Beruflich Dokumente
Kultur Dokumente
For example,here we can consider three safety valves are Super heater safety valve,Drum safety valve one and Drum safety valve two. Step 1: Super heater safety valve set pressure= (steam operating pressure at MSSV exit point/0.93). It means 7% of steam pressure at MSSV exit point. Step 2: Drum safety valve one set pressure is always more or equal to 7% of steam drum operating pressure.But same time,drum safety valve one set pressure is always more than super heater safety valve set pressure at MSSV line exit plus total system drop.Total system drop is equal to the sum of all pressure drop from steam drum to MSSV exit. Step 3:Drum safety valve two set pressure is equal to the Drum safety one set pressure plus 1 kg/sq.cm