Beruflich Dokumente
Kultur Dokumente
ISBN # 1-892765-35-7 The Eighth Edition of Manual J (MJ8 ACCA/ ANSI) is the American National Standard for residential heating and cooling load calculations.
Version Two of Manual J reorganizes the presentation of material provided in previous versions, and provides guidance on using an abridged version of Manual J (MJ8AE), which supports hand calculations for a subset of Manual J applications.
Submit all comments to standards-sec@acca.org by 11:59pm (EST) 24 October 2011 on the ACCA RESPONSE FORM available from www.acca.org/ansi.
Section 2
n
In general, take full credit for the rated (or tested) performance of construction materials, insulation materials and construction features. a) As specified for new construction. b) As installed (verify the installation conforms to methods and materials protocols). c) As tested (see quality control programs for new construction, investigate existing construction) Take full credit for the tightness of the envelope construction. a) As specified by builder or code. b) As installed (verify the installation conforms to methods and materials protocols). c) As tested (see quality control programs for new construction, investigate existing construction). Follow Manual J procedures for infiltration and ventilation a) Use the Table 8A procedure to evaluate the fresh air requirement. b) Use Table 5A to estimate infiltration rates for heating and cooling (ignore intermittent exhaust fans). c) Decide on the installation of an engineered ventilation system (mandatory if the code fresh air requirement is larger than an honest estimate of the Manual J infiltration rate). d) Intermittent bathroom and kitchen exhaust fans are not ventilation devices or ventilation systems. Take full credit for duct system sealing and duct insulation when such efforts are confidently anticipated or certifiable. a) Use the default (0.12/0.24) scenario for (untested) ducts that are reasonably sealed. b) Take full credit for sealing efforts that are certifiably tighter than the default scenario for sealed ducts. c) If the duct sealing work is deficient seal the ducts and take credit for sealed ducts (use unsealed options to show why the sealing work is required). Match location as close as possible when selecting a duct load table (use Table 7 unabridged if the MJ8AE tables do not provide a satisfactory match). a) For attic ducts, match roof material, roof color, use of radiant barrier or foam, and attic ventilation. b) For closed crawlspace locations, match crawlspace tightness, crawlspace wall insulation and crawlspace ceiling insulation. Match duct system geometry (radial and spider systems tend to have less surface area than extended plenum and trunk and branch systems). Match return system geometry (use advanced Manual J procedures when the system has more than one or two large returns or when the returns are not located close to the air handler).
Be sure to use the duct wall insulation correction if the R-value of the insulation is not R-6. Be sure to use the surface adjustment factor for the exposed duct surface area when the surface area of the actual duct system is significantly different than the defaults listed in Table 7. Make sure the occupancy and internal loads are compatible with the MJ8AE defaults (use Manual J, Worksheet F if MJ8AE does not provide a satisfactory match). Add blower heat to the sensible load if equipment performance data is not adjusted for blower heat (if equipment manufacturer or blower power is unknown, assume 1,707 Btuh for indoor blower motor heat). Educate consumers: Sit down with your customers or clients and educate them on these issues.
Manual J Donts (Mandatory Requirements) n Do not use Manual J (any version) for: a) Any type of commercial application (even if located in a residential structure). b) Large multi-family buildings or residential high rise structures. c) A room or space containing an indoor swimming pool or hot tub. d) Earth-berm or earth covered dwellings. e) Solar homes that have passive features. n Do not use MJ8 AE to estimate heating and cooling loads for applications that are not compatible with the "Abridged Edition Check List" (see the page that precedes Section 1). n Do not design for record breaking (or news making) weather conditions. n Do not add a safety factor to the Table 1A design conditions. n Do not design for abnormally low or high indoor temperatures or humidity conditions (unless there is a certified medical reason for doing so). n Do not assume that there will be no internal shade on ordinary windows and glass doors (bare glass is an acceptable assumption for glass specifically installed for day-lighting). n Do not fail to take credit for overhangs. n Do not assume that the load for the worst case site orientation can be used for other orientations. (Rotating the dwelling on a site can change the cooling load by a half ton or more. Room airflow requirements change as the orientation changes. If the same design is used for any orientation, some rooms may have too much supply air and other rooms will not have enough supply air for temperature control and comfort.) n Do not reduce known ceiling, wall or floor R-values just to be safe.
b) An exposed wall has brick veneer, R-2 insulation board sheathing, wood studs, R-19 cavity insulation and interior finish. There is 240 SqFt of gross area with 70 SqFt of window and door area. The panel heating load is 803 Btuh.
Table 4A construction number = 12E-2b-w Table 4A U-value = 0.063 HTM = U x HTD = 0.063 x 75 = 4.725 Net area = Gross area Opening area = 240 - 70 = 170 SqFt Heating load = HTM x Net area = 4.725 x 170 = 803 Btuh
Note: Metal framing significantly affects wall performance. Use advanced Manual J procedures for this type of construction.
c) An exposed block wall has brick veneer, no insulated cores, R-6 board insulation and interior finish. There is 240 SqFt of gross area with 70 SqFt of window and door area. The panel heating load is 1,454 Btuh.
Table 4A construction number = 13A-6oc-b Table 4A U-value = 0.114 HTM = U x HTD = 0.114 x 75 = 8.55 Net area = Gross area Opening area = 240 - 70 = 170 SqFt Heating load = HTM x Net area = 8.55 x 170 = 1,454 Btuh
Note: Core insulation significant affects wall performance. Use advanced Manual J procedures for this type of construction.
d) An exposed block wall has wood siding, empty cores, R-2 board insulation, wood 2x4 studs, R-11 blanket insulation and interior finish. There is 240 SqFt of gross area with 70 SqFt of window and door area. The panel heating load is 1,020 Btuh.
Table 4A construction number = 13B-2oc-w Table 4A U-value = 0.080 HTM = U x HTD = 0.080 x 75 = 6.0 Net area = Gross area Opening area = 240 - 70 = 170 SqFt Heating load = HTM x Net area = 6.0 x 170 = 1,020 Btuh
e) A basement wall has empty cores, R-2 board insulation extending from the sill plate to the floor and no interior finish. The wall is 8 ft high and has 320 Ft of gross wall area. The basement floor is 6 feet below grade (2 feet of the wall is above grade). There is 240 SqFt of below-grade area and 80 SqFt of gross above-grade area with 16 SqFt of window area. The heating load for the below grade wall area is 1,854 Btuh, and 1,291 Btuh for the above grade strip.
Table 4A construction number = 15A-2sfoc-6 Table 4A below grade U-value = 0.103 Below grade HTM = U x HTD = 0.103 x 75 = 7.725 Below grade area = Gross area = 240 SqFt Below grade heating load = HTM x Gross area = 7.725 x 240 = 1,854 Btuh Table 4A above grade U-value = 0.269 Above grade HTM = U x HTD = 0.269 x 75 = 20.175 Net above grade area = Gross area Opening area = 80 16 = 64 SqFt Above grade heating load = HTM x Net area = 20.175 x 64 = 1,291 Btuh
f) A below grade block wall has no insulation in the cores, R-4 board insulation extending to 3 feet below the sill plate, wood 2x4 studs, R-11 blanket insulation and interior finish. The wall is completely below grade with a 240 SqFt area. The basement floor is 8 feet below grade. The panel heating load is 828 Btuh.
Table 4A construction number = 15A11-4ocw-8 Table 4A U-value = 0.046 HTM = U x HTD = 0.046 x 75 = 3.45 Net area = Gross area = 240 SqFt Heating load = HTM x Gross area = 3.45 x 240 = 828 Btuh
23
AGV for each level = Floor area X Average ceiling height The above grade portion of a conditioned basement is one level. AGV = Total of the volumes for all levels Default Occupancy = Number of bedrooms + 1 For Smith: AGV = 8 x 56 x 32 + 188 x 32 = 20,352 CuFt
Cfm @ 0.35 = 0.35 x AGV / 60 Cfm for people = 20 x Number of people Cfm for Burner = 0.50 x Input Btuh / 1,000 Table 8 OA Cfm = Largest of the three Cfm values. Cfmoa determined by code requirement or designer decision to use the Table 8 OA Cfm value.
Step 2, Option 1 Table 5 Defaults Operating Mode Heating Cooling Floor Area (SqFt) 2,848 2,848 Type of Const. Average Average Space ACH 0.32 0.16 AGV (CuFt) 20,355 20,355 Space ICFM 109 85 Fireplace ICFM 0 Total ICFM
(Note 1) (Note 2)
109 54
T8 vent-CFM = T8 OA CFM - Cooling ICFM If cooling ICFMis greater than T8 OA CFM, the T8 vent CFM is zero.
1) For default estimates use Table 5A or 5B to find ICFM values for the conditioned space and fireplace. 2) The component leakage area method or the blower door method may be used to estimate ICFM values.
Total ICFM = Space ICFM + FP ICFM Space ICFM = ACH x AGV / 60 Use the AGV from the Table 8 procedure.
Step 2, Option 2 Component Leakage Area Method Operating Mode HTD and CTD 76 oF 15 oF Wind Velocity (MPH) 15 85.6 7.5
Detail from Worksheet E1
ICFM
Table 8 OA CFM
Heating Cooling
119
28
Default heating season velocity = 15 MPH Default cooling season velocity = 7.5 MPH
Step 2, Option 3 Blower Door Method Operating Mode HTD and CTD 76 oF 15 oF Wind Velocity (MPH) 15 62 7.5
Provided by field test
ICFM
Table 8 OA-CFM
Table 8 Vent-CFM
Heating Cooling
119
53
Default heating season velocity = 15 MPH Default cooling season velocity = 7.5 MPH
Step 3 Infiltration Loads on Central Equipment Type of Load Heat Load Sens Load Lat Load 70 70 0 66 66 1,651 Wrksht. H Value for Vent CFM 70 Exhaust CFM 70 CFMimb ICFM (Option 3) 139 Net Infilt. CFM NCFM 139 H&C Loads (Btuh) 11,237 1,054
CFMimb = CFM exhaust - CFMvent NCFM = (ICFM1.5 CFMimb1.5 ) 0.67 NCFM = 0 if (ICFM1.5 - CFMimb1.5) < 0 The sign in the NCFM equation is determined by the sign of the Heat Load = 1.1 x ACF x NCFM x HTD CFMimb Sensible Load = 1.1 x ACF x NCFM x CTD value. Latent Load = 0.68 x ACF x NCFM x Grains
The room infiltration load equals the load on the central equipment multiplied by the gross wall area ratio (WAR). WAR = Gross room wall area / Gross wall area for all rooms served by the central equipment
95
Section 13
B Tops of B windows are 1.0 foot below a 1.5 foot overhang. A Entire House 56 x 32 x 8 East B South C Top of glass door is 0.75 feet below a 1.5 foot overhang. West D Skylight S2 D windows equipped with external sun screen
Bedroom 1 14 x 17
North Bedroom 3 14 x 16
Bedroom 2 14 x 15
Kitchen and Utility 21 x 14 Hall and Two Closets 14 x 9 Entry 7 x 14 Bath 1 9x7 Bath 2 5x7 Skylight S1 A
Figure 13-3
Figure 13-4 Lines 7 through 11 show HTM values and load areas for opaque surfaces. The HTM values are copied from Worksheet D. The load area for a door is equal to the 21 SqFt default value. The load area for walls and ceilings is equal to the net surface area. The associated heating and sensible cooling loads are determined by multiplying the HTM values by the load areas. Line 12 shows the infiltration loads, as copied from Worksheet E. In this case the wall area ratio equals 1.0 because the calculation is for the entire house. Line 15 shows the effective load factors (EHLF and ESGF) for the duct system, as copied from Worksheet G. The heating and sensible load values are equal to the
104
Section 13
1 Name of Room Walker Residence 2 Running Feet of Exposed Wall 3 Ceiling Height (Ft) and Gross Wall Area (SqFt) 4 Room Dimensions (Ft) and Floor Plan Area (SqFt) 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt) Type of Panel HTM Const.. Exposure Faces Number Htg. Clg. West 7.92 15.01 Windows a 1G Unit A and Glass b 1G Unit A East 7.92 15.01 Doors c 1G Unit C oh South 8.28 7.14 d 1G Unit B oh South 7.56 7.09 e 1G Unit B North 7.56 7.09 f 1G Unit A North 7.92 7.36 g 1G Unit D West 8.10 10.98 h I j North 16.74 84.33 Skylights a 9C Kitchen b 9C Living South 12.78 78.33 c a 11N 6.30 10.50 Wood and Metal b 11N 6.30 10.50 Doors c a 14C-5 All 1.24 1.01 Above Grade b Walls and Partitions c d e f g a Below Grade b Walls c 0.47 0.49 Ceilings a 16F-39tw b c Floors a Rad 22D-5rl 12.34 b c d 0.137 Infiltration Heating Load (Btuh) Effct. Sensible Load (Btuh) ACH 0.00 Latent Load (Btuh) a Occupants at 230 and 200 Btuh Internal b Scenario Number Option 3 c Default Adjustments d Custom Appliances tv & computer e Plants Sum lines 5 through 12 Subtotals 0.066 Duct EHLF & ESGF Loads ELG 0 Ventilation Loads Vent Cfm 50 E Cfm Winter Humidification Load Gal / Day Piping Load Blower Heat AED Excursion & Latent Moisture Migration Load Sum Lines 13 Through 19 Total Load Entire House 176 1,408 1,792 1,792 Btuh Heating 69 139 480 212 106 347 255 S-Clg. 131 263 414 199 99 322 348 L-Clg.
