EXTERNAL STATIC PRESSURE CALCULATION Project Job No Date : Rev Sl No 1 2 : MSE Hotel :24/06/2013 :0 Rectangular Duct Size (mm)

EA DUCT 200x150 Total Length Location Ref Drawing No Air Qty (Lps) 126 : Roof Floor :TX/8/17 (Toilet Extract Fan)

Eq. length 3 20

Pr. Drop (Pa/m) 1.545 1.545

Total Pr. Drop (Pa) 4.635 30.90 35.54 10.66 15 35

Remarks

3 4

Sub Total Add 30 % for fittings like Elbows, collars, vanes etc Fire Damper Diffuser

TOTAL

131.73

EXTERNAL STATIC PRESSURE CALCULATION Project Job No Date : Rev Sl No 1 2 : MSE Hotel :24/06/2013 :0 Rectangular Duct Size (mm) EA DUCT 250x200 Total Length Location Ref Drawing No Air Qty (Lps) 240 : Roof Floor :KX/8/11 (Kitchen Extract Fan)

Eq. length 3 25

Pr. Drop (Pa/m) 1.435 1.435

Total Pr. Drop (Pa) 4.305 35.88 40.18 12.05 15 35

Remarks

3 4 5

Sub Total Add 30 % for fittings like Elbows, collars, vanes etc Fire Damper Diffuser Kitchen Hood TOTAL

Details Not Available 142.41