Describe the Main Features of the Series C System

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics

Honeywell

Series C Deliverables Key features of Series C hardware R300 performance targets

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

R300 Series C Deliverables Products and Functions delivered under the Series C Umbrella:
Includes Series C I/O Series C FIM C300 Control Firewall

Honeywell

Related Deliverables:
Includes New FTE Bridge firmware that supports C300 to selected Series A I/O Allow FTE Bridge firmware to be upgraded from a R300 system

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

R300 Series C Deliverables, contd. Products delivered in R300 Series C Release


C300 Controller HART (HLAI) Analog Input HART Analog Output Discrete Input Discrete Output Low Level Mux Input

Honeywell

Fieldbus Interface Module (FIM) Control Firewall Power System

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: Series C Deliverables

Honeywell

Which of these statements about the Series C deliverables is false?


A) It includes Series C I/O, C300, Series C FIM and Control Firewall B) It includes a new Power System C) New FTE Bridge firmware is required but cannot be upgraded from a R300 system

Correct! Incorrect. The false The false statement is " New is " New FTE Bridge FTE The Your correct answer: answer is: statement firmware Bridge firmware is required is required but it cannot but it be cannot upgraded be You must answer the question before You Incorrect Correct did You not answer answered -Click Clickanywhere anywhere this this question correctly! to tocontinue continue completely upgraded from from a R300 a R300 system." system." continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics

Honeywell

Series C Deliverables
Key features of Series C hardware R300 performance targets

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Packaging - Overview Series C term is for the new styling for family of Controller and I/O Space-efficient design
Designed Vertical No electronic card files Zero Footprint power system does not impact module space >30% reductions compared to equivalent HPM

Honeywell

Combines I/O Processor and Field Terminations into one Assembly


Fewer components providing higher MTBF and Availability

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Key Attributes Environmental ratings equivalent to HPM


Temperature, corrosives, EMI/RFI, Vibration, other equal to HPM Class 1 Div 2/Zone 2 interface & mounting support

Honeywell

Approvals Support (CE, FM, CSA, ATEX, and so on)


No plans for UL certification of complete system

Corrosion protected models All Series C components can be mixed and matched in cabinet Electronics mounted to IOTA
Module Removal and Insertion Under Power (RIUP) Reduces footprint

Packaged cabinet solution


Similar to TPS Process Manager today

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Key Attributes, contd. Designed Vertical


More Uniform Heat Management Reduces hot spots More Efficient Field Wiring Top/Bottom Wiring Entry More Natural Terminations No Severe Wire Bends

Honeywell

Space Efficient Design


Comparable to highest density current competitive offerings

Modular Approach
Removable Terminal Blocks

Integral Shields Termination

C300 Controller Architecture Describe the Main Features of the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Mechanical Keying Modules will have Key to prevent insertion into invalid IOTA Intended to prevent inadvertent insertion of Module
Average Use

Honeywell

Keys

Key Slots

C300 Controller Architecture Describe the Main Features of the Series C System

10

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

New Terminology IOTA Support IOTA Carrier IOTA (Input/Output Termination Assembly) IOM (Input/Output Module)

Honeywell

C300 Controller Architecture Describe the Main Features of the Series C System

11

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

I/O Options for C300 Series C I/O


New form Factor AI, AO, DI, DO, LLMUX

Honeywell

Series C Fieldbus Interface


PMIO
As supported by C200

FTEB connected Series A I/O


Serial Interface, Profibus Interface, DeviceNet Interface, and Pulse Input NOT regular chassis I/O

FTEB connections to AB PLCs


Using a bridge chassis with a FTEB and downlink CNI
C300 Controller Architecture Describe the Main Features of the Series C System

12

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Main Components Mounting concept:


Single cabinet side for electronics and terminations Cable tray mounted carrier/IOTA with:

Honeywell

Replaceable Module Power and Communication Connectors Field Wiring Connections

Vertical stacking of elements


Natural flow of field wiring

Channel mount
Channel is like PM FTA channel Channel is not the same as FTA and cannot be used for Series C mounting

C300 Controller Architecture Describe the Main Features of the Series C System

13

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

New Cabinet Design Power Supply Area I/O Rail Area

Honeywell

Batteries/ Battery Charger

C300 Controller Architecture Describe the Main Features of the Series C System

14

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 2: Packaging Why is Series C a more space efficient design?


A) Designed Vertical
B) No electronic card files C) Power system does not occupy footprint D) All of the above

Honeywell

The Your correct answer: answer is: Incorrect! Correct! All All of ofthe the above abovestatements statementsare aretrue trueand and make Series C a more space efficient You must answer the question before design. You Incorrect Correct did You not answer answered -Click Clickanywhere anywhere this this question correctly! to tocontinue continue completely continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the Main Features of the Series C System

15

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 3: Terminology Which of the following is not a Series C hardware terminology?


A) IOTA Support
B) IOTA Carrier C) IOTA D) IOM E) CPM

Honeywell

Incorrect. Correct! The Theterm term"CPM" "CPM"is isnot notaaSeries SeriesC C The correct Your answer: answer is: hardware terminology and is used when You must answer question before referring to athe C200 controller. You Incorrect Correct did You not answer answered -Click Click anywhere anywhere this this question correctly! to tocontinue continue completely continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the Main Features of the Series C System

16

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics

Honeywell

Series C Deliverables
Key features of Series C hardware R300 performance targets

C300 Controller Architecture Describe the Main Features of the Series C System

17

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

R300 Performance Targets

Honeywell

FEATURE Fault-Tolerant Ethernet FTE Nodes per Community Non-FTE Nodes per Community ACE No. ACE per Server Controller No. Controllers per Server (C200 or C300) Latency Analog Digital

R210

R300

200 200

330 (200) 200

10

16 250 ms 100 ms

1: 330 nodes per community if no FTEBs are present; 200 nodes per community with FTEBs.