Area or Length
6a
6b
1,752
820
865
10
176
2,172
<- Radiant added to block load, not added to subtotal load, see 13-4
11
471 WAR 1.00 4 920 3,400 1,221 5,152 12,976 851 7,040 800 655 -2,067 800 WAR
12
13
14 15 16 17 18 19 20 21
990
Section 13 product of the load factor and the corresponding Line 14 sub-total. Line 15 shows the effective latent gain (ELG). Lines 16 through 19 show the ventilation load and the blower motor load. These values were copied from worksheets H and I.. Line 20 shows the AED adjustment and the moisture migration load (no AED adjustment for this example). Line 21 shows the total heating load, total sensible load and total latent load (equipment sizing loads). AED Adjustment The AED adjustment curve is derived (by computer) from Worksheet B and C input. Figure 13-5 shows the AED curve for the Walker Residence. In this case there is no excursion, so the system designer elected to use a single zone constant volume system.
Fenestration Gain vs Hour of Day
If the peak-hour gain exceeds the average gain by more than 30 percent, the conditioned space is a candidate for the peak load procedure. See MJ8, Section 1-13.
Operation
Window
c d S 1.5 10.1 15.2 0.75 14.40 7.25 0 8.00 58.0 0 7.14 7.93 414 0 414 58.0 7.14
Direction X SLM Z=BxC Y S=Z-Y H U=H-S W SxW UxW Wrksht B Wrksht B JxL KxM N+O GxI P/Q
S 1.5 10.1 15.2 1.00 14.15 3.5 0 4.00 14.0 0 7.09 7.78 99 0 99 14.0 7.09
R) Assembly HTMOH
Btuh
Figure 13-6
Hour of Day
Figure 13-5
Worksheet B Worksheet B (next page) provides heating and cooling HTM values for windows and glass doors. All calculations are made for NFRC labeled fenestration. A sun screen adjustment is applied to the West-facing windows. Lines a through f show the directional calculations for all the windows and the sliding glass door. The resulting HTM values for heating are listed in the Heat HTM column. The resulting HTM values for cooling are listed in the Cool HTMD column. The values in this column have no insect screen adjustment. The values in the AHTMD column are adjusted for an insect screen, when this adjustment is applicable. The values in this column have not been adjusted for shading by a sun screen or overhang. The AHTMD values on lines a, b, and c are not subject to this adjustment, so they are copied to Form J1. The AHTMD values on lines d, e and f are not copied to Form J1 because the South-facing windows and glass door are shaded by an 1.5 foot overhang and the West-facing windows are shaded by sun screens. These
13-3 Worksheets
The worksheets for Form J1 appear on the following pages. Comment and guidance pertaining to the information that appears on Form J1 and the associated work sheets is provided here. Worksheet A Table 1A provides altitude, latitude values and outdoor design conditions for Worksheet A (next page). The system designer provides values for the indoor design conditions. This is a humid, semi-tropical climate (the winter design temperature is above 50 oF). The cooling season design is based on a 55% RH value for indoor humidity, so there is a 57 grain moisture differential between the outdoor air and the indoor air.
106
Section 13 Ushaft, Apanel, Acurb and Ashaft are used. Note that the panel area (Apanel) for domed skylights equals the flat panel area multiplied by a 1.25 adjustment for the curvature of the dome. Step 3 is used to generate the effective HTM values for the skylights. The resulting Heat HTM and Cool HTM values are transferred to Form J1. Worksheet D Worksheet D (and the associated notes show the procedure used to produce HTM values for opaque panels. The resulting Heat HTM and Cool HTM values are transferred to Form J1. Worksheet E Worksheet E (next page) is used to estimate infiltration loads and to set the ventilation rate. Step 1 shows that 84 CFM of outdoor air will satisfy the most demanding test, which is the 0.35 ACH test. Step 2 uses the default air change method to estimate infiltration loads, but in this case the Table 5A ACH values are replaced by air change values that are compatible with the track record of the builder (0.25 for heating and 0.15 for cooling). The Step 2 calculations return a 60 ICFM value for heating, a 36 ICFM value for cooling and a 48 CFM value for the Table 8 ventilation requirement. Step 3 shows that the system designer has decided to route 50 CFM of outdoor air through the dehumidifying ventilator (50 CFM is required to satisfy the code requirement) and that this amount of unbalanced ventilation (there is no exhaust air) reduces the winter infiltration rate to 24 CFM and completely eliminates summer infiltration. This results in a 471 Btuh heating load, and no cooling load. Worksheet F Worksheet F (page 111) shows that the occupants produce a 920 Btuh sensible load and a 800 Btuh latent load and that default scenario two adds 3,400 Btuh of sensible load. The home has three televisions and two computers, so the sensible load is increased by 683 Btuh for one television plus another 538 Btuh for one computer. (One television is included in the default scenario and the practitioner has decided that one television and one computer will not be used during late afternoons.)
Worksheet D HTM Values and Net Area for Opaque Panels Walker Residence
Construction Number and Exposure Direction, or Ceiling Slope HTD = 18 F Length Average (Ft) Height / Width (Ft) CTD = 15 F Gross Area (SqFt) Opening Area (SqFt) Daily Range = Low Net Area (SqFt) Slab Edge (Ft) U-Value or Slab F-Value 4A HTD or PTDH
Heating HTM = U x HTD or U x PTDH Cooling HTM = U x CLTD or U x PTDC
Group Number 4A
CLTD 4B or PTDC
Heating HTM
Cooling HTM
Wood and Metal Doors (Construction 11) a 11N En. door b 11N Kit door c Above Grade Walls (Construction 12, 13 and 14) a 14C-5 b Ceilings (Construction 16, 17 and 18) For sloped ceiling, note slope angle in degrees; then Gross Area = (L x W) / Cosine of slope angle a 16F-38tw b 16DR-38aw c 16C-38aw 56 56 56 32 32 32 1,792 1,792 1,792 40 40 40 1,752 1,752 1,752 0.026 0.026 0.026 18 18 18 19 0.47 0.47 0.47 0.49 0.88 1.14 all 176 8 1,408 243.5 1,165 0.069 18 K 14.6 1.24 1.01 3 3 7 7 21 21
Use gross area if less than 50 %; use French door if
0.35 0.35
18 18
30.0 30.0
6.30 6.30
10.50 10.50
34
44
Radiant Floors (construction Numbers 20, 21 and 22) Note: Use F-value and running feet of exposed edge for slab floors a 22D-5rl b 56 32 1,792 176 0.287 43.0 12.34
109
Table 8 OA Cfm 84 84
AGV for each level = Floor area X Average ceiling height The above grade portion of a conditioned basement is one level. AGV = Total of the volumes for all levels Default Occupancy = Number of bedrooms + 1 For Walker: AGV = 8 x 56 x 32 = 14,336 CuFt
Cfm @ 0.35 = 0.35 x AGV / 60 Cfm for people = 20 x Number of people Cfm for Burner = 0.50 x Input Btuh / 1,000 Table 8 OA Cfm = Largest of the three Cfm values. Cfmoa determined by code requirement or designer decision to use the Table 8 OA Cfm value.
Step 2, Option 1 Table 5 Defaults Operating Mode Heating Cooling Floor Area (SqFt) 1,792 1,792 Type of Const. Track Rec Track Rec Space ACH 0.25 0.15 AGV (CuFt) 14,336 14,336 Space ICFM 60 36 Fireplace ICFM Total ICFM
(Note 1) (Note 2)
Table 8 OA CFM 84
60 36
T8 vent-CFM = T8 OA CFM - Cooling ICFM If cooling ICFMis greater than T8 OA CFM, the T8 vent CFM is zero.
1) For default estimates use Table 5A or 5B to find ICFM values for the conditioned space and fireplace. 2) The component leakage area method or the blower door method may be used to estimate ICFM values.
Total ICFM = Space ICFM + FP ICFM Space ICFM = ACH x AGV / 60 Use the AGV from the Table 8 procedure.
Step 2, Option 2 Component Leakage Area Method Operating Mode HTD and CTD Wind Velocity (MPH) Table 5C ELA4 (SqIn) Table 5D Cs Shielding Class Cw ICFM Table 8 OA CFM Table 8 Vent CFM
Heating Cooling
Default heating season velocity = 15 MPH Default cooling season velocity = 7.5 MPH Detail from Worksheet E1 ICFM = ELA4 x ( Cs x TD + Cw x V2 ) 0.50 T8 vent CFM = T8 OA CFM - Cooling ICFM If cooling ICFMis greater than T8 OA CFM, the T8 vent CFM is zero.
Step 2, Option 3 Blower Door Method Operating Mode HTD and CTD Wind Velocity (MPH) Blower Door ELA4 Table 5D Cs Shielding Class Cw ICFM Table 8 OA-CFM Table 8 Vent-CFM
Heating Cooling
Default heating season velocity = 15 MPH Default cooling season velocity = 7.5 MPH Provided by field test ICFM = ELA4 x ( Cs x TD + Cw x V2 ) 0.50 T8 vent-CFM = T8 OA CFM - Cooling ICFM If cooling ICFMis greater than T8 OA CFM, the T8 vent CFM is zero.
