Sie sind auf Seite 1von 16

City Place

Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours DRIVE TEMP Main Fuses: VFD I-Limit Setting: 154.56 VFD Freq Limits: / Data N/A X 75 Deg.F 109 F X X X X 0 TO 60 Hz

S-13
ABB H502100400P2000000 CRH03H MOTOR TEMP

11/28/11
14TH FLOOR 153386 45666 H DRIVE TEMP

VFD Fuses: BUSSMAN 200A 95184 VFD O.L. Config: 700s/110% Bypass O.L. Config: VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 469 418 63 78 Vac Vac Amps Amps C-A: C-A: C: C: 467 418 62 76 2 Vac Vac Amps Amps Vac

/ Data *

X X X 53.91 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 468 418 63 77 Vac Vac Amps Amps 627 B-C: B-C: B: B: Vdc

Display 413 Vac Display 76.2 Amps 620 0 659 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 663 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 0 3 7 120 Vac mVac mVac Vac mVac mVac

*ONE FAN IS N/G, NEEDS REPLACEMENT, RECOMMEND CHANGING BOTH

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours GRND FAULT

S-13A
ABB H502100400P2000000 D-TECH CRH03H MOTOR TEMP

12/13/13
14TH FLOOR 153388 JOB M2870 57607 H GRND FAULT

VFD Fuses: BUSSMAN 200A 95184 Main Fuses: VFD O.L. Config: 700s/100% VFD I-Limit Setting: 136.64 Bypass O.L. Config: OL FURNAS 48JA37AA4 OLHEATERS:E102 VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 65 Deg.F 90 F X X X X VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 473 470 65 74 Vac Vac Amps Amps C-A: C-A: C: C: 473 470 62 74 3 Vac Vac Amps Amps Vac

/ Data X n/a n/a X X X X X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 473 470 65 74 Vac Vac Amps Amps 625 B-C: B-C: B: B: Vdc

Display 458 Vac Display 85.1 Amps 625 0 671 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 670 10 24 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 6 5 123 Vac mVac mVac Vac mVac mVac

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours

CHWP-5
ABB ACH550-UH-031A-4 313D HEX DC UNDERVOLT

11/28/11
14TH FLOOR 2100602058 9.06 KH

VFD Fuses: VFD O.L. Config: 1050s/110% Bypass O.L. Config: VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 21 C 29 C X X X X

Main Fuses: VFD I-Limit Setting: 41.4 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 464 163 3 8 Vac Vac Amps Amps C-A: C-A: C: C: 464 163 3 8 3 Vac Vac Amps Amps Vac

/ Data X

X X X 25.5 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 464 163 3 8 Vac Vac Amps Amps 639 B-C: B-C: B: B: Vdc

Display 167 Vac Display 84 Amps 641 0 656 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 652 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 4 19 Vac mVac mVac Vac mVac mVac

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: URD 22 100 PROTISTOR VFD O.L. Config: 2400S/115% Bypass O.L. Config: VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 21 C 26 C X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours

CHWP-4
ABB ACH501-050-4-00P2 CRH03C

11/28/11
14TH FLOOR S103599 39173 H OVERCURRENT

Main Fuses: AJT100 VFD I-Limit Setting: 71.30 VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 464 102 5.6 21 Vac Vac Amps Amps C-A: C-A: C: C: 464 102 6 21 2 Vac Vac Amps Amps Vac

/ Data X 1 UF .98 UF X X X 30 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 464 102 5.6 21 Vac Vac Amps Amps 635 B-C: B-C: B: B: Vdc

Display 99 Vac Display 20.5 Amps 642 0 657 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 652 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 Vac mVac mVac Vac mVac mVac

"CONTROL POWER ON" LED IS N/G

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: NA VFD O.L. Config: 700s/100% Bypass O.L. Config: NA VFD U.V. Config: NA System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 18 C 23 C X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 12.10 VFD Freq Limits: 0 TO 60 Hz

CV-2-P7B
ABB ACH501007400P2 NA CRH03H 0

12/13/13
14TH FLOOR 153885 NA 31192 H 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 471 272 *1 *1 Vac Vac Amps Amps C-A: C-A: C: C: 471 271 *1 *1 2.1 Vac Vac Amps Amps Vac

/ Data X NA NA X X x X X 35.97 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 471 271 *1 *1 Vac Vac Amps Amps 635 B-C: B-C: B: B: Vdc

Display 276 Vac Display 4.8 Amps 638 0 667 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 8 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 Vac mVac mVac Vac mVac mVac

*1=CABLES TO SHORT TO RECORD AMPERAGE READINGS

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: NA VFD O.L. Config: 700s/100% Bypass O.L. Config: NA VFD U.V. Config: NA System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 17 C 29 C X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 12.10 VFD Freq Limits: 0 TO 60 Hz

CV-2-P7A
ABB ACH501007400P2 NA CRH03H 0

11/28/13
14TH FLOOR 153968 NA 33010 H 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 478 266 *1 *1 Vac Vac Amps Amps C-A: C-A: C: C: 479 265 *1 *1 2 Vac Vac Amps Amps Vac

