KW
= 30KW
RATED VOLTAGE
415 V
I fl.
31 Amp
I st.
107.1 Amp
DERATING FACTOR
D.F.
0.552
LENGTH(Max.)
0.080 KM
.
= 70Amp
Vst
Vrun
NUMBER OF RUNS
=2
1)
Vst
Rac
VOLTAGE DROP
AT STARTING
WHERE
Since the cable lengths are not very big, the reactance of the cables will be negligible and
hence not considered in the above mentioned calculations
So Vst.
Voltage Drop During Starting in
Percentage
Vst.
=21.37 V
Vst.%
=Vst. X 100
415
=5.15%
2)
VOLTAGE DROP
AT Running
Vrun
WHERE
Rac
Since the cable lengths are not very big, the reactance of the cables will be negligible and
hence not considered in the above mentioned calculations
So
t.
Voltage Drop During Running in
Percentage
3)Conclusion
Vrun
=6.11 V
Vrun.%
=Vrun. X 100
415
=1.47%
The Voltage drop at starting 5.15% & running is
1.47%,for a motor of 45 Kw which is at a
distance of 80 meters
Hence Cable Size Selected as 2Rx3Cx25Sq mm
Is in order.