Step 3 Infiltration Loads on Central Equipment Type of Load Heat Load Sens Load Lat Load 50 0 -50 36 0 0 Wrksht. H Value for Vent CFM 50 Exhaust CFM 0 CFMimb ICFM (Option 1) 60 Net Infilt. CFM NCFM 24 H&C Loads (Btuh) 471 0
CFMimb = CFM exhaust - CFMvent NCFM = (ICFM1.5 CFMimb1.5 ) 0.67 NCFM = 0 if (ICFM1.5 - CFMimb1.5) < 0 The sign in the NCFM equation is determined by the sign of the Heat Load = 1.1 x ACF x NCFM x HTD CFMimb Sensible Load = 1.1 x ACF x NCFM x CTD value. Latent Load = 0.68 x ACF x NCFM x Grains
-50
The room infiltration load equals the load on the central equipment multiplied by the gross wall area ratio (WAR). WAR = Gross room wall area / Gross wall area for all rooms served by the central equipment
110
Section 14 Worksheet D HTM Values and Net Area for Opaque Panels Cobb Residence
Construction Number and Exposure Direction, or Ceiling Slope HTD = 23 F Length Average (Ft) Height / Width (Ft) CTD = 18 F Gross Area (SqFt) Opening Area (SqFt) Daily Range = Medium Net Area (SqFt) Slab Edge (Ft) U-Value or Slab F-Value 4A HTD or PTDH
Heating HTM = U x HTD or U x PTDH Cooling HTM = U x CLTD or U x PTDC
Group Number 4A
CLTD 4B or PTDC
Heating HTM
Cooling HTM
Wood and Metal Doors (Construction 11) a b Above Grade Walls (Construction 12, 13 and 14) a b Partition Walls (Construction 12, 13 and 14) Use estimated partition temperature difference for heating (PTDH) and cooling (PTDC) g 13Ca-0oc-m 40 8 320 21.0 299.0 0.123 23.0 I 10.9 2.83 1.34 13Ca-0oc-m 69 8 552 152.9 399.1 0.123 23.0 I 17.0 2.83 2.09 11N 3 7 21
Use gross area if less than 50 %; use
0.35
23.0
31.0
8.05
10.9
Step 1 Table 8 Outdoor Air Requirement Operating Mode Heat Cool Above Grade Volume AGV (CuFt) 14,472 14,472 Number of Bed Rooms 3 3 Number of People 4 4
Air source heat pump
Table 8 OA Cfm
84 84
AGV for each level = Floor area X Average ceiling height The above grade portion of a conditioned basement is one level. AGV = Total of the volumes for all levels
Cfm @ 0.35 = 0.35 x AGV / 60 Cfm for people = 20 x Number of people Cfm for Burner = 0.50 x Input Btuh / 1,000
Step 2, Option 1 Table 5 Defaults Operating Mode Heating Cooling Floor Area (SqFt) 1,809 1,809 Type of Const. Space ACH AGV (CuFt) Space ICFM Fireplace ICFM Total ICFM
(Note 1) (Note 2)
Table 8 OA CFM 84
Avg-Tight Avg-Tight
0.290 0.160
14,472 14,472
70 39
70 39
T8 vent-CFM = T8 OA CFM - Cooling ICFM .
1) For default estimates use Table 5A or 5B to find ICFM values for the conditioned space and fireplace.
Step 3 Infiltration Loads on Central Equipment Type of Load Heat Load Sens Load 39 Lat Load 39 1,391 Wrksht. H Value for Vent CFM Exhaust CFM CFMimb ICFM (Option 1) Net Infilt. CFM NCFM 70 H&C Loads (Btuh) 1,770 764
CFMimb = CFM exhaust - CFMvent NCFM = (ICFM1.5 CFMimb1.5 ) 0.67 NCFM = 0 if (ICFM1.5 - CFMimb1.5) < 0 The sign in the NCFM equation is determined by the sign of the Heating Load = 1.1 x ACF x NCFM x HTD CFMimb Sensible Load = 1.1 x ACF x NCFM x CTD value. Latent Load = 0.68 x ACF x NCFM x Grains
70
118
Step 1 Table 8 Outdoor Air Requirement Operating Mode Heat Cool Above Grade Volume AGV (CuFt) 11,592 11,592 Number of Bed Rooms 3 3 Number of People 4 4
Furnace input defaults: Direct Vent = 0 Btuh Atmospheric = 100,000 Btuh
Table 8 OA Cfm
80 80
AGV for each level = Floor area X Average ceiling height The above grade portion of a conditioned basement is one level. AGV = Total of the volumes for all levels
Cfm @ 0.35 = 0.35 x AGV / 60 Cfm for people = 20 x Number of people Cfm for Burner = 0.50 x Input Btuh / 1,000
Step 2, Option 1 Table 5 Defaults Operating Mode Heating Cooling Floor Area (SqFt) 1,288 1,288 Type of Const. Space ACH AGV (CuFt) Space ICFM Fireplace ICFM Total ICFM
(Note 1) (Note 2)
Table 8 OA CFM 80
Tight Tight
0.140 0.070
11,592 11,592
27 14
27 14
T8 vent-CFM = T8 OA CFM - Cooling ICFM If cooling ICFMis greater than T8 OA CFM, the T8 vent CFM is zero.
1) For default estimates use Table 5A or 5B to find ICFM values for the conditioned space and fireplace. 2) The component leakage area method or the blower door method.
Total ICFM = Space ICFM + FP ICFM Space ICFM = ACH x AGV / 60 Use the AGV from the Table 8 procedure.
Step 3 Infiltration Loads on Central Equipment Type of Load Heat Load Sens Load 50 Lat Load 50 0 14 14 241 Wrksht. H Value for Vent CFM 50 Exhaust CFM CFMimb ICFM (Option 1 ) Net Infilt. CFM NCFM 27 H&C Loads (Btuh) 1,760 317
CFMimb = CFM exhaust - CFMvent NCFM = (ICFM1.5 CFMimb1.5 ) 0.67 NCFM = 0 if (ICFM1.5 - CFMimb1.5) < 0 The sign in the NCFM equation is determined by the sign of the Heating Load = 1.1 x ACF x NCFM x HTD CFMimb Sensible Load = 1.1 x ACF x NCFM x CTD value. Latent Load = 0.68 x ACF x NCFM x Grains
50
27
Occupants Default = Number bedrooms + 1 4 230 200 1.0 1.0 920 800 800 Total occupancy loads for Form J1 (Btuh) =
Default Scenario Scenario option 1 1 2,400 1.0 1.0 2,400 2,400 Default scenario load for Form J1 (Btuh) =
Individual Appliance Options Color TV Computer and monitor 1 1 683 1,536 1.00 0.35 1.00 1.00 683 538 1,221
Total individual appliance loads for Form J1 (Btuh) = e Plants Small 20 10 Total plant load for Form J1 (Btuh) =
200 200
128
Section 18 Design Conditions Section 19 Fenestration Load Procedures Section 20 Opaque Panel Load Procedures Section 21 Infiltration Load Procedures Section 22 Internal Load Procedures Section 23 Duct Load Procedures Section 24 Ventilation Load Procedures Section 25 Blower Heat Procedure Section 26 Hot-Water Piping Load Procedure Section 27 Winter Humidification Load Procedure Section 28 Moisture Migration Load Procedure
141
Section 21
(This information is generated automatically and presented on a video screen or paper print out.) For example, software-generated values for C and n for the Figure 21-4 blower door test are 288.3 and 0.755.
Multipoint Blower Door Test
12000 10000 8000 6000
Measured Cfm
The fenestration leakage area values in Table 5C do not apply to rated fenestration. The 4-Pascal leakage area of rated fenestration is equivalent to Table 5C information.
Test Points
This equation converts a Q15 rating to a 4-Pascal leakage area value (ELA4).
ELA4 (SqIn) = 2.929 x (Q15 / (Ptest) n) x 4 0.5 x (d / 2) 0.5 Where: Ptest = 15 Mph stagnation pressure (26.84 Pascals) n = 1.0 for long narrow cracks d = 0.075 Lb/CuFt for standard air So: ELA4 (SqIn) = 0.04225 x Q15
5,850 Cfm
4000 2000 0 0 10 20 30 40 50 60 70 80 90 100 110 Referance Pressure (Pascals)
Figure 21-4
For example, suppose manufacturer's performance data shows the tested leakage rate was 0.25 Cfm per square foot of assembly area. Then for component leakage area calculations, the 4-Pascal leakage area is 0.01056 square inches.
0.04225 x 0.25 = 0.01056 SqIn
Effective Leakage Area The C and n constants are used to calculate the effective leakage area for the structure. This value depends on the density of the air and the reference pressure difference (PD). The following equation is used for standard air. (This equation can be used for elevations that range from sea level to 2,000 feet.)
Sea Level ELA4 (SqIn) = 0.2835 x C x (PD) n
A 4-Pascal reference pressure (that simulates natural conditions) is used to produce an effective leakage area value. For C and n values of 288.3 and 0.755, the sea-level leakage area is 232.8 SqIn.
Sea Level ELA4 = 0.2835 x 288.3 x (4) 0.755 = 232.8 SqIn
The C and n constants in this equation depend on the size, shape and number of the cracks and openings in the thermal envelope (including partition and duct surfaces that leak to an unconditioned space). These constants are relatively insensitive to ambient conditions (outdoor wind and temperature) when test pressures are in the 30 to 60 Pascal range. (Testing at pressures that greatly exceed the 4-Pascal pressure caused by natural effects minimizes the "noise" in the measurement.) Values for the C and n constants are provided by software that is packaged with the blower door apparatus.
The equation used to estimate the effective leakage area for any altitude is provided here. In this case, the altitude ELA4 value depends on the C and n constants, the differential pressure (PD) and the density of the air (d) leaking through the cracks.
ELA4 (SqIn) = 2.929 x C x (PD) n 0.5 x (d / 2) 0.5
For example, for standard sea level conditions, the density of the air is 0.075 Lb/CuFt, so the ELA4 leakage area is about 233 SqIn, which agrees with the sea level version of this equation.
233 SqIn = 2.929 x 288.3 x (4) 0.755- 0.50 x (0.075 / 2) 0.5
178
Section 21 room and for the entire structure when using this equation.
ICFM = Infiltration Cfm for entire conditioned space WAR = Gross wall area room / Gross wall area dwelling Room Infiltration CFM = WAR x ICFM
n
If the flow of outdoor air is greater than the flow of exhaust air, the space will be pressurized and the infiltration is reduced. If the flow of outdoor air is less than the flow of exhaust air, the space will be depressurized and the infiltration is increased.
This guideline is a compromise between accuracy and expediency. It is presented with the understanding that room apportionments may not be sensitive to local differences in the construction detail, exhaust equipment, vent openings and fuel burning equipment. The accuracy of this guideline is compatible with three methods that are used to estimate the ICFM value.
When an unbalanced condition occurs, the combined infiltration rate (CFMcomb) depends on the standard infiltration rate (CFMinf) and the imbalance between the ventilation CFM and the exhaust CFM (CFMimb). The following equations estimate the infiltration rate for a dwelling that has an unbalanced ventilation system:
CFMimb = (Exhaust CFM - Ventilation CFM) ICFM = CFMcomb = (CFMinf 1.5 CFMimb 1.5) 0.67 Where: CFMcomb = 0 when (CFMinf 1.5 - CFMimb 1.5) is negative
For example, suppose a home has an standard infiltration rate of 130 CFM. If 50 CFM of outdoor air is introduced through the return side of the air distribution system with no provision for exhausting this air, the home is pressurized and the infiltration rate is reduced to 111 CFM as demonstrated here:
CFMimb = 0 - 50 = -50 ICFM = CFMcomb = (130 1.5 - 50 1.5) 0.67 = 111.0
Conversely, if exhaust equipment draws 50 CFM of outdoor air through this home, the thermal envelope will be under a negative pressure. In this case, the infiltration rate increases to about 154 CFM, as demonstrated here:
CFMimb = 50 - 0 = 50 ICFM = CFMcomb = (130 1.5 + 50 1.5) 0.67 = 153.7
If the flow rate of the outdoor air equals the flow rate of the exhaust air, the ventilation system has no affect on the space pressure or the infiltration rate.
