

0
0.002830512

0
0.0249

0
0.039653849

0.8714

0.957510894
1.000000961

Dari Trial didapat nilai Tdew = 174,40504 oF


Taverage = (174,40504 + 117,25) = 145,8275 oF
Perhitungan Heat Duty
Beban panas Q yang dipindahkan dapat dinyatakan dengan cara berikut :
q = w x cp x (t2-t1)
q = 162.155,70 x 0,998 x (86,54-80,24)
q = 1.019.537,748 Btu/hr
q = Q = W x Cp x (T1-T2)

Komponen

yi

Cp(Pada Tav)

Yi . Cp

H2
C2
C3
C3=

0,0511
0,0327
0,0249
0,8714

BTU/lb/oF
3,404
0,460
0,910
0,430
Cp camp

0,1739
0,0150
0,0227
0,3747
0,5863

Perhitungan Log Mean Temperature Difference (LMTD)


Hot Fluid oF

Temperature oF

Cold fluid oF

Difference oF

Laporan Kerja Praktek PT PERTAMINA(PERSERO) RU III

Lampiran Evaluasi kinerja Condensor E-2201

158,00 High temperature


117,25 Low temperature
40,75
difference

86,54
80,24
6,30

71,46
37,01
34,45

Perhitungan True Mean Temperature Difference


Karena aliran yang mengalir berupa aliran counterflow maka F = 1:

Perhitungan Temperature Kalorik


Tc tidak perlu dicari karena viskositas umpan kurang dari 1, sehingga Tc =
Tav, tc = tav
Efektivitas

Design

Actual

Perhitungan Tube
Laporan Kerja Praktek PT PERTAMINA(PERSERO) RU III

Lampiran Evaluasi kinerja Condensor E-2201

1. Flow Area
at = 0,546 in2

(table 10, Process Heat Transfer, Kern)

2. Mass velocity

3. Menghitung Reynold number

D = inside diameter (ft) dari Tabel 10 = 0,834 in/12 = 0,0695 ft


= viscositas diambil dari data design = 0,011 cp = 0,02662 lb/hr.ft

4. jH = 78 dari Fig. 24, Process Heat Transfer, Kern.


5. Menghitung nilai hi
Dari data design didapat :
k = 0,032 kcal/m.hr.oC = 0,02147 Btu/hr.ft. oF
c = 0,193 Btu/lb.oF

6. Menghitung Design Overall Coefficient (Ud)


a = 0,2618 , table 10, Process Heat Transfer, Kern.

Laporan Kerja Praktek PT PERTAMINA(PERSERO) RU III

Lampiran Evaluasi kinerja Condensor E-2201

A = NT . a . L
A = 931 x 16 x 0,2618 = 3.899,77

7. Menghitung ho dengan Trial and Error


Trial ho = 6057,435 Btu/(hr)(ft)(oF)
Tv = 145,8275 oF
tv = 83,39 oF
tw = ta + ho/(hio + ho) . (Tv ta)

jadi didapat nilai ho = 85.545,58 Btu / (hr)(ft)(oF)


Perhitungan Shell
1. Shell side

2. Mass Velocity

3. Reynold Number
Pada tav = 83,39 oF dari Fig. 14 (Process Heat Transfer, Kern) didapat:
= 0,89 cp = 2,1538 lb / (ft)(hr).
Laporan Kerja Praktek PT PERTAMINA(PERSERO) RU III

Lampiran Evaluasi kinerja Condensor E-2201

De = 0,72 in = 0,06 ft (Fig. 28, Process Heat Tranfer, Donald, Q.


Kern)

4. jH = 50 ditentukan menurut harga Re dengan Fig. 28, Process Heat


Transfer, Donald Q. Kern.
Perhitungan Clean Overall Coefficient (Uc)

Menghitung Fouling Factor (Rd)

Perhitungan Pressure Drop

Shell side
Untuk Re =7.091,509 dari fig.29 Kern didapat f = 0,00225
Jumlah Cross N + 1 = 12L/B

s = 1 untuk air
Ds = IDs/12 = 43,3/12 = 3,608

Laporan Kerja Praktek PT PERTAMINA(PERSERO) RU III

Lampiran Evaluasi kinerja Condensor E-2201

Tube side
P tube = Pt + Pr
a. Pt

Pada Re =

, f = 0,00022

P = 44,9 kg/cm2 (diambil dari data desain Heat Condenser E-2201)


s = 0,419 (hal 141, Data Book On Hydrocarbons, J.B. Maxwell)

b.

Nilai

diperoleh dari figure 27, Kern pada G t = 8.618,946

adalah 0,001

Jadi PT = Pt + P = (0,009546 + 0,000172)psi = 0,009718 psi

Laporan Kerja Praktek PT PERTAMINA(PERSERO) RU III