/ Data X NA NA NA X X X X 35.5 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 474 265 *1 *1 Vac Vac Amps Amps 621 B-C: B-C: B: B: Vdc

Display 280 Vac Display 4.8 Amps 657 0 640 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 634 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 6 14 Vac mVac mVac Vac mVac mVac

*1=CABLES TO SHORT TO RECORD AMPERAGE READINGS

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours OVERCURRENT

EF-13
ABB ACH50100400P2 CRH03H OVERCURRENT

11/28/11
14TH FLOOR 153387 46260 H OVERCURRENT

VFD Fuses: BUSSMAN 200A 95184 VFD O.L. Config: 700s/100% Bypass O.L. Config: VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 21 C 37 C X X X X

Main Fuses: VFD I-Limit Setting: 136.64 VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 465 360 36 55 Vac Vac Amps Amps C-A: C-A: C: C: 465 360 38 54 2 Vac Vac Amps Amps Vac

/ Data X

X X X 45 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 466 360 37 56 Vac Vac Amps Amps 621 B-C: B-C: B: B: Vdc

Display 346 Vac Display 54 Amps 617 0 656 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 659 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 122 <1 Vac mVac mVac Vac mVac mVac

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: 700s/100% Bypass O.L. Config: VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 21 C 25 C X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 12.10 VFD Freq Limits: 0 TO 60 Hz

CV-3-PB
ABB ACH501007400P2 CRH03H 0

11/28/11
39TH FLOOR 153970 29789 H 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 474 309 *1 *1 Vac Vac Amps Amps C-A: C-A: C: C: 474 309 *1 *1 2 Vac Vac Amps Amps Vac

/ Data X

X X X 21 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 474 309 *1 *1 Vac Vac Amps Amps 654 B-C: B-C: B: B: Vdc

Display 169 Vac Display 3.2 Amps 657 0 656 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 659 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 Vac mVac mVac Vac mVac mVac

*1=CABLES TO SHORT TO RECORD AMPERAGE READINGS

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 6

CV-4-P9A
ABB ACH401601132 D-TECH 1.1.3.7 1

12/13/13
P1-STEAM METER RM. 2034101082 Job M2870 31.17 kh 6

VFD Fuses: AMP-TRAP AJT30 Main Fuses: Breaker VFD O.L. Config: 1050s/100% VFD I-Limit Setting: 25.3 Bypass O.L. Config: Furnas OL 48DC37Aa4 heaters are hard to read, but look like size E88 VFD U.V. Config: Enable(Time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 88 F 114 X X X X VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 487 201 4.5 9.7 Vac Vac Amps Amps C-A: C-A: C: C: 487 201 5 9.7 2.5 3 Vac Vac Amps Amps Vac

/ Data X n/a n/a X X no X X 40 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 487 201 4.4 8.6 Vac Vac Amps Amps 656 B-C: B-C: B: B: Vdc

Display 205 Vac Display 9.2 Amps 654 0 681 n/a n/a n/a n/a n/a Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 683 9.96 24 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: .5 .5 .4 133 Vac mVac mVac Vac mVac mVac

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 12.10 VFD Freq Limits: / Data N/A X 21 C 25 C X X X X 0 TO 60 Hz

CV-3-PA
ABB ACH501007400P2 CRH03H UNDERVOLTAGE

11/28/11
39TH FLOOR 153969 25901 H 0

VFD Fuses: VFD O.L. Config: 700s/100% Bypass O.L. Config: VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 472 169 *1 *1 Vac Vac Amps Amps C-A: C-A: C: C: 473 167 *1 *1 1.1 Vac Vac Amps Amps Vac

/ Data X

X X X 22.11 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 472 167 *1 *1 Vac Vac Amps Amps 651 B-C: B-C: B: B: Vdc

Display 170 Vac Display 3.4 Amps 657 0 668 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 658 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 13 <1 Vac mVac mVac Vac mVac mVac

*1=CABLES TO SHORT TO RECORD AMPERAGE READINGS

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 15.44 VFD Freq Limits: / Data N/A X 29 C 30 C X X X X 0 TO 60 Hz

CV-1-P6A
ABB ACH501010400P2 NA CRH03H 0

12/13/13
P1-STEAM METER RM. 153704 NA 31331 H 0

VFD Fuses: BUSSMAN 80A22F VFD O.L. Config: 700s/100% Bypass O.L. Config: NA VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 489 228 7 9 Vac Vac Amps Amps C-A: C-A: C: C: 489 228 7 9 1.6 Vac Vac Amps Amps Vac

/ Data X NA NA X X X 30 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 489 228 7 9 Vac Vac Amps Amps 659 B-C: B-C: B: B: Vdc

Display 230 Vac Display 4.4 Amps 665 0 684 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 678 10 26 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 14 <1 Vac mVac mVac Vac mVac mVac

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 23.22 VFD Freq Limits: / Data N/A X 29 C 33 C X X X X 0 TO 60 Hz

CV-4-P9B
ABB ACH501015400P2 NA CRH03H 0

12/13/13
P1-STEAM METER RM. 176282 NA 47421 H 0

VFD Fuses: BUSSMAN FWC 30A10F VFD O.L. Config: 700s/100% Bypass O.L. Config: VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 488 226 1.3 6 Vac Vac Amps Amps C-A: C-A: C: C: 488 225 1.2 6.3 1.6 Vac Vac Amps Amps Vac

/ Data X NA NA X X X X X 30 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 488 226 1.3 6 Vac Vac Amps Amps 668 B-C: B-C: B: B: Vdc

Display 230 Vac Display 4.9 Amps 675 0 689 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 678 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 6 19 Vac mVac mVac Vac mVac mVac

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 15.44 VFD Freq Limits: / Data n/a X 86 F 84 F X X X X 0 TO 60 Hz

CV-1-P6B
ABB ACH501010400P2 n/a CRH03H 0

12/13/13
P1-STEAM METER RM. 154395 n/a 28242 h 0

VFD Fuses: BUSSMAN 80A22F VFD O.L. Config: 700s/100% Bypass O.L. Config: VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 489 189 .4 4.9 Vac Vac Amps Amps C-A: C-A: C: C: 487 189 .4 4.9 .6 Vac Vac Amps Amps Vac

/ Data X n/a n/a X X No X X 25 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 489 189 .3 4.9 Vac Vac Amps Amps 673 B-C: B-C: B: B: Vdc

Display 192 Vac Display 3.0 Amps 680 0 686 n/a n/a n/a n/a n/a Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 680 10.11 26.28 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: .6 .4 .5 n/a n/a n/a Vac mVac mVac Vac mVac mVac

Customer informed us of a broken coupler between the motor and pump for this drive. This problem did not have any effect on

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours DC UNDERVOLT

CHWP-1
ABB ACH550UH072A4 D-Tech 313D HEX DC UNDERVOLT

12/13/13
P1-STEAM METER RM. 2100301199 Job M1660 16.64KH DC UNDERVOLT

VFD Fuses: AJT100 Main Fuses: VFD O.L. Config: 1050s/110% VFD I-Limit Setting: 106.2 Bypass O.L. Config: FURNAS 48HA37AA4 heaters E78 VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 29 C 36.7 C X X X X VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 488 132 Vac Vac C-A: C-A: C: C: 488 132 5 16 1 Vac Vac Amps Amps Vac

/ Data X Na Na X X X X X 22.4 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 488 132 Vac Vac B-C: B-C: B: B: Vdc

Display 136 Vac Display 16.3 Amps 672 0 680 Vdc Hz

5 Amps 16.3 Amps 672

5.4 Amps 16.4 Amps

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 684 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 5 7 Vac mVac mVac Vac mVac mVac

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

CHWP-2
ABB ACH501050400P2 D-Tech CRH03H 0

12/13/13
P1-STEAM METER RM. S103639 Job M1660 31942 H 0

VFD Fuses: AJT100 Main Fuses: VFD O.L. Config: 2400s/115% VFD I-Limit Setting: 71.3 Bypass O.L. Config: FURNAS 48HA37AA4 heaters E78 VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 29 C 34 C X X X X VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 489 70 4.9 23 Vac Vac Amps Amps C-A: C-A: C: C: 489 70 4.9 23 1 Vac Vac Amps Amps Vac

/ Data X 1 UF .98UF X X X X X 24.4 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 489 70 4 23 Vac Vac Amps Amps 670 B-C: B-C: B: B: Vdc

Display 75 Vac Display 20.5 Amps 678 0 680 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 682 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 18 133 Vac mVac mVac Vac mVac mVac

2011:COVER FOR DRIVE IS BADLY CRACKED, RECOMMEND REPLACEMENT, NOT SAFE TO LEAVE LIKE THIS

12/13/13:cover completely broken apart, no cover on VFD. Put a replacement cover aside for this customer next time a 501 is ta Removed 501 control/power boards to clean Mini DC control board fan is NG

City Place
Hartford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours DRIVE TEMP

CHWP-3
ABB ACH501050400P2 D-Tech CRH03D DRIVE TEMP

12/13/13
P1-STEAM METER RM. 114208 Job M1660 28916 H DRIVE TEMP

VFD Fuses: AJT100 Main Fuses: VFD O.L. Config: 2400s/115% VFD I-Limit Setting: 71.3 Bypass O.L. Config: FURNAS 48HA37AA4 heaters E78 VFD U.V. Config: NO System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A X 95 F 82 F (*1) X X X X VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 488 71 2.4 12 Vac Vac Amps Amps C-A: C-A: C: C: 489 71 2.6 12 >1 Vac Vac Amps Amps Vac

/ Data *1 *1 1 uf X X X X X 24.33 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 488 71 2.3 12 Vac Vac Amps Amps 677 B-C: B-C: B: B: Vdc

Display 75 Vac Display 11.8 Amps 679 0 679 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 670 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 22 133 Vac mVac mVac Vac mVac mVac

*1: 12/13/13:Capacitor replaced, DCTiny Fan (TUDC24B4) replaced. Connection onto board for DC tiny fan had signs of moistu 12/13/13: Removed 501 control/power boards to clean