Infiltration Principles
Infiltration rates depend on flow paths and pressure drivers. Some factors cannot be controlled (the wind), some factors are controlled by the builder (cracks) and some factors are controlled by the HVAC contractor (engineered ventilation, exhausts and vents). Understanding infiltration mechanics and related pressure conditions is essential for system design, for trouble-shooting air quality problems and for assuring occupant comfort, health and safety.
181
Section 21 drivers act in concert, so a wide range of pressure conditions and infiltration rates are possible, depending on which drivers are active. latent infiltration loads. It may even be possible to produce a condition that would cause a combustion appliance to backdraft. It is possible for the operating cost of an attic exhaust fan to greater than the associated reduction in cooling energy cost. Attic exhaust fans are sized by attic ceiling area. Sizes range from 0.50 Cfm per SqFt to 0.75 Cfm per SqFt. (Fan capacity is typically 1,000 Cfm or more. A small 50 cfm or so fan is not classified as an attic exhaust fan.) Vent Openings Exhaust vents may have no damper or a leaky damper. The leakage area for vent openings can vary from 2 to 12 percent of the total leakage area (the mean value was 5 percent). Fireplaces The leakage produced by inoperative fireplaces depends on the source of combustion air. If the combustion air comes from the conditioned space, the leakage depends on the quality of the flue damper and the seal at the glass doors (when installed). The leakage area associated with fireplaces can vary between 0 percent and 30 percent (the mean was equal to 12 percent). Comfort System The leakage attributed to comfort systems can range from 0 percent to 28 percent (the mean was 18 percent). The total amount of leakage area depends on the type of equipment, the location of the equipment and duct runs, and the amount of exposed duct-wall area.
186
Section 23 runs are not sealed (0.35/0.70 scenario), the Worksheet G values for the second floor area (previous example) will be larger and the system load factors and latent gain value will be larger. When risers or drops are located in an exposed wall, the duct load factor or latent load is added to the system load values. This will increase the system load factors and latent gain value for the previous example.
n
Or use values that are compatible with the track record of the installer.
Note: Software solutions are only as good as the input data. If the duct surface area is off by 100 percent the duct load error will be in the neighborhood of 100 percent. If the leakage estimate is way off the mark, the duct load will be incorrect. Also expect extremely large load factors for R-0 scenarios, especially if there is a lot of exposed surface area.
n n n n n
The location of the duct runs. The surface area of the supply system. The surface area of the return system. The duct wall R-value or values. Supply-side and return-side leakage CFM per square foot of duct surface area (based on a 25 Pascal duct leakage test, SMACNA CL value or practitioner estimate). Weather data and altitude correction from Worksheet A. The indoor design conditions. Envelope loads and envelope infiltration rate. Many types of roof-attic construction. The temperature of supply air (heating). The blower CFM (heating and cooling).
For existing duct systems, this information is gathered by inspection and testing. Or, the practitioner provides the information for duct systems that are on the drawing board. For leakage values, the practitioner has to make a decision pertaining to expected tightness of the supply runs and the return runs. Manual J provides the following options:
n
The heat loss factor for the entire duct system is 0.410. The sensible gain factor for the entire duct system is 0.562. The latent cooling load value for the entire duct system is 3,052 Btuh.
Th e right side of Figure 23-2 shows Worksheet G calculations for the return side of the duct system. Note that the supply side surface areas have been set to zero.
n
Use the Table 7 default values for sealed (0.12 and 0.24) or unsealed (0.35 and 0.70). Or use Figure 23-5 or Figures 23-8 and 23-9 to generate leakage rate values. Or use values that are compatible with a code requirement.
The heat loss factor for the return-side of the duct system is 0.167. The sensible gain factor for the return-side of the duct system is 0.229. The latent cooling load value for the return-side of the duct system is 3,052 Btuh.
196
Refer to Section 23.6 for guidance pertaining to case number and look-up floor area. For multiple locations use a separate worksheet for each location. Then the Form J1 loss/gain factors and latent gain for the entire system equal the sum of the worksheet (Step 5) values. See Section 23.7.
Step 1) Enter base-case load factors and latent heat value from Table 7 (eyeball interpolation is acceptable) Existing Construction R-Value 1 2 3 4 Leakage 0.35 / 0.70 Base-case factors from table Heat loss factor = Sensible gain factor = Latent gain (Btuh) = 0.170 0.220 601 R-Value 4 Leakage 0.35 / 0.70 Improved Construction Base-case factors from table Heat loss factor = Sensible gain factor = Latent gain (Btuh) = 0.170 0.220 601
Step 2) R-Value Correction (WIF) 4 5 6 7 For heat loss = For sensible gain = Adjusted heat loss factor = Adjusted sensible gain factor = 1.370 1.330 0.233 0.293 For heat loss = For sensible gain = < Line 1 factor x line 4 adjustment > < Line 2 factor x line 5 adjustment > 1.370 1.330 0.233 0.293
Step 3) Leakage Rate Correction (LCF) 8 9 10 11 12 13 For heat loss = For sensible gain = For latent gain = Adjusted heat loss factor = Adjusted sensible gain factor = Adjusted latent gain (Btuh) = 1.75 1.91 4.02 0.048 0.559 2,416 For heat loss = For sensible gain = For latent gain = < Line 6 factor x line 8 adjustment t > < Line 7 factor x line 9 adjustment > < Line 3 value x line 10 adjustment > 1.75 1.91 4.02 0.048 0.559 2,416
Step 4) Surface Area Adjustment 14 15 16 17 18 19 20 21 22 Ks = Installed supply area (SqFt) = Default supply area (SqFt) = Rs = Installed area / default area = Installed return area (SqFt) = Default return area (SqFt) = Rr = Installed area / default area = 0.676 Kr = SAA (heating and sensible cooling) = LGA (latent cooling) = 275 312 0.881 120 95 1.263 0.324 1.005 1.263 Ks = DSF for Sect 23-18 Shortcut Installed supply area (SqFt) = Default supply area (SqFt) = Rs = Installed area / default area = Installed return area (SqFt) = Default return area (SqFt) = Rr = Installed area / default area = 0.676 Kr = < Ks (L20) x Rs (L16) + Kr (L20) x Rr (L19) > < Latent LGA = Rr (L19) > 0 0 ~ 120 95 1.263 0.324 0.409 1.263
Step 5) Heat Loss and heat gain factors and latent gain (Btuh) 23 24 25 Effective heat loss factor (EHLF) = Effective sensible gain factor (ESGF) = Effective latent gain Btuh (ELG) = 0.410 0.562 3,052 < Line 11 Factor x Line 21 SAA value > < Line 12 Factor x Line 21 SAA value > < Line 13 gain x Line 22 LGA adjustment > 0.167 0.229 3,052
Figure 23-2
197
Section 23 Return Side Loads The J1 Form converts duct load factors to duct loads. The return side loads for this example are as follows:
n
Where: ACF is an altitude correction factor (see Table 10A) Rcfm = Return air Cfm = Blower Cfm
The heating load for the space served by the duct system converts the return side heat loss factor to a heating load. For example, if the space heating load is 52,000 Btuh (per line 14 on the J1 form), the heating load for the return-side of the duct system is 0.167 x 52,000 = 8,684 Btuh. The sensible cooling load for the space served by the duct system converts the return side sensible gain factor to a sensible cooling load. For example, if the sensible space load is 22,000 Btuh (per line 14 on the J1 form), the sensible cooling load for the return-side of the duct system is 0.229 x 22,000 = 5,038 Btuh. The return side latent load is provided by Worksheet G.
Note: Return air Cfm may be equal to the blower Cfm, or may be somewhat larger or smaller. For the purpose of this calculation, Rcfm defaults to blower Cfm
An indoor humidity ratio (grains of moisture per pound of air value) is provided by altitude sensitive psychometrics (based on the indoor dry-bulb and relative humidity values). Then the latent heat equation (below), converts a latent return duct load (latent Btuh) to a grains of moisture gain (DGR). Then the exiting grains value equals the indoor grains value plus the latent moisture gain
Indoor Grains = Psychometric value DGR = Latent Load Btuh / 1.1 x ACF x Rcfm Exiting Grains = Indoor Grains + DGR
Dry-Bulb and Wet-Bulb at the Exit of the Return Duct The sensible heat equation (below) converts a sensible return duct load (sensible Btuh) to a dry-bulb gain, or dry-bulb loss (DT). Then the dry-bulb temperature (DB) of the air that exits the return duct equals the indoor dry-bulb temperature plus the return duct gain.
Indoor DB temperature = Given DT (F) = Sensible Btuh / (1.1 x ACF x Rcfm ) Exiting DB (F) = Indoor DB DT
Altitude sensitive psychometrics converts an exiting dry-bulb temperature and grains value to a exiting wet-bulb temperature, and converts an indoor dry-bulb temperature and relative humidity value to an entering wet-bulb temperature. The wet-bulb rise (DWB) equals the difference between the two wet-bulb values.
Exiting WB (F) = Psychometric value Indoor WB (F) = Given psychometric state point DWB (F)= Exiting WB - Indoor WB
198
Section 23
and uninsulated crawlspaces can be comparable to or greater than the loads for attic locations. (The crawlspace system has more exposed duct wall area than the attic system because the crawlspace runouts extend to the perimeter of the floor plan and attic runouts only ran to the center of a room.) This figure also indicates that radiant barriers (or white shingles or tile roofs) reduce the cooling load for attic duct systems. Duct heat transfer to an unconditioned space can be significantly reduced if the surface area of the system is minimized. In this regard, research performed at the National Renewable Energy Laboratory (NREL) indicates that when the thermal envelope is efficient, an acceptable level of comfort can be provided by an attic duct system that features a central air handler and short supply runs that feed supply air diffusers located near the interior walls of the rooms. Duct loads are eliminated when duct runs are in a conditioned space, and significantly reduced when in an encapsulated attic.
Comparison of Duct Load Factors Radial Duct System In Vented Attic Under Dark Shingles
Range of Duct Load Factors Scenario Ordinary Vented Attic Mostly Sealed Not Sealed Vented Attic With Radiant Barrier Mostly Sealed Not Sealed Open Crawl Space Mostly Sealed Not Sealed Closed Crawl Space, No Insulation Mostly Sealed Not Sealed Sensible Cooling 0.11 > 0.27 0.20 > 0.58 Latent Btuh 136 > 1,044 483 > 3,930 Heating SAT = 110 F 0.06 > 0.20 0.11 > 0.41 Grille Location Supply Return
Center room
1,000 cfm per grille, short ducts 1,000 cfm per grille, short ducts 1,000 cfm per grille, short ducts 1,000 cfm per grille, short ducts
Center room
Perimeter
Perimeter
Figure 23-3
198
Section 27 humidity level that produces condensation on a visible surface. The following equation is used to evaluate the temperature distribution across a structural panel. This equation shows that the temperature at a concealed surface (Tc) depends on the R-value for the layers of material between the surface of interest and the outdoors (Rc), the total R-value across the sandwich (Rt), the outdoor design temperature (To), and the indoor temperature (Ti).
Tc - Ro + (Ti - To) x (Tc / Rt)
Dew point 37% RH
43 oF
70 oF
For example, the following guidance compares the condensation potential at the inside surface of a cinder block wall that has insulation on the indoor side of the block with the condensation potential of a block wall with the same amount of insulation installed on the outdoor side of the block. These calculations are based on data provided by Figure 27-2, which shows the thermal resistance of the path between the concealed surface and the outdoor air is R-2 for indoor insulation and R-10 for outdoor insulation. Figure 27-2 also shows that the total thermal resistance for both walls is R-12 and the indoor and outdoor temperatures are 70 oF and -5 oF.
-5 F
Figure 27-1
R-12
R-12
R-2
Concealed Surface
R-2
70 F
-5 F
70F
Insulation on Inside Surface This equation provides the temperature at indoor surface of the block (under the insulation) if the insulation is on the indoor side of the wall.
Tc = -5 + (70 - (-5)) x (2 / 12) = 7.5 oF
Overall resistance of both walls is R-13 with Interior finish and air films
For a 7.5 oF dew point, a low-temperature psychometric chart indicates that indoor air with 8 Grains of moisture will produce condensation on the concealed surface of the block (an absolute humidity of 8 Gr/Lb is associated with a 7.5 oF dew point). A psychometric chart for normal temperatures shows that the relative humidity of the indoor air must be 8 percent or less to prevent condensation at the indoor surface of the block wall (8% RH is compatible with 70 oF dry-bulb and 8 Grains of moisture). These calculations show that concealed condensation is almost certain if the insulation is installed on the inside surface of the block wall. Insulation on Outside Surface This equation provides the value for the temperature at indoor surface of the cinder block if the insulation is installed on the outdoor surface of the wall.
Tc = -5 + ((70 - (-5)) x 10) / 12 = 57.5 oF
Figure 27-2
70 Grains of moisture will produce condensation on the concealed surface of the block. This chart also shows that 62% RH is compatible with 57 oF dry-bulb and 70 Grains of moisture. Therefore, condensation will not occur until the indoor humidity exceeds 62% RH. These calculations show that concealed condensation is prevented (or will be unusual) if the insulation is installed on the outdoor side of the block wall.
For a 57 oF dew point, the psychometric chart for normal temperatures indicates that indoor air with
220
Section 27 following equation shows that airway surface temperature (Ts) depends on duct air temperature (Ti) and ambient temperature (To), the overall R-value (Rt) of the duct wall (duct material, insulation and air film resistence), and the resistance of the inside air film (Ri).
Ts = Ti - (Ti - To) x (Ri / Rt) Where: Ri equals the air film coefficient for airway air: Ri is about 0.25 for typical air velocities Ri is about 0.68 for no air velocity (blower off)
If the ambient temperature is 0F and the duct air temperature is 105F, the temperature for the duct airway surface is about 76.8F, so supply duct condensation will not occur. A similar calculation shows that return duct condensation will not occur.
Dew-point for supply air (105F, 12% RH) = 42.3 F Ts = 105 - (105 - 0) x (0.25 / 0.93) = 76.8F Dew-point for return air (70F, 30% RH) = 37.3 F Ts = 70 - (70 - 0) x (0.25 / 0.93) = 51.2F
For example, sea level dwelling has winter humidification added to supply air, and the dew-point of space air is 37.3F for 70F dry-bulb and 30% RH. If the blower is off, space air may siphon through an attic duct system. Uninsulated metal duct is used to demonstrate the calculation procedure. If the blower is off, the total R-value of a sealed metal duct that has no insulation is about 1.36 (metal resistance is negligible, Ri is about 0.68, and Ro is about 0.68). If the ambient air temperature (To) is 0F and the duct air temperature(Ti) is 70F, the temperature for the duct airway surface is about 35F, so condensation is possible.
Dew-point for duct air = 37.3 F Ts = 70 - (70 - 0) x (0.68 / 1.36) = 35.0F
In general, duct runs installed outside of the conditioned space should be insulated (R4 is common, R6 or R8 is good practice, and ma be a code requirement). For winter humidification, the amount of duct wall insulation must assure that the duct airway surfaces will be warmer than the dew-point of ducted air. In general, duct runs installed outside of the conditioned space should be comprehensively sealed (this is good practice, and may be a code requirement). For winter humidification, exposed duct runs must be as tight as possible (much better than the 0.12/0.24 Cfm per SqFt of duct surface area default for sealed duct per Table 7).
n
When the blower operates, 1,400 CFM of 105F air moves through the supply side of the duct system. The Manual J humidification load was determined to be 4,760 Btuh for the winter design condition, so the humidifier must add 4.5 pounds of water per continuous hour of operation. But the furnace only operates for 42 minutes per hour because it is oversized, so the humidifier must add moisture at a rate of 6.5 pounds (Lb) of water per hour when the furnace operates. This means that return air enters the return duct at 70F and 32.5 Grains (Gr) and leaves the supply duct at 105F and 39.7 Grains, so the dew-point (DP) of the supply air is about 42.3F.
ACF for sea level = 1.0 Return air at 70 F and 30% RH = 32.5 Grains Latent heat added to air = 6.5 x 1,054 = 6,851 Btuh Grains rise = 6,851 / (1.0 x 0.68 x 1,400) = 7.2 Supply air grains = 32.5 + 7.2 = 39.7 Supply air at 105 F and 39.7 Grains = 42.3 F DP
Reactively humid air leaking out of a supply duct may condense (and possibly freeze) on a nearby surface. Cold air leaking into a return duct can cause condensation (and possible freezing) at the leakage point.
If the blower runs, the total R-value of a sealed metal duct that has no insulation is about 0.93 (metal resistance is negligible, Ri is about 0.25, and Ro is about 0.68).
221
Section 27 system installed in the attic may have problems with duct wall condensation or air handler cabinet condensation during cold weather. In extreme cases water may drip from the ceiling supply outlets or returns. This moisture is generated when humid, buoyant room air migrates to the attic duct system (through a supply or return), loses sensible heat and moisture (the water vapor in the air condenses on cold surfaces), loses buoyancy and falls back into the room (through a supply or return), which draws more room air into the duct system. This continuous, gravity-driven circulation process is called thermosiphoning (see Section 27-3). Moisture Content at Sea Level
Outdoor Dry Bulb F -10 or lower -9 to -1 0 5 10 15 20 25 30 35 40 45 Outdoor Grains Indoor Humidity % RH 10 15 20 25 30 35 40 45 50 55 Indoor Grains @ 70 F 10.8 16.2 21.6 27.1 32.5 38.0 43.5 49.0 54.5 60.0
2.6 3.4 4.4 5.7 7.3 9.4 12.0 15.2 19.2 23.8 29.0 35.2
Provide a comprehensive vapor retarding membrane for structural surfaces. Duct runs and equipment cabinets in an unconditioned space must be tightly sealed. Section 28-6 guidance pertains to the moisture migration load for winter humidification. Section 27-7 provides guidance for calculating humidification loads caused by duct leakage.
The following equations show that the default humidification load depends on the total flow of outdoor air (infiltration CFM plus the ventilation CFM), the absolute humidity difference between the indoor air (at the indoor design condition) and the outdoor air (at the winter design temperature and 80 percent RH), and the altitude correction factor (ACF) from Table 10A.
Outdoor Air CFM = ICFM + VCFM Pounds of Water Per Hour = 0.000645 x Outdoor CFM x (Indoor Grains - Outdoor Grains) x ACF
Figure 27-4 For example, sea level calculations show that 4.67 gallons of water per day are required to humidify 100 CFM of outdoor air when the outdoor design temperature is 10 oF and the indoor design condition is 70 oF dry bulb and 30 percent RH. For convenience, Figure 27-4 summarizes the result of a similar set calculations for a range of outdoor temperatures and indoor humidities.
Outdoor Grains = 7.3 (10 oF, 80% RH) Indoor Grains = 32.5 (70 oF, 30% RH) Pounds per Hour = 0.000645 x 100 x (32.5 - 7.3) x 1.0 = 1.625
Figure 27-3 provides moisture content values for a range of outdoor air temperatures and moisture content values for a variety of indoor humidity values. This information is used when the elevation is 2,500 feet or less. For higher elevations, moisture content values are read from Table 12, a psychometric chart for the altitude of concern, or they can be obtained by using altitude sensitive psychometric software.
The following equation converts pounds of water per hour to gallons of water per day:
Gallons per Day = 2.874 x Pounds Water per Hour
222
Section 27 Therefore, the 1.625 Lb/Hr water requirement is equivalent to 4.67 gallons per day.
Gallons per day = 2.874 x 1.625 = 4.67
those used for the Manual J duct load calculation per Worksheet G (or use different values for what-if investigations). This procedure is for moisture added to supply air, so the grains of moisture in the supply duct is greater than the grains of moisture in the return duct. The supply-side moisture loss due to duct leakage is relative to dry outdoor air. The return-side moisture load due to duct leakage depends on the moisture in the ambient air in contact with the return duct.
n
For example, an evaporative device that processes 1.625 pounds of water per hour produces a 1,713 Btuh load on the central heating equipment.
1,713 Btuh = 1,054 x 1.625
Assume that ambient air moisture equals outdoor air moisture if the unconditioned space is not sealed from outdoor air. Duct moisture leakage to an unconditioned space that is tightly sealed from outdoor air may not cause a significant humidification load (a regain issue), but may cause a structural condensation problem for the unconditioned space.
The following equation provides a value for the heating load produced by evaporative humidification devices. For this equation, CFMoa is the total flow of outdoor air (infiltration plus ventilation) and Grains Added is the grains of moisture added to the flow of outdoor air.
HHL (Btuh) = ACF x 0.68 x CFMoa x Grains Added x ACF
These equations determine the supply-side heating load (SHL) and moisture load (SML) for supply-side leakage, and the return-side heating load (RHL) and moisture load (RML) for return-side leakage. The total heating load (THL) and total moisture load (TML) for the duct system is equal to the sum of the supply and return values.
LHS (Btuh) = 1,054 x Pounds Water per Hour DSG (grains) = HLS / (0.68 x ACF x Bcfm) SG (grains) = RG + DSG LScfm = SA x SLR LRcfm = RA x RLR SHL (Btuh) = 0.68 x ACF x LScfm x (SG - OG) RHL (Btuh) = 0.68 x ACF x LRcfm x (RG - AG) THL (Btuh) = SML + RML SML (Lb water per Hr) = SHL / 1,054 RML (Lb water per Hr) = RHL / 1,054 TML (Lb water per Hr) = SML + RML Where: LHS is the latent heat (Btuh) added to supply air. For the first iteration, pounds water per hour is the moisture requirement for infiltration and engineered ventilation at the winter design condition, per Section 27.5 guidance. For the second and final iteration, pounds water per hour is equal to the Section 27.5 value plus the TML value from the first iteration. DSG is the grains of moisture added to supply air. ACF is the altitude correction factor (Table 10A). Bcfm is the blower Cfm. SG is the grains of moisture in the supply air . RG is the grains of moisture at the return grille (which defaults to the grains value for the conditioned space).
For example, adding 15 Grains of moisture to 100 CFM of outdoor air produces a 1,020 Btuh humidification load (at sea level).
HHL = 1.0 x 0.68 x 100 x 15 x 1.0 = 1,020 Btuh
223
Section 27
This value is determined by Table 12, or use altitude sensitive psychometric software. LScfm is the supply-side leakage Cfm. SA is the surface area of the exposed supply duct (SqFt). SLR is the leakage rate (Cfm/SqFt) for the supply duct. LRcfm is the return-side leakage Cfm. RA is the surface area of the exposed return duct (SqFt). RLR is the leakage rate (Cfm/SqFt) for the return duct. SHL is the latent heating load for supply moisture loss. OG is the grains of moisture for outdoor air at the winter design condition. This value is determined by Table 12, or use altitude sensitive psychometric software. RHL is the latent heating load for return moisture loss. AG is the grains of moisture in the ambient air that contacts the return duct . This defaults to OG if the unconditioned space is not tightly sealed (no regain), or may be about equal to RG if the unconditioned space is tightly sealed. (100% regain). THL is the total latent heating load . SML is the supply-side moisture loss. RML is the return-side moisture load . TML is the moisture load for both sides of the duct system.
Figure 27-5 shows the solutions for the first iteration and for the second and final iteration. Note that the humidification load is very sensitive to duct leakage (and much less sensitive to the iteration).
Duct Leakage Loads -- Iteration 1 6.5 Lb Water per Hr for Infiltration and Ventilation Sealed 0.06/0.06 Supply Btuh 367 Return Btuh 201 Sealed 0.12/0.24 Supply Btuh 734 Return Btuh 803 Unsealed 0.37/0.70 Supply Btuh 2,142 Return Btuh 2,341
Duct Leakage Loads -- Iteration 2 Lb Water per Hr for Infiltration, Ventilation and Duct Leakage 7.04 Sealed 0.06/0.06 7.96 Sealed 0.12/0.24 Supply Btuh 768 Return Btuh 803 10.75 Unsealed 0.37/0.70 Supply Btuh 2,428 Return Btuh 2,341
For example, the outdoor design temperature for a sea level dwelling is 0F, and the indoor design condition for winter humidification is 70F and 30% RH. Per Table 12, there are 4.4 grains for outdoor air and 32.5 grains for indoor air. The design humidification load for infiltration and ventilation is 6.5 Lb/Hr. The duct runs are in a vented attic, and 1,400 Cfm flows through the duct system. The supply-side surface area is 255 SqFt and the return-side surface area is 175 SqFt. Humidification loads are compared for ducts that are exceptionally tight (0.06/0.06 Cfm/SqFt), default sealed (0.12/0.24 Cfm/SqFt), and default unsealed (0.35/0.70 Cfm/SqFt).
Total Humidification Load (Lb/Hr) Sealed 0.06/0.06 7.04 Sealed 0.12/0.24 7.99 Unsealed 0.37/0.70 11.02
Figure 27-5
224
Section 28
Example A dwelling in Charleston, SC has a 2,000 SqFt gypsum board ceiling that is 5/8 of an inch thick. The ceiling is covered by blanket insulation that has negligible resistance to moisture migration. There is no vapor retarding membrane. The perm value for a 3/8 inch thick gypsum board is 5.0 Btuh/(100 SqFtGrain Difference). For 50% RH indoor humidity, the Table 1 grains difference value is 54. The latent load is 3,305 Btuh
MML = 5.0 x (0.375 / 0.625) x 54 x (2000 /100) = 3,305 Btuh
A latent cooling load is not an issue for higher elevations (see the Table 1 grains difference values). A winter humidification load is a design possibility for any elevation.
Table 1
Table 1A
Outdoor Design Conditions for the United States
Location Elevation Latitude Feet Degrees North Winter Heating 99% Dry Bulb Cooling 1% Dry Bulb Coincident Wet Bulb Summer Design Grains 55% RH Design Grains 50% RH Design Grains 45% RH Daily Range (DR)
Alabama Alexander City Anniston AP Auburn Birmingham AP Decatur Dothan AP Florence AP Gadsden Huntsville AP Mobile AP Mobile CO Montgomery AP Ozark, Fort Rucker Selma-Craig AFB Talladega Tuscaloosa AP Alaska Adak, NAS Anchorage IAP Anchorage, Elemendorf AFB Anchorage, Fort Richardson Annette Barrow Bethel Bettles Big Delta, Ft. Greely Cold Bay Cordova Deadhorse Dillingham Fairbanks IAP Fairbanks, Eielson AFB Galena Gulkana Homer Juneau IAP Kenai Ketchikan IAP King Salmon Kodiak Kotzebue McGrath Middleton Island Nenana Nome AP Northway Port Heiden Saint Paul Island Sitka Talkeetna Valdez Yakutat 19 144 212 342 110 44 123 643 1277 98 42 61 86 434 545 152 1579 78 19 92 88 57 73 11 337 87 362 37 1716 105 63 21 358 120 33 52 61 61 61 55 71 61 67 64 55 60 70 59 64 64 64 62 59 58 60 55 58 57 66 62 59 64 64 62 56 57 57 62 61 59 23 -9 -8 -13 17 - 36 -24 -44 -39 10 1 -34 -13 -41 -31 -31 -39 4 7 -14 20 -19 12 -31 -42 21 -44 -26 -32 -2 3 21 -21 7 2 57 68 69 71 70 52 68 75 75 57 67 61 66 77 78 74 73 62 69 65 68 67 65 64 73 60 76 65 74 61 52 64 73 66 63 53 57 57 58 59 49 57 59 58 53 57 54 56 59 60 59 56 55 58 55 59 56 56 58 58 51 59 55 57 52 50 58 58 55 55 -18 -20 -21 -20 -14 -25 -20 -22 -27 -18 -18 -21 -21 -26 -23 -21 -32 -18 -17 -23 -11 -22 -19 -9 -23 -31 -24 -23 -29 -29 -22 -9 -23 -25 -20 -11 -13 -14 -13 -7 -18 -13 -15 -20 -11 -11 -14 -14 -19 -16 -14 -25 -11 -10 -16 -4 -15 -12 -2 -16 -24 -17 -16 -22 -22 -15 -2 -16 -18 -13 -5 -7 -8 -7 -1 -12 -7 -9 -14 -5 -5 -8 -8 -13 -10 -8 -19 -5 -4 -10 2 -9 -6 4 -10 -18 -11 -10 -16 -16 -9 4 -10 -12 -7 L L L M L L M M M L M M M M M M M L L M L M L L M L M L M L L L M L L 686 612 776 644 592 401 581 569 629 218 26 221 356 166 528 170 33 33 32 33 34 31 34 34 34 30 30 32 31 32 33 33 22 24 22 23 16 32 21 20 20 30 29 27 31 26 22 24 93 93 93 92 93 93 94 94 92 92 93 93 94 95 94 94 76 76 76 75 74 76 75 75 74 76 77 76 77 77 76 77 39 39 39 34 27 39 31 31 28 41 46 39 44 42 37 44 46 46 46 41 34 46 38 38 35 48 53 46 51 49 44 51 52 52 52 47 40 52 44 44 41 54 59 52 57 55 50 57 M M M M M M M M M M M M M M M M
225
Table 1
Table 1A
Outdoor Design Conditions for the United States
Location Elevation Latitude Feet Degrees North Winter Heating 99% Dry Bulb Cooling 1% Dry Bulb Coincident Wet Bulb Summer Design Grains 55% RH Design Grains 50% RH Design Grains 45% RH Daily Range (DR)
Arizona Douglas AP Flagstaff Ap Fort Huachuca AP Kingman AP Nogalas Page Phoenix AP Phoenix, Luke AFB Prescott AP Safford, Agri. Center Tuscon Ap Winslow AP Yuma AP Arkansas Blytheville AFB Camden El Dorado AP Fayetteville AP Fort Smith AP Hot Springs Jonesboro Little Rock AP Pine Bluff AP Texarkana AP California Alameda, NAS Bakersfield AP Barstow Blue Canyon Blythe AP Burbank AP Chico Concord Covina Crescent City AP Downey El Cajon El Centro AP Escondido Eureaka/Arcata AP Fairfield-Travis AFB Fresno AP Hamiltion AFB Laguna Beach Lemoore, Reeves NAS Livermore Lompoc, Vandenburg AFB Long Beach AP Los Angeles AP Los Angeles CO Marysville, Beale AFB 15 507 1927 5280 397 775 238 23 575 57 110 387 -30 660 217 62 328 3 35 237 500 87 30 97 270 119 37 35 34 39 33 34 39 38 34 41 34 32 32 33 41 38 36 38 33 36 37 34 33 34 34 39 42 35 32 24 33 41 30 27 35 33 40 44 38 41 32 34 32 32 43 32 27 38 43 45 40 34 79 101 105 81 110 95 101 97 95 65 89 80 110 85 67 94 101 84 80 101 97 70 88 81 89 98 64 69 67 57 71 69 68 68 68 59 70 69 74 68 59 67 70 66 68 71 68 61 67 64 70 69 -6 -15 -32 -41 -18 -6 -22 -14 -11 -6 9 19 -3 5 -10 -15 -10 -4 0 -4 -14 -5 -5 -9 10 -10 1 -8 -25 -34 -11 1 -15 -7 -5 1 15 26 4 12 -3 -8 -3 3 3 3 -7 2 2 -2 17 -3 7 -2 -19 -28 -5 7 -9 -1 2 7 22 32 10 18 3 -2 3 9 6 9 -1 8 8 8 23 3 M H H M H M H H H M M H H H L H H H M H M M M L M H 264 130 277 1251 469 540 262 260 206 389 36 33 33 36 35 34 35 34 34 33 18 23 23 13 19 23 15 21 22 25 95 96 96 93 96 97 94 95 97 95 77 76 76 75 76 77 77 77 77 77 42 34 34 33 34 39 44 42 39 42 49 41 41 40 41 46 51 49 46 49 55 47 47 46 47 52 57 55 52 55 M M M M M M M M M M 4173 7011 4716 3446 3932 4310 1133 1101 5042 3176 2641 4938 213 31 35 31 35 31 36 33 33 34 32 32 35 32 31 8 28 27 32 24 37 38 20 26 24 14 44 95 83 92 97 96 97 108 107 91 99 103 93 109 63 55 62 63 64 62 70 71 60 66 66 60 72 -34 -54 -34 -38 -32 -43 -21 -14 -42 -25 -39 -46 -15 -27 -47 -27 -31 -25 -36 -14 -7 -35 -18 -30 -39 -8 -21 -41 -21 -25 -19 -30 -8 -1 -29 -12 -24 -33 -2 H H H H H H H H H H H H H
226
Table 1
Table 1A
Outdoor Design Conditions for the United States
Location Elevation Latitude Feet Degrees North 29 28 28 27 30 28 30 27 26 Winter Heating 99% Dry Bulb 35 47 38 43 28 40 33 43 47 Cooling 1% Dry Bulb 89 93 93 92 93 91 90 90 90 Coincident Wet Bulb Summer Design Grains 55% RH 59 59 39 61 39 49 57 57 57 Design Grains 50% RH 66 66 46 68 46 56 64 64 64 Design Grains 45% RH 72 72 52 74 52 62 70 70 70 Daily Range (DR) M M M M M M M M M
St. Augustine St. Petersburg Sanford Sarasota/Bradenton Tallahassee AP Tampa AP Valpariso, Eglin AFB Vero Beach West Palm Beach AP Georgia Albany, Turner AFB Americus Athens Atlanta AP Augusta AP Brunswick Columbus, Fort Benning Columbus, Lawson AFB Columbus, Metro AP Dalton Dublin Gainesville Griffin La Grange Macon AP Marietta, Dobbins AFB Moultrie Rome AP Savannah, Travis AP Valdosta, Moody AFB Valdosta, Regional AP Waycross Hawaii Ewa, Barbers Point NAS Hilo AP Honolulu AP Kahului Kaneohe Bay MCAS Lihue Molokai Wahaiwa Idaho Boise AP Burley Coeur DAlene AP Idaho Falls AP Kamiah Lewiston AP Moscow Mountain Home AFB Mullan
10 11 55 30 55 19 85 13 15
78 79 76 79 76 77 78 78 78
223 466 802 1010 148 20 232 971 397 710 310 1275 980 693 354 1068 292 637 49 233 203 151
31 32 34 33 33 31 32 32 32 34 32 34 33 33 32 34 31 34 32 31 30 31
30 25 25 23 25 34 27 24 27 22 25 21 22 23 27 26 30 21 29 34 31 32
95 94 92 91 94 91 94 93 93 93 93 91 90 91 94 91 95 94 93 94 94 94
76 76 75 74 76 79 76 76 75 76 76 74 75 75 75 74 77 74 76 77 76 76
49 37 34 30 37 62 37 39 33 39 39 30 38 36 31 30 42 25 39 44 37 37
56 44 41 37 44 69 44 46 40 46 46 37 45 43 38 37 49 32 46 51 44 44
62 50 47 43 50 75 50 53 46 52 52 43 51 49 44 43 55 38 52 57 50 50
M M M M M M M M M M M M M M M M M M M M M M
21 19 21 20 21 21 21 21
61 63 63 61 68 62 61 59
90 84 88 88 85 85 87 85
72 74 73 74 74 74 73 72
19 41 29 35 40 40 30 28
26 48 36 42 47 47 37 35
32 54 42 48 53 53 43 41
M L L M L L M L
43 42 47 43 46 46 46 43 47
9 2 -1 -6 15 15 0 5 7
94 90 86 89 93 93 87 96 84
63 62 61 60 64 64 62 62 61
H H H H H H H H H
229
Table 4A
Table 4A
Heating and Cooling Performance for Opaque Panels U-Values and Group Numbers or CLTD Values
Heating Application
Heating Load HTM = U-Value x (Indoor Design Temperature - Outdoor Design Temperature) Heating Load (Btuh) = HTM x Reference Area
Default indoor design temperature = 70 F. Outdoor design temperature provided by Table 1. Reference area provided with construction number. Heating Exceptions Number 15 Basement walls may be partly above grade and partly below grade: Below Grade Heating HTM = Below Grade U-Value x HTD; Heating Load = HTM x Below Grade Wall Area Above Grade Heating HTM = Above Grade U-Value x HTD; Heating Load = HTM x Net Above Grade Wall Area Above Grade Cooling HTM = Above Grade U-Value x CLTD; Cooling Load = HTM x Net Above Grade Wall Area Number 19 Passive or radiant floor over enclosed craw space: HTM = U-Value x Floor TD From Table 19 Number 20 Radiant floor over open crawlspace: HTM = U-Value x (HTD + 25) Number 22 Passive slab floor: HTM = F-Value x HTD; Heating Load = HTM x Running Feet of Exposed Edge Number 22 Radiant slab floor: HTM = F-Value x (HTD + 25); Heating Load = HTM x Running Feet of Exposed Edge Table 4C Partition wall for closed garage Table 4D Partition wall for closed sunroom Table 4E Ceiling below and encapsulated attic Cooling Application
Cooling HTM = U-Value x Table 4B CLTD Value Cooling Load (Btuh) = HTM x Reference Area Default indoor design temperature = 75 oF.
Outdoor design temperature and daily range provided by Table 1. Design Temperature Difference = Outdoor Design Temperature - Indoor Design Temperature Use the CLTD provided by Table 4A or use the Table 4A group number and the Table 4B CLTD. Reference area provided with construction number. Cooling Excpetions Table 4C Table 4D Table 4E Partition wall for closed garage Partition wall for closed sunroom Ceiling below an encapsulated attic
Wood Door A. Hollow Core B. Hollow Core with Wood Storm C. Hollow Core with Metal Storm D. Solid Core E. Solid Core with Wood Storm F. Solid Core with Metal Storm G. Panel H. Panel with Wood Storm I. Panel with Metal Storm Metal Door J. K. L. M. N. O. P. Q. Fiberglass Core Fiberglass Core with Storm Paper Honeycomb Core Paper Honeycomb Core, with Storm Polystyrene Core Polystyrene Core with Storm Polyurethane Core Polyurethane Core with Storm
U-Value 0.47 0.30 0.32 0.39 0.26 0.28 0.54 0.32 0.36 U-Value 0.60 0.36 0.56 0.34 0.35 0.21 0.29 0.17
15 M 26.0
H 21.0
L 35.0
20 M 31.0
30 H 36.0
35 H 41.0
309
Table 4A
Table 4A
Heating and Cooling Performance for Opaque Panels U-Values and Group Numbers or CLTD Values
Construction Number 15 Basement Walls Block (open or filled core), brick, concrete, insulated concrete form and plywood panel Insulation options: None, closed cell foam board, framing with cavity insulation (blanket or fill) and board-cavity combinations Insulation coverage code: From sill plate to 3 feet below grade = s3, from sill plate to floor = sf Core condition code: oc = open core; fc = filled core Framing code: w = wood, m = metal (studs 16 Inches on center, 75% cavity, 25% framing) Soil path code: (for distance from grade line to basement floor): x = 2, 4, 6, 8 or 10 feet A foundation wall that drops from grade to a floor that is at least 2 feet below grade is a below grade wall. Below Grade Reference Area = Distance From Grade To Floor x Length A foundation wall that is less than 2 feet below grade is part of the above grade wall (add below grade height to above grade height). Above Grade Reference Area = (Effective Above Grade Height x Length) - Area of Window and Door Openings Construction Description of Number Construction Insulation R-Value and Coverage Type of Stud Below Grade Wall Performance U-Value for Basement Floor Depth 2 4 6 8 10 Above Grade Performance U Group
15B Eight Inch Brick, Stone or Concrete Wall with Framing and Cavity Insulation 15B11-0w-x 15B11-0m-x 15B13-0w-x 15B13-0m-x 15B15-0w-x 15B15-0m-x 15B19-0w-x 15B19-0m-x 15B21-0w-x 15B21-0m-x Eight inches brick or stone, framing with R-11 in 2 x 4 cavity, no board insulation, plus interior finish Eight inches brick or stone, framing with R-13 in 2 x 4 cavity, no board insulation, plus interior finish Eight inches brick or stone, framing with R-15 in 2 x 4 cavity, no board insulation, plus interior finish Eight inches brick or stone, framing with R-19 in 2 x 6 cavity, no board insulation, plus interior finish Eight inches brick or stone, framing with R-21 in 2 x 6 cavity, no board insulation, plus interior finish Eight inches brick or stone, framing with R-11 in 2 x 4 cavity, R-4 board insulation, plus interior finish Eight inches brick or stone, framing with R-11 in 2 x 4 cavity, R-8 board insulation, plus interior finish Eight inches brick or stone, framing with R-13 in 2 x 4 cavity, R-4 board insulation, plus interior finish Eight inches brick or stone, framing with R-13 in 2 x 4 cavity, R-8 board insulation, plus interior finish Eight inches brick or stone, framing with R-19 in 2 x 6 cavity, R-4 board insulation, plus interior finish Eight inches brick or stone, framing with R-19 in 2 x 6 cavity, R-8 board insulation, plus interior finish R-11 cavity sill to floor Wood Metal R-13 cavity sill to floor Wood Metal R-15 cavity sill to floor Wood Metal R-19 cavity sill to floor Wood Metal R-21 cavity sill to floor Wood Metal 0.071 0.087 0.068 0.083 0.065 0.079 0.052 0.075 0.051 0.073 0.062 0.074 0.059 0.071 0.057 0.068 0.047 0.065 0.046 0.064 0.056 0.065 0.053 0.063 0.051 0.061 0.043 0.058 0.042 0.057 0.051 0.059 0.049 0.057 0.047 0.055 0.040 0.053 0.039 0.052 0.047 0.054 0.045 0.052 0.043 0.050 0.037 0.048 0.036 0.048 0.099 0.125 0.093 0.118 0.088 0.112 0.069 0.105 0.067 0.102 J J K K K K K K K K
15B Eight Inch Brick, Stone or Concrete Wall with Framing and Cavity Insulation Plus Board Insulation 15B11-4w-x 15B11-4m-x 15B11-8w-x 15B11-8m-x 15B13-4w-x 15B13-4m-x 15B13-8w-x 15B13-8m-x 15B19-4w-x 15B19-4m-x 15B19-8w-x 15B19-8m-x R-11 cavity sill to floor, plus 3 feet R-4 board R-11 cavity sill to floor, plus 3 feet R-8 board R-13 cavity sill to floor, plus 3 feet R-4 board R-13 cavity sill to floor, plus 3 feet R-8 board R-19 cavity sill to floor, plus 3 feet R-4 board R-19 cavity sill to floor, plus 3 feet R-8 board Wood Metal Wood Metal Wood Metal Wood Metal Wood Metal Wood Metal 0.053 0.062 0.043 0.048 0.051 0.059 0.041 0.046 0.042 0.055 0.035 0.044 0.050 0.058 0.043 0.048 0.048 0.056 0.042 0.047 0.040 0.052 0.035 0.044 0.048 0.054 0.043 0.048 0.046 0.053 0.042 0.047 0.038 0.049 0.035 0.044 0.045 0.051 0.041 0.046 0.043 0.049 0.040 0.045 0.036 0.046 0.034 0.042 0.042 0.047 0.039 0.043 0.041 0.046 0.038 0.042 0.034 0.043 0.032 0.040 0.071 0.083 0.055 0.063 0.068 0.080 0.053 0.061 0.054 0.074 0.044 0.057 K K K K K K K K K K K K
321
Table 4A
Table 4A
Heating and Cooling Performance for Opaque Panels U-Values and Group Numbers or CLTD Values
Construction Number 16A through 16F Insulated Ceiling Under Attic or Attic Knee Wall (see Table 4E for encapsulated attic) Ventilation options: Unvented or vented to FHA specifications, or attic fan, or extra attic vent area. Roofing material options: Asphalt shingles, wood shakes, tile, slate, metal, concrete, tar and gravel or membrane. Roof color options: Dark, red or solid bold color; light color, light gray, silver or unpainted metal and white (see absorptivity notes). Reference Area = Gross Area - Skylight Area (SqFt) Number 16A 16A-0 16A-7 16A-11 16A-13 16A-15 16A-19 16A-21 16A-25 16A-28 16A-30 16A-38 16A-44 16A-56 16B 16BR 16B-0 16B-7 16B-11 16B-13 16B-15 16B-19 16B-21 16B-25 16B-28 16B-30 16B-38 16B-44 16B-50 16B-56 Construction Notes Insulation R-Value U-Value CLTD Values Ceilings Under an Attic or Attic Knee Wall
Attic temperature = 150 F when outdoor temperature = 95 F Unvented Attic, No Radiant Barrier, Any Roofing Material, Any Roof Color 16A Unvented attic over ceiling or same type of air space behind an attic knee wall. None R-7 R-11 R-13 R-15 R-19 R-21 R-25 R-28 R-30 R-38 R-44 R-56 0.408 0.112 0.081 0.070 0.061 0.049 0.044 0.038 0.034 0.032 0.026 0.022 0.018 L 69 10 M 65 L 74 Design Temperature Difference and Daily Range 15 M 70 H 65 L 79 20 M 75 H 70 M 80 25 H 75 30 H 80 35 H 85
Roofs and ceilings do not have a group number. 16A Roofing material code: None required Roof color code: None required
Attic temperature = 130 F when outdoor temperature = 95 F 16B = Vented Attic, No Radiant Barrier, Dark Asphalt Shingles or Dark Metal, Tar and Gravel or Membrane 16BR = Unvented Attic with Radiant Barrier, Any Roofing Material, Any Roof Color 16B FHA vented attic with no radiant barrier over ceiling or same type of air space behind an attic knee wall. 16BR Unvented attic with radiant barrier over ceiling or same type of air space behind an attic knee wall. None R-7 R-11 R-13 R-15 R-19 R-21 R-25 R-28 R-30 R-38 R-44 R-50 R-56 0.408 0.112 0.081 0.070 0.061 0.049 0.044 0.038 0.034 0.032 0.026 0.022 0.020 0.018 16BR Roof material code: None required Roof color code: None required L 49 10 M 45 L 54 Design Temperature Difference and Daily Range 15 M 50 H 45 L 59 20 M 55 H 50 M 60 25 H 55 30 H 60 35 H 65
Roofs and ceilings do not have a group number. 16B Roofing code: a = asphalt shingles, m = metal, x = tar/gravel, z = membrane Roof color code: d = dark (absorptivity of roofing material exceeds 0.75) Red or solid bold color shingle = dark color
326
Table 4A
Table 4A
Heating and Cooling Performance for Opaque Panels U-Values and Group Numbers or CLTD Values
Construction Number 16A through 16F Insulated Ceiling Under Attic or Attic Knee Wall (see Table 4E for encapsulated attic) Ventilation options: Unvented or vented to FHA specifications, or attic fan, or extra attic vent area. Roofing material options: Asphalt shingles, wood shakes, tile, slate, metal, concrete, tar and gravel or membrane. Roof color options: Dark, red or solid bold color; light color, light gray, silver or unpainted metal and white (see absorptivity notes). Reference Area = Gross Area - Skylight Area (SqFt) Number 16C 16CR 16C-0 16C-7 16C-11 16C-13 16C-15 16C-19 16C-21 16C-25 16C-28 16C-30 16C-38 16C-44 16C-50 16B-56 16D 16DR 16D-0 16D-7 16D-11 16D-13 16D-15 16D-19 16D-21 16D-25 16D-28 16D-30 16D-38 16C-44 16C-50 Construction Notes Insulation R-Value U-Value CLTD Values Ceilings Under an Attic or Attic Knee Wall
Attic temperature = 120 oF when outdoor temperature = 95 oF 16C = Vented Attic, No Radiant Barrier, White or Light Color Shingles, Any Wood Shake, Light Metal, Tar and Gravel or Membrane 16CR = Vented Attic with Radiant Barrier; 16CF = Attic Fan; Dark Asphalt Shingles or Dark Metal, Tar and Gravel or Membrane 16C FHA vented attic with no radiant barrier over ceiling or same type of air space behind an attic knee wall. 16CR FHA vented attic with radiant barrier over ceiling or same type of air space behind an attic knee wall. 16CF Dark roof, FHA vented attic with attic fan; or extra attic vent area. None R-7 R-11 R-13 R-15 R-19 R-21 R-25 R-28 R-30 R-38 R-44 R-50 R-56 0.408 0.112 0.081 0.070 0.061 0.049 0.044 0.038 0.034 0.032 0.026 0.022 0.020 0.018 L 39 10 M 35 L 44 Design Temperature Difference and Daily Range 15 M 40 H 35 L 49 20 M 45 H 40 M 50 25 H 45 30 H 50 35 H 55
Roofs and ceilings do not have a group number. 16C Roofing code: a = shingles, w = shakes, m = metal, x = tar/gravel, z = membrane Roof color code: l = light (absorptivity of roofing material 0.50 to 0.75) Light gray shingle, unpainted metal or silver membrane = light color 16CR or 16CF Roof material code: a = asphalt shingles, m = metal, x = tar/gravel, z = membrane Roof color code: d = dark (absorptivity of roofing material exceeds 0.75) Red or solid bold color shingle = dark color See glossary for definition: Attic fan Extra attic vent area
Attic Temperature = 110 oF when outdoor temperature = 95 oF 16DR = Vented Attic, No Radiant Barrier, Dark Tile, Slate or Concrete 16DR = Vented Attic with Radiant Barrier, White or Light Color Shingles; Any Wood Shake; Light Metal, Tar and Gravel or Membrane 16D FHA vented attic with no radiant barrier over ceiling or same type of air space behind an attic knee wall. 16DR FHA vented attic with radiant barrier over ceiling or same type of air space behind an attic knee wall. 16DF Light roof, FHA vented attic with attic fan; or extra attic vent area. None R-7 R-11 R-13 R-15 R-19 R-21 R-25 R-28 R-30 R-38 R-44 R-50 0.408 0.112 0.081 0.070 0.061 0.049 0.044 0.038 0.034 0.032 0.026 0.022 0.020 L 29 10 M 25 L 34 Design Temperature Difference and Daily Range 15 M 30 H 25 L 39 20 M 35 H 30 M 40 25 H 35 30 H 40 35 H 45
Roofs and ceilings do not have a group number. 16D Roofing code: t = tile (terra cotta, slate or concrete) Roof color code: d = dark (absorptivity of roofing material exceeds 0.75) Red or solid bold color tile = dark color 16DR or 16DF Roofing code: a = shingles, w = shakes, m = metal, x = tar/gravel, z = membrane Roof color code: l = light (absorptivity of roofing material 0.50 to 0.75) Light gray shingle, unpainted metal or silver membrane = light color See glossary for definition: Attic fan Extra attic vent area
327
Table 4A
Table 4A
Heating and Cooling Performance for Opaque Panels U-Values and Group Numbers or CLTD Values
Construction Number 16A through 16F Insulated Ceiling Under Attic or Attic Knee Wall (see Table 4E for encapsulated attic) Ventilation options: Unvented or vented to FHA specifications, or attic fan, or extra attic vent area. Roofing material options: Asphalt shingles, wood shakes, tile, slate, metal, concrete, tar and gravel or membrane. Roof color options: Dark, red or solid bold color; light color, light gray, silver or unpainted metal and white (see absorptivity notes). Reference Area = Gross Area - Skylight Area (SqFt) Number Construction Notes Insulation R-Value U-Value CLTD Values Ceilings Under an Attic or Attic Knee Wall
16E 16ER 16E-0 16E-7 16E-11 16E-13 16E-15 16E-19 16E-21 16E-25 16E-28 16E-30 16E-38 16E-44 16E-50 16F 16FR 16F-0 16F-7 16F-11 16F-13 16F-15 16F-19 16F-21 16F-25 16F-28 16F-30 16F-38 16F-44 16F-50
Attic Temperature = 105 oF when outdoor temperature = 95 oF 16E = Vented Attic, No Radiant Barrier, Light Tile, Slate or Concrete 16ER = Vented Attic with Radiant Barrier, Dark Tile, Slate or Concrete 16E FHA vented attic with no radiant barrier over ceiling or same type of air space behind an attic knee wall. 16ER FHA vented attic with radiant barrier over ceiling or same type of air space behind an attic knee wall None R-7 R-11 R-13 R-15 R-19 R-21 R-25 R-28 R-30 R-38 R-44 R-50 0.408 0.112 0.081 0.070 0.061 0.049 0.044 0.038 0.034 0.032 0.026 0.22 0.20 L 24 10 M 20 L 29 Design Temperature Difference and Daily Range 15 M 25 H 20 L 34 20 M 30 H 25 M 35 25 H 30 30 H 35 35 H 40
Roofs and ceilings do not have a group number. 16E Roofing code: t = tile (terra cotta, slate or concrete) Roof color code: l = light Light gray tile = light color (absorptivity of roofing material 0.50 to 0.75) 16ER Roofing code: t = tile (terra cotta, slate or concrete) Roof color code: d = dark (absorptivity of roofing material exceeds 0.75) Red or solid bold color tile = dark color
Attic Temperature = 95 oF when outdoor temperature = 95 oF 16F = Vented Attic, No Radiant Barrier, White Tile, Slate or Concrete; White Metal or White Membrane 16FR = Vented Attic with Radiant Barrier, Light or White Tile, Slate or Concrete; White Metal or White Membrane 16F FHA vented attic with no radiant barrier over ceiling or same type of air space behind an attic knee wall. 16FR FHA vented attic with radiant barrier over ceiling or same type of air space behind an attic knee wall None R-7 R-11 R-13 R-15 R-19 R-21 R-25 R-28 R-30 R-38 R-44 R-50 0.408 0.112 0.081 0.070 0.061 0.049 0.044 0.038 0.034 0.032 0.026 0.022 0.020 L 14 10 M 10 L 19 Design Temperature Difference and Daily Range 15 M 15 H 10 L 24 20 M 20 H 15 M 25 25 H 20 30 H 25 35 H 30
Roofs and ceilings do not have a group number. 16F Roofing code: t = tile (terra cotta, slate or concrete), x = metal, z = membrane Roof color code: w = white (absorptivity of roofing less than 0.50) 16FR Roofing code: t = tile (terra cotta, slate or concrete), x = metal, z = membrane Roof color code: l = light (absorptivity of roofing material 0.50 to 0.75) w = white (absorptivity of roofing material less than 0.50) Light Gray tile = light color
328
Table 4C
Table 4C
Approximate Ambient Temperature in a Closed Garage
The temperature rise values provided by Table 4C are approximations (see the table notes) that can be used to estimate partition heating load and cooling load for the listed scenarios. Rough estimates for ambient space temperatures are suitable for this task because partition loads are relatively small when compared to the total load. For example, if the partition load is 3 percent of the total load, a 20 percent error in the partition load translates to a less than 1 percent error in the total load. The temperature rise values for scenarios that are significantly different than the listed scenarios are provided by the heat balance procedure that appears in Section 18 of the unabridged version of Manual J. Garage 1: Two car garage, no significant glass area, one insulated partition wall, garage walls have no insulation, uninsulated garage ceiling under vented attic.
Temperature rise values are daily averages. Hourly values may be larger or smaller.
Garage 2: Two car garage, no significant glass area, conditioned space above garage, insulated ceiling partition, one insulated partition wall, garage walls have no insulation. (Note: A conditioned space above a garage should be a separate zone.)
Temperature rise values are daily averages. Hourly values may be larger or smaller.
349
Table 4D
Table 4D
Approximate Ambient Temperature in an Isolated Sunroom
Sunroom 1: Primary exposure faces South, 24 Ft wide by 12 Ft deep, sunroom walls are 60 percent double-pane clear glass (no external or internal shade), sunroom walls and ceiling are insulated, one insulated partition wall with sliding glass door. Note: Sunrooms should be architecturally and mechanically isolated from the main living space. If conditioned, heating and cooling should be provided by a separate system.
Temperature rise values are daily averages. Hourly values may be larger or smaller. Sun Room 2: Primary exposure faces South, 24 Ft wide by 12 Ft deep, sunroom walls are 60 percent spectrally-selective glass (no external or internal shade), sunroom walls and ceiling are insulated, one insulated partition wall with sliding glass door. Note: Sunrooms should be architecturally and mechanically isolated from the main living space. If conditioned, heating and cooling should be provided by a separate system.
Temperature rise values are daily averages. Hourly values may be larger or smaller.
350
Table 4E
Table 4E
Approximate Ambient Temperature in an Encapsulated Attic
Encapsulated Attic: Attic space roof and gable ends sprayed with R-19 insulating foam. Attic space sealed (no vents, infiltration 0.15 ACH or less). Attic floor is uninsulated plasterboard (ceiling of conditioned space below the attic).
Table 1A Cooling Drybulb (F) 95 79F Partition ceiling: Load area = 2,400 SqFt R-value of insulation: No insulation Finish: Plaster board 105 80F 115 81F
The ambient air condition depends on the actual construction details. Section 18-5 provides guidance for estimating the temperature of an unconditioned space (buffer zone). Tables 4E, 7M and 7N apply when the air condition in the actual space is similar (say 5 F) to the Table 4E values.
Duct Loads
Table 4E shows that the ambient temperature in an encapsulated attic is benign and relatively constant for heating and cooling. Foam seals attic cracks, so attic humidity is similar to indoor humidity. Tables 7M and 7N provide duct load factors and latent loads for ducts runs in an encapsulated attic. Comments on these tables are provided here.
n n
Attic behavior should be similar to Table 4E. For heating, the ambient temperature is relatively steady as outdoor temperature increases, so the duct load is a lager portion of the total load as outdoor conditions moderate. For cooling, the ambient temperature is relatