SEQUENCE OF EVENTS WHILE STARING CHILLER

Power ON

Close IGV
YES

CHWP and CWP Relay de-energized

Restart inhibit Timer timing out

Test IGV

YES

YES

YES

NO

Chiller mode set to AUTO


YES

CHWP Relay energized


YES

Confirm CHW flow

Time out 3 min if no flow

Start Oil pump


YES

Call for heating or YES cooling

Confirm CHW flow

Time out 3 min if no flow

Time out 3 min if no flow

Confirm Oil pressure 9PSID


YES YES YES

YES

Energize vent line solenoid

Start compressor in X-line DELTA configuration

Modulate IGV to satisfy set point

Shutdown Sequence

STOP

Call for heating or cooling OR Chiller mode is set to STOP

Close IGV for 50s

YES

Compressor De-energized
YES

Oil Pump De-energized


YES

Chiller mode set to stop


YES 30s

CWHP relay de-energized