C300 Controller Architecture Describe the Main Features of the Series C System

18

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Limitations The following is not supported with C300:


Peer-to-Peer communications with FTEB-based IOLIMs Series C I/O and PM I/O cannot be mixed on the same I/O Link

Honeywell

The following will not be tested and therefore not supported in R300:
C200 Peer-to-Peer communications with Series C FIM modules C300 Peer-to-Peer communications with FTEB-based (Series A) FIM modules

C300 Controller Architecture Describe the Main Features of the Series C System

19

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 4: Rules
A) Peer-to-peer communication with FTEB based IOLIMs is not supported B) Series C I/O and PM I/O cannot be mixed on the same I/O Link

Honeywell

Which of the following statements is true about the Series C system?

C) C200 Peer-to-peer communications with Series C FIM modules is not supported


D) C300 Peer-to-peer communications with FTEBbased (Series A) FIM modules is not supported E) All of the above

The Your correct answer: answer is: Incorrect. Correct! All All of ofthe the above abovestatements statements You must answer the question before are true about the Series C system. You Incorrect Correct did You not answer answered -Click Clickanywhere anywhere this this question correctly! to tocontinue continue completely continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the Main Features of the Series C System

20

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary Series C hardware includes Series C I/O (HART AI, AO, DI, DO, LLMUX)
Series C FIM C300 Controller Control Firewall

Honeywell

Series C is a space efficient design that combines I/O processor and field termination into one assembly Series C electronics are mounted to IOTAs reducing footprint and supporting module removal and insertion under power (RIUP) C300 controller supports Series C, Series A, and PM I/O, Series C Fieldbus interface and FTEB connections to AB PLCs via Downlink CNI 16 C300 controllers are supported per server C300 Peer-to-Peer communications with FTEB-based IOLIMs is not supported Series C and PM I/O cannot be mixed on the same I/O link
C300 Controller Architecture Describe the Main Features of the Series C System

21

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Describe the main features of the Series C system

Completion Certificate

Proceed to the next lesson in your course material


C300 Controller Architecture Describe the Main Features of the Series C System

22

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Describe the Architecture of Series C System

C300 Controller Architecture Describe the Architecture of Series C System

23

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Experion Platform Architecture


Advanced Enterprise Wide Applications Business FLEX Workcenter POMS, OptiVISION
Plant Wide Data Warehouse PHD Casual User Secure Read Only Process Display Web Server eServer Desktop Access for Business Applications Web Browsers

Honeywell
Integrated Physical Security Enterprise Building Integrator Plant Simulation UniSim

Firewall

Business Network
Plant Asset Management Asset Manager Remote Operations Experion Station Multivariable Control Video as a Process Sensor Digital Video Manager and Optimization Profit Suite

Video Ethernet

Advanced Applications Network


Integrated Supervisory Control ACE Web-based Human Interface Experion Station ASM Operator Effectiveness Ergonomic Operator Consoles Icon Series Precision Measurement Redundant and Control Global Database & Historian Quality Control System Experion Server

Focus of this Presentation


Supervisory Control Network
Wireless Access Regulatory, Logic Sequential & Model Based Controls C300/C200 & Profit Loop Redundant and/or Remote I/O Wireless Transmitters

Local Control Network

Field Mobility Mobile PKS

Field Rounds Automation IntelaTrac PKS

SIL 3 Safety System Safety Manager Basic Process Controller Manager Investment Protection for TPS/TDC Experion on LCN

C300 Controller Architecture Describe the Architecture of Series C System

24

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series C Architecture

Honeywell

C300 Controller Architecture Describe the Architecture of Series C System

25

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: Architecture

Honeywell

Which of the following statements is not true about the Series C Architecture?
A) Series C FIM is connected to L1 or L2 switch B) Serial Interface, Pulse Input, Device Net Interface, and Profibus Interface Series A I/Os are connected to Control Firewall using FTEB C) Allen Bradely PLCs can also be connected to a rack, and then to the Control Firewall using an FTEB D) All of the above

Incorrect. Correct! The Thefalse falsestatement statementis is""Series SeriesC CFIM FIMis is connected to L1 or L2 Cisco switch". The Series C Yourcorrect The answer: answer is: FIM is the Fieldbus interface module which You must answer the question before connects to the Control Firewall via FTE. You Incorrect Correct did You not answer answered -Click Click anywhere anywhere this this question correctly! to tocontinue continue completely continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the Architecture of Series C System

26

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary

Honeywell

Control Firewalls are connected to Level 1 or Level 2 switches The C300 Controller is connected to the Control Firewall using FTE The Series C FIM is the Fieldbus interface. This module also connects to the Control Firewall via FTE Series A Rack IO connects to the C300 through the Control Firewall using an FTEB
This IO is currently limited to Serial Interface, Pulse Input, DeviceNet Interface and Profibus Interface modules only. This rack is connected to the Control Firewall using an FTEB and via FTE

Allen Bradley PLCs can also be connected to a Rack and then to the Control Firewall using an FTEB

C300 Controller Architecture Describe the Architecture of Series C System

27

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Describe the Architecture of Series C System

Completion Certificate

Proceed to the next lesson in your course material


C300 Controller Architecture Describe the Architecture of Series C System

28

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Describe Series C Input-Output Modules and Options

C300 Controller Architecture Describe Series C Input-Output Modules and Options

29

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Controller Supported I/O Flexible I/O support:


Adaptable to fit range of I/O interface requirements mix and match Can be any mix of PMIO Series C I/O Series A Chassis I/O (supported modules only) through FTE Bridge module FIMs 64 primary I/O units per C300 Support 2 on board IOLINK interfaces Each IOL can support 40 I/O units

Honeywell
IOL Connection

IOL Connection
C300 Controller Architecture Describe Series C Input-Output Modules and Options

30

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Types of Series C I/O Modules HART Analog Input (AI) 16 Channels HART Analog Output (AO) 16 Channels Digital Input (DI) 32 Channels 2 physical types
24VDC Input Common Ground (Non-Isolated) 100VAC/120VAC/125VDC/240VAC (Isolated)

Honeywell

Digital Output (DO) 32 Channels


Relay Extension Board

Low Level Analog Input (LL) 64 channels


Thermocouple and RTD

AI, AO, DI and DO are optionally redundant LL Inputs are not available in redundant configuration

C300 Controller Architecture Describe Series C Input-Output Modules and Options

31

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Non-Redundant Series C I/O Module IOM is physically placed on an IOTA The IOTA has all the wiring and power connections The IOM has the electronics and diagnostics AI, AO, and LL modules mount on a 6 IOTA DI/DO modules mount on a 9 IOTA
Calibration
Field Termination I/O Module

Honeywell
I/O Link Connection

Resistors / Jumpers
32

C300 Controller Architecture Describe Series C Input-Output Modules and Options

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: Series C I/O Support

Honeywell

Which of the following statements is true about C300 I/O Support?


A) Supports 2 I/O Link interfaces
B) Supports mix and match of I/O types C) 64 primary IO units per C300, 40 per I/O Link D) HLAI, HLAO, DI, DO and LL type Series C I/O's E) All of the above

The correct Your answer: answer is: Correct! Incorrect. All All of the of the above above statements statements are You must answer the question before are true true about about Series Series C C I/O I/O support. support. You Incorrect Correct did You not answer answered -Click Click anywhere anywhere this this question correctly! to tocontinue continue completely continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe Series C Input-Output Modules and Options

33

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Redundant Series C I/O Module Same IO module as non redundant AI, AO, DI, DO modules mount on a 12 IOTA Modular Redundancy Modular Connection System
No Common Backplane No Single Point of Failure
Field Termination I/O Module

Honeywell
I/O Link Connection

I/O Termination Assembly

Redundant IOM

C300 Controller Architecture Describe Series C Input-Output Modules and Options

34

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Diagnostic LEDs

Honeywell

Power and Status LEDs on the module itself Provides display of any failure conditions

C300 Controller Architecture Describe Series C Input-Output Modules and Options

35

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

HART Analog Input 16 Analog Channels Supports Integrated HART Communications 4 Analog Channels support Voltage mode Optionally Redundant

Honeywell

50msec Scan for 4-20ma input


4 configurable modems 250ms Loop Latency

C300 Controller Architecture Describe Series C Input-Output Modules and Options

36

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

HART Analog Input Non Redundant

Honeywell
I/O Link Connections

Differential Voltage Input Channels 13-16

Analog Input I/O Module I/O Link Address

C300 Controller Architecture Describe Series C Input-Output Modules and Options

37

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 2: Series C I/O Support Which of the these statements explains an IOTA?
A) IOTA has all wiring and power connections B) Power and Status LEDs are located on the IOTA

Honeywell

C) Same IOTA is used for non-redundant and redundant IOM

The Your correct answer: answer is: has Correct! Incorrect. The The IOTA IOTA has all the all the wiring wiring and You must answer the question before and power power connections. connections. You Incorrect Correct did You not answer answered -Click Clickanywhere anywhere this this question correctly! to tocontinue continue completely continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe Series C Input-Output Modules and Options

38

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

IOM Addressing and IOLINK

Honeywell
I/O Link Connections

IOM Address

C300 Controller Architecture Describe Series C Input-Output Modules and Options

39

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

HART Analog Input Wiring Options

Honeywell

Channels 1-12

Channels 13-16

C300 Controller Architecture Describe Series C Input-Output Modules and Options

40

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

HART Analog Input Redundant


Module Fuse

Honeywell

I/O Link Connections I/O Link Address

Analog Input I/O Module primary and redundant

C300 Controller Architecture Describe Series C Input-Output Modules and Options

41

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

HART Analog Input New Detail Displays

Honeywell

C300 Controller Architecture Describe Series C Input-Output Modules and Options

42

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

HART Analog Output 16 Analog Channels Supports Integrated HART Communications Optionally Redundant 4 configurable modems 250ms Loop Latency when used with Series C HLAI

Honeywell

C300 Controller Architecture Describe Series C Input-Output Modules and Options

43

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

HART Analog Output, contd.


Calibration Voltage Reference

Honeywell
I/O Link Connections

I/O Link Address

Analog Output I/O Module

Standby Manual (Future)


C300 Controller Architecture Describe Series C Input-Output Modules and Options

44

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

HART Analog Output New Detail Displays

Honeywell

C300 Controller Architecture Describe Series C Input-Output Modules and Options

45

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Low Level Inputs 64 Channel Low Level Multiplexer Analog Input


Thermocouple (T/C) and RTD

Honeywell

Initially, the Series C LLMUX will only use the New Solid State FTAs
Support for FTAs requiring the Power Adapter FTA will be provided in a subsequent release

With the new Solid State FTAs:


OTD before propagation of PV every 1 sec Does not require Power Adapter FTA Can be used with existing UCN/xPM installations

With the existing FTAs:


OTD propagates every 30 sec

FTAs will require standard FTA Channel and cannot be mounted on IOTA Carrier

C300 Controller Architecture Describe Series C Input-Output Modules and Options

46

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

LLMUX Solutions R300 Solution


LL IN-CABINET CONFIGURATION
Power Status

Honeywell Power Adapter Solution (Future)


LL REMOTE CONFIGURATION
A-Size FTA Cable
CU/CC-TAIM01 VL/BS LL TCMUX IOTA

51304465-xxx Internal Cabinet Cable

PMIO LLMUX
CC-PAIM01

Model MU-KFTAxxx Internal FTA Cabinet Cable or Model KFTSxxx External FTA Cabinet Cable [50 meters (164 feet) MAximum Length]

Power Status

CU/CC-TAIM11 VL/BS

PMIO LLMUX
CC-PAIM01

LL TCMUX IOTA

6C on

du ct or

PM
Ca b

FT A

Co

le

He a

nn ec to

Max. Length 1000 ft.


B-Size

51304465-xxx Internal Cable or Model MU-KLXxxx External Cabinet Cable [305 meters(1000 feet) Maximum Length]

B-Size

LLMUX Models
FTA Assemblies must be installed in a cabinet.

LLMUX Models MU/MC-TAMT04 MU/MC-TAMR04 MU/MC-TAMT14

MU/MC-TAMT03 MU/MC-TAMR03 MU/MC-TAMT13 MU/MC-TAMT04 MU/MC-TAMR04 MU/MC-TAMT14

FTA Assemblies must be installed in a cabinet or a NEMA 12 mounting box.

New FTAs Only (no Power Adapter)


C300 Controller Architecture Describe Series C Input-Output Modules and Options

New or Existing FTAs(Requires Power Adapter)


47
EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

LLMUX Solutions, contd.

Honeywell

R300 Solution

Power Adapter Solution (Future)


I/O Link Connections

IOLINK addressing

I/O Link Address

IOLINK addressing

Fuses

C300 Controller Architecture Describe Series C Input-Output Modules and Options

48

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Digital Input 32 Channels Two (2) Physical IOM Types


1. 24VDC Input Common Ground (Non-Isolated) 2. 100VAC/120VAC/125VDC /240VAC (Isolated)

Honeywell

Three (3) Physical IOTA Types


1. 24VDC 2. 120VAC/125VDC 3. 240VAC

Optionally Redundant 100ms Loop Latency

C300 Controller Architecture Describe Series C Input-Output Modules and Options

49

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Digital Input, contd.


I/O Link Connections
Digital Input I/O Module

Honeywell

I/O Link Address


Internal
Used with Honeywells 24v power supply

Pin 1 external return Pin 2 external 24v Pin 3 internal return Pin 4 internal 24v

External

Used with customers provided 24v power supply

Pin 1 external return Pin 2 external 24v Pin 3 internal return Pin 4 internal 24v

C300 Controller Architecture Describe Series C Input-Output Modules and Options

50

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Digital Input New Detail Displays

Honeywell

C300 Controller Architecture Describe Series C Input-Output Modules and Options

51

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Digital Output 32 Channels 24VDC Bussed Output Relay Output


100VAC / 120VAC / 240VAC / 125VDC / 48VDC Utilizes Relay Extension Board

Honeywell

Optionally Redundant 100ms Loop Latency

C300 Controller Architecture Describe Series C Input-Output Modules and Options

52

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Digital Output, contd.


I/O Link Connections I/O Link Address

Honeywell

Digital Output I/O Module

Internal

Used with Honeywells 24v power supply

Pin 1 external return Pin 2 external 24v Pin 3 internal return Pin 4 internal 24v

External

Used with customers provided 24v power supply

Pin 1 external return Pin 2 external 24v Pin 3 internal return Pin 4 internal 24v

C300 Controller Architecture Describe Series C Input-Output Modules and Options

53

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Digital Output Module with Relay Extender


Relay Extension Panel

Honeywell

Digital Output IOTA

C300 Controller Architecture Describe Series C Input-Output Modules and Options

54

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Digital Output New Detail Displays

Honeywell

C300 Controller Architecture Describe Series C Input-Output Modules and Options

55

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series C I/O in Hazardous Areas Honeywell will initially work with MTL to manufacturer an IOTA for use wiring into hazardous locations (C1D1 / Zone 1) The IOTA will be larger than a standard IOTA (approximately 9 wide) 1-, 2- and 4-channel options will be available

Honeywell

C300 Controller Architecture Describe Series C Input-Output Modules and Options

56

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series C I/O in Hazardous Areas, contd.

Honeywell

Non-Redundant IOTA + IOM

Standard IOTA Footprint

6.00

Redundant IOTA + IOM

Extended IOTA Footprint for IS

C300 Controller Architecture Describe Series C Input-Output Modules and Options

57

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series C I/O in Hazardous Areas, contd. Cabinet Layout Wide Channel Supports mixture of IS and general purpose signals within same cabinet Cables are segregated using hazardousarea trunking High vertical packing density

Honeywell

C300 Controller Architecture Describe Series C Input-Output Modules and Options

58

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Process Manager I/O No separate IOLIM needed, connects directly to IOLink PM I/O includes AI, AO, DI, DO, RTD, T/C, DI SOE PM I/O can be redundant FTA for I/O Remote I/O using Fiber Optic

Honeywell

Direct connection to C300 IOLINK

PM I/O

C300 Controller Architecture Describe Series C Input-Output Modules and Options

59

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell DE Transmitters and C300

Honeywell

Support is provided for Honeywell DE-based smart transmitters in C300 via existing PMIO modules:
Smart Transmitter Interface (STI) Smart Transmitter Interface Multivariable (STI-MV)

The Experion Platform provides full integration of all DE information (diagnostics, configuration, etc.) within the standard system displays No additional Asset Management software (e.g., Asset Manager PKS or Field Device Manager) is required to access the DE data

C300 Controller Architecture Describe Series C Input-Output Modules and Options

60

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

FTE Bridge in Series C FTE Bridge, as part of a Series C system allows:


A C300 Controller to use selected Series A chassis I/O (Serial, DeviceNet, Profibus, and Pulse Input modules) without the need for a C200 A C300 to communicate (Exchange Block peer-to-peer) with Rockwell devices like PLC5 and CL5550 using a bridge chassis with a FTEB and downlink CNI

Honeywell

The FTEB continues to operate at 10Mbps after updating firmware to support C300 communication with Series A Chassis I/O C200 with FTEB can be used for Peer to Peer with a C300 Controller
C300 Controller Architecture Describe Series C Input-Output Modules and Options

61

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 3: Series C I/O Which of the following I/Os are available in a Series C type?
A) HLAI, HLAO, Profibus I/O, LL Inputs B) DI, DO, HLAI, HLAO, LL Inputs
C) HLAI, HLAO, LL Inputs, Serial Interface D) Serial Interface, DeviceNet, PulseInput, HLAI

Honeywell

Incorrect. Correct! The TheI/O's I/O's available availablein inaa The Your correct answer: answer is: Series C type are DI, DO, HLAI, You must answer the question before You Incorrect Correct did HLAO You not answer answered -Click Click anywhere anywhere this this question correctly! to tocontinue continue completely and LL Inputs. continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe Series C Input-Output Modules and Options

62

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 4: FTEB in Series C

Honeywell

Which of the following scenarios are available for a FTEB to publish I/O data to a C300?
A) FTEB in redundant chassis connected to C300 B) FTEB in a non-redundant chassis connected to C300 via Control Firewall C) FTEB in a non-redundant chassis connected to C300 via L1 or L2 switch

The Your correct answer: answer is: Incorrect. Correct! The The valid validscenario scenariofor forFTEB FTEBto topublish publishI/O I/O data You to C300 " FTEBthe in a non redundant mustis answer question before I/O chassis You Incorrect Correct did You not answer answered -Click Clickanywhere anywhere this this question correctly! to tocontinue continue completely connected to C300 via Control Firewall." continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe Series C Input-Output Modules and Options

63

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 I/O Compatibility


I/O Family I/O Type HLAI HLAI w/ HART LLAI LLMUX RHMUX STI STI-MV AO8 AO16 AO16 w/ HART Serial Device Serial Pulse DI DI-24V DISOE DO16 DO32 Fieldbus C300 Support C200 Support xPM Support
I/O Family I/O Type HLAI16 HLAI6 HLAI8 w/ HART LLAI-TC6 LLAI-RTD6 AO6V AO6MA AO8 AO8 w/ HART Pulse (6I2O) DI120A16I DI220A16I DI120A8D DI120A16 DI24D16I DI24D16D DI24D32 DO220A16-Relay DO24D16I DO24D16D DO24D32 Serial Fieldbus Profibus DP DeviceNet C300 Support

Honeywell
C200 Support xPM Support

PMIO

I/O Family

I/O Type HLAI w/ HART LLMUX64 AO16 w/ HART DI24D32 DI32 DO24D32 DO32 Fieldbus

C300 Support

C200 Support

xPM Support

CHASSIS SERIES-A

SERIES C

C300 Controller Architecture Describe Series C Input-Output Modules and Options

64

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 I/O Compatibility, contd.


I/O Family I/O Type HLAI DI24D DI120A LLAI-TC LLAI-RTD AO DO24D DO120A DO-Relay C300 Support C200 Support xPM Support

Honeywell

I/O Family

RAIL SERIES A

I/O Type HLAI8 LLAI8 AO8 DI16 DO4 DI16

C300 Support

C200 Support

xPM Support

RAIL SERIES H

C300 Controller Architecture Describe Series C Input-Output Modules and Options

65

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion Describe Series C Input/Output Modules and Options

Honeywell

Completion Certificate

Proceed to the next lesson in your course material


C300 Controller Architecture Describe Series C Input-Output Modules and Options

66

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Describe the IO Topology Rules for the Series C System

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

67

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series C IO Topology Rules I/O topology rules


2 IOLINKS PMIO and Series C I/O on same C300

Honeywell

Connect select series A I/O using FTEB


Connect Allen Bradley PLCs using FTEB

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

68

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules IO Capacity

Honeywell

A C300 can support a maximum of 64 IO Units (IOU) Series C IO and PM IO count as 1 IOU each Series C IO and PMIO are connected to C300 using IO LINKS Series A I/O also consume IOUs, shown later
C300 Controller Architecture Describe the IO Topology Rules for the Series C System

69

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules IO Capacity, contd.

Honeywell

Each IO Link can support a maximum of 40 IOUs A C300 controller supports 2 IOLINKs

An IOLINK can be configured for either Series C IO (at 750 kb link speed) or PMIO (at 375 kb link speed)
An IOLINK cannot support both Series C IO and PMIO on the same link
C300 Controller Architecture Describe the IO Topology Rules for the Series C System

70

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series C IO and PMIO mix


#1: Series C I/O TOTAL 64 IOUs
Link 1 750 kbps 40 PRI Series C IOMs 40 RED Series C IOMs Link 2 750 kbps 24 PRI Series C IOMs 24 RED Series C IOMs

Honeywell
#2: PMIO TOTAL 64 IOUs
Link 1 375 kbps 24 PRI PM - IOPs 24 RED PM - IOPs Link 2 375 kbps 40 PRI PM - IOPs 40 RED PM - IOPs

#3: Series C +PMIO TOTAL 64 IOUs


Link 1 750 kbps 40 PRI Series C IOMs 40 RED Series C IOMs Link 2 375 kbps 24 PRI PM - IOPs 24 RED PM - IOPs

#4: Series C +PMIO TOTAL 64 IOUs


Link 1 375 kbps 40 PRI PM - IOPs 40 RED PM - IOPs Link 2 750 kbps 24 PRI Series C IOMs 24 RED Series C IOMs

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

71

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules IO Capacity

Honeywell

A C300 can support up to 8 FTEBs for interfacing with supported Chassis I/O or AB PLC interface

FTEBs must be connected to the same Control Firewall as the C300


This limits the FTEBs to 6 per redundant C300 controller

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

72

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules IO Capacity, contd.

Honeywell

Each FTEB used to connect Series A IO can support up to 16 IOUs. The IOU count per module is
Serial Interface Profibus Interface 4 2 DeviceNet Interface Pulse Input 2 1

The FTEB used for Series A cannot be in a redundant configuration


C300 Controller Architecture Describe the IO Topology Rules for the Series C System

73

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Controller I/O Link Configurations

Honeywell

#5: Series C + PMIO + Series A TOTAL 64 IOUs

C300 Capacity 3 MIX #3 Link 1 Link 2 750 kbps 375 kbps

FTE

16 Series A IO Units w/FTEB


Pulse Input, Serial, DeviceNet, and ProfiBus IOMs only

24 PRI Series C IOMs 24 RED Series C IOMs


C300 Controller Architecture Describe the IO Topology Rules for the Series C System

24 PRI PM-IOPs
24 RED PM-IOPs
74

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules IO Capacity

Honeywell

Important limitations: An FTEB connected chassis can allow connections to only 1 C300 controller

You cannot have any other C200, IO or CNI downlink modules in the FTEB chassis to connect to other IO chassis
C300 Controller Architecture Describe the IO Topology Rules for the Series C System

75

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules IO Capacity, contd.

Honeywell CNI, ENET or DHRIO only

FTEBs can be used to connect AB PLCs for Peer to Peer, using Exchange Blocks. A maximum of 32 exchange blocks, and a maximum of 8 PLCs can be connected

The interface uses Control Net to the AB PLCs and allows only the CNI, ENET or DHRIO
C300 Controller Architecture Describe the IO Topology Rules for the Series C System

76

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules IO Capacity, contd.

Honeywell

A Series C FIM can be used with or without the C300 controller A FIM needs to connect to a C300 controller if a combined control strategy is needed

A FIM counts as 4 IOUs


A C300 controller can support 15 FIMs
C300 Controller Architecture Describe the IO Topology Rules for the Series C System

77

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules IO Capacity, contd.

Honeywell

An Experion Server can support upto 125 FIMs A FIM supports 4 H1 links, with 16 devices per link

Do the math: An Experion server can support 500 links, with a total of 8000 FieldBus devices!

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

78

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell Question 1: IO Topology Rules Which of the following statements is not true for Series C IO Topology Rules?
A) Series C, PM and Series C A IO on the same IO Link

B) Series C and PM IO cannot be on the same IO Link


C) FTEB connected chassis can allow connections to only 1 C300 controller D) Each FTEB used to connect Series A IO can support up to 16 IOUs
Incorrect. Series C, PM and Series A IO on the same Correct! Series C, PM and Series A IO on the same IOLINK IOLINK is not true for a Series C IO Topology. An IOLINK is not true for a Series C IO Topology. An IOLINK cannot cannot support both Series C IO and PMIO on the same support both Series C IO and PMIO on the same link. An Your The correct answer: answer is: link. An FTEB connected to the same Control Firewall as FTEB connected to the same Control Firewall as the C300 You must answer the question before the C300 controller can publish Series A IO data to the You Incorrect Correct did You not answer answered Click Click anywhere anywhere this this question correctly! to to continue continue completely controller can continuing publish Series A IO data to the C300. C300. Click anywhere to continue. Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

79

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell Question 2: Topology Rules For a project it is required to use Fieldbus only control strategy for 1500 FF devices. How many C300 controllers are required?
A) 2 C300 Controllers + 24 FIM Modules B) 1 C300 Controller + 48 FIM Modules
C) No C300 Controllers are required, only 24 Series C FIM Modules

Yes! No. The The correct correct statement statement is is "No "No C300 C300 controllers controllers are are The Your correct answer: answer is: required, only 24 Series C FIM Modules". Since the project requires only Fieldbus control strategy the C300 You must answer the question before controller is not required. Each FIM Module has 4 FF links You Incorrect Correct did You not answer answered -Click Clickanywhere anywhere this this question correctly! to tocontinue continue completely and each link continuing supports 16 FF devices. Hence 1 FIM module can support a maximum of 64 (16*4) FF devices. Hence only 24 (1500/64) Series C FIM Modules are required. Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

80

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell Question 3: Topology Rules FTEBs can be used in the Series C topology under specific scenarios. Which of the these is true?
A) FTEB connected to AB PLC via Downlink CNI B) FTEBs must be connected to the same Control Firewall as the C300 C) An FTEB connected chassis can allow connections to only 1 C300 controller D) All of the above

The correct Your answer: answer is: Correct! Incorrect. All All of of the the above above statements statements are are correct correct for You must answer the question before for FTEBs FTEBs used used in in the the Series Series C C topology. topology. You Incorrect Correct did You not answer answered -Click Click anywhere anywhere this this question correctly! to tocontinue continue completely continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

81

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary
There are 2 IOLINKS per C300 System
Mix and match of Series C I/O and PMIO is an option Specific Series A I/O and AB PLC can be connected using FTEB Same IOLINK cannot support both Series C and PM IO

Honeywell

A C300 can support a maximum of 64 IO Units (IOU)

Each IO Link can support a maximum of 40 IOUs A C300 can support up to 8 FTEBs for interfacing with supported Chassis I/O or AB PLC interface FTEBs must be connected to the same Control Firewall as the C300 Each FTEB used to connect Series A IO can support up to 16 IOUs The FTEB used for Series A cannot be in a redundant configuration

A Series C FIM can be used with or without the C300 controller A C300 controller can support 15 FIMs An Experion Server can support up to 125 FIMs
C300 Controller Architecture Describe the IO Topology Rules for the Series C System

82

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Describe the I/O Topology Rules for the Series C System

Completion Certificate

Proceed to the next lesson in your course material


C300 Controller Architecture Describe the IO Topology Rules for the Series C System

83

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell

This page intentionally left blank

C300 Controller Architecture Describe the IO Topology Rules for the Series C System

84

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Describe Fiber Optic Extender and its Connection Rules

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

85

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics Overview Series C I/O Link Fiber Optic Extender Module Topology Series C IOM, PM IOP Topology Type Daisy Chain, Star, Tree Distance Limitation Cabinet Layout Specifications

Honeywell

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

86

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Overview

Honeywell

C300 controller can now be connected remotely to Series C I/O or PMIO through the use of an I/O Link Fiber Optic Extender (FOE) module Same FOE cannot be used for Series C and PMIO connections, concurrently Each FOE can connect to two remote sites
Two fiber optic ports sets, FO1 and FO2 Ports have both receive (Rx) and transmit (Tx)

Mounting options
IOTA Din Rail Stand Alone

Two types of IOLINK cables


PMIO Series C

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

87

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series C I/O Link Fiber Optic Extender Module


24V DC

Honeywell
IOLINK cable COMMON

Carrier Mounting Screws

Fiber Optic Extender IOTA

Fuse LED Indicators FOE to IOTA Mounting Screw

FOE to IOTA power connection

Fiber Optic ports

I/O Link Connector

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

88

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topology Series C IOM


IO Link Cable

Honeywell

C300 1.5 Km Max.


Remote Site B

IOM 1.5 Km Max. Fiber Optic Cable


Remote Site A

4 KM Max. (requires IOLE every 1.5 km)

Configuration possible are


Star Daisy chain Tree (Star + Daisy chain)

IOM
C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

Series C IOM
89

Series C IOM

Series C IOM

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topology PM IOP
IO Link Cable
1.5 Km Max.

Honeywell

C300 1.5 Km Max. Fiber Optic Cable 1.5 Km Max.

10 Km Max. (requires IOLE every 1.5 Km)

PM IOP With IOLink Extender IOP


Remote Site A

PM IOP With IOLink Extender IOP

IOLink Extender pair MC-IOLX02


90

Remote Site B

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topology Type Daisy Chain

Honeywell

IOM C300 IO Link Cable

Main Location

Remote Site 1

Remote Site 2

FOE

Fiber Optic Cable

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

91

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topology Type Star

Honeywell

IO Link Cable FOE


Main Location

Fiber Optic Cable

Remote Site 1

Remote Site 3

IOM
Remote Site 2 Remote Site 4

It is possible to have multiple fiber-optic extenders in any location, provided distance limitations are observed and no more than 40 IOMs on a single I/O Link
92
EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

Topology Type Tree

Honeywell

C300

IO Link Cable

FOE

Fiber1
Fiber2 Fiber3

Fiber1 Fiber2 IOM Fiber3


Main Location Remote Site 1 Remote Site 2

IOM

Fiber Optic Cable

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

93

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Distance Limitations
Main Location

Honeywell
d1
Remote Site#1

C300 IOM IOM

d2
Remote Site#2 Remote Site#3 Remote Site#4

d4 d3
IOM IOM

IOM

Maximum distance of any single fiber-optic segment must be less than 1.5 km
d1, d2, d3, d4 <= 1.5 km

Maximum distance of any single leg must be less than 4.0 km. In above figure,
0.25 + d1 + 0.25 <= 4.0 km 0.25 + d2 + 0.25 + d3 + 0.25 + d4 + 0.25 <= 4.0 km

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

94

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Distance Limitations (Example)


Main Location

Honeywell
Remote Site#1

d1 = 1.5 km

C300 IOM IOM

d2 = 1.0 km
Remote Site#2 Remote Site#3

d3 = 1.0 km
IOM

d4 = 1 km

Remote Site#4

IOM

IOM

The connections shown in figure above will work because,


d1(1.5), d2(1.0), d3 (1.0), d4(1.0) <= 1.5 km 0.25 + d1(1.5) + 0.25 = 2.0 <= 4.0 km 0.25 + d2(1.0) + 0.25 + d3(1.0) + 0.25 + d4(1.0) + 0.25 = 4.0 <= 4.0 km
C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

95

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Distance Limitations (Example), contd.


Main Location

Honeywell
Remote Site#1

d1 = 2.0 km

C300 IOM IOM

d2 = 1.5 km
Remote Site#2 Remote Site#3

d3 = 1.5 km
IOM

d4 = 1 km

Remote Site#4

IOM

IOM

The connections shown in above figure will not work because,


d1(2.0) which is not <= 1.5 km 0.25 + d2(1.5) + 0.25 + d3(1.5) + 0.25 + d4(1.0) + 0.25 = 5.0 km which is not <= 4.0 km
C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

96

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Cabinet Layout

Honeywell

FOE can use either Violet or Grey IOL

C300 Controller

Control Firewall FOE A I/O Link Extender for Link A

Digital Input Card

FOE B I/O Link Extender for Link B

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

97

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Specifications Power Supply Options


20 to 30V @ 200mA

Honeywell

Distance
Segment distance: 1.5 Km Total maximum IOLink length Series C IO: 4 Km PM IO: 10 Km Propagation delay: each IOLE fiber optic converter subtracts a certain value from the total IOLink length Series C IO: 0.25 Km per FOE PM IO: 0.5 Km per FOE

Fiber-Optic
Fiber type: Multimode Fiber core diameter: 62.5 mm Fiber cladding diameter: 125 mm Fiber connectors: ST type Power budget: 8 db min, 15 db typical

C300 Controller Architecture Describe Fiber Optic Extender and its Connection Rules

98

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Describe the Control Firewall Connections in the Series C System

C300 Controller Architecture Describe the Control Firewall Connections in the Series C System

99

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Overview Topology rules pertaining to the Control Firewall Overview of FTE limits

Honeywell

C300 Controller Architecture Describe the Control Firewall Connections in the Series C System

100

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules Control Firewall

Honeywell

C300, Series C FIMs must be connected to the Control Firewall. The C300 and any FTEBs assigned to it must be on the same control firewall

No other device, such as FTEB for C200, Ethernet PLCs, Stations or Servers, can connect to the Control Firewall
C300 Controller Architecture Describe the Control Firewall Connections in the Series C System

101

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C300 Topology Rules Control Firewall, contd.

Honeywell

The Control Firewall is connected by uplink to a L1 or L2 switch. Connections can be Fiber Optic or STP Cable. Fiber Optic: 2 KM multi mode or 15 KM single mode. STP cable: CAT 5 up to 100 M Control Firewalls cannot be cascaded
102

C300 Controller Architecture Describe the Control Firewall Connections in the Series C System

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

How Many FTE Nodes Do You Have?

Honeywell

An FTE Community can have no more than 330 FTE Nodes calculated as follows:
Max. 125 Redundant FIMs per Server = 125 x 2 = 250 Max. 16 Redundant C300s per Server = 16 x 2 = 32 Max. 40 Stations = 40 Max. 1 Redundant Server = 2 Max. 5 ACE = 5

GRAND TOTAL: 329

If any FTEBs are present in the Community, the limit is 200 FTE Nodes Embedded FTE used in C300 and Series C FIM is at the MAC level, and therefore yellow and green have same IP address Servers and Workstations require one IP address per NIC port

C300 Controller Architecture Describe the Control Firewall Connections in the Series C System

103

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: Control Firewall

Honeywell

Which of the following is not a valid connection to a Control Firewall?


A) Series C FIM
B) C300 Controller C) FTEB for specific Series A IO D) FTEB for C200

Incorrect. Correct! FTEB FTEBfor forC200 C200controller controlleris isnot notaavalid validdevice deviceto to connect to Control Firewall. No device such as FTEB for C200, Ethernet PLCs, Stations or Servers, can connect to Yourcorrect The answer: answer is: the Control Firewall Correct Incorrect You You must did - Click not -answer Click answer anywhere anywhere thethis question to before You answered this correctly! question to continue continue completely continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Describe the Control Firewall Connections in the Series C System

104

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary

Honeywell

C300 and Series C FIM must be connected to the Control Firewall No other device, such as FTEB for C200, Ethernet PLCs, Stations or
Servers, can connect to the Control Firewall

C300 and FTEB (for specific Series A IO and AB devices) associated to it must be on the same Control Firewall The Control Firewall is connected by uplink to a L1 or L2 switch Control Firewalls cannot be cascaded

C300 Controller Architecture Describe the Control Firewall Connections in the Series C System

105

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell

Describe the Control Firewall connections in the Series C System

Completion Certificate

Proceed to the next lesson in your course material


C300 Controller Architecture Describe the Control Firewall Connections in the Series C System

106

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Define a Typical Series C Configuration

C300 Controller Architecture Define a Typical Series C Configuration

107

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Putting the Pieces Together

Honeywell

C300 Controller Architecture Define a Typical Series C Configuration

108

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: Connectivity

Honeywell

A C300 Controller has PM IO connected to both IOLINKs. Some of the data is obtained from a remote monitoring system 5 km from the C300 cabinet. Which of the following is the correct option?
A) Extend the PM IO using IO Link Extender B) Series C FIM C) Series C IO

Correct! Incorrect. To get To data get from data the from remote the remote vibrating The Your correct answer: answer is: vibrating monitoring monitoring system extend system the extend PM IO the using PM IO You must answer the question before You Incorrect Correct did You notusing answer answered -Click Click anywhere anywhere this this question correctly! to to continue continue completely Link IO Link Extender. Extender. continuing Click anywhere to continue.

Submit

Clear

C300 Controller Architecture Define a Typical Series C Configuration

109

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary C300 controllers, Series C FIM, and FTEB for Series A IO are connected to the Control Firewall

Honeywell

Series C and PM IO are connected to the C300 controller by the two IOLINKs on C300 Controller IOTA
Series C and PM IO cannot be mixed on the same IOLINK

Remote PMIO is implemented using the PM IO Link Extender C300 can be associated to Series A IO directly via FTEB only when Profibus, DeviceNet, Serial Interface and Pulse Input modules are

required

C300 Controller Architecture Define a Typical Series C Configuration

110

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Define a Typical Series C Configuration

Completion Certificate

Proceed to the next lesson in your course material


C300 Controller Architecture Define a Typical Series C Configuration

111

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell

This page intentionally left blank

C300 Controller Architecture Define a Typical Series C Configuration

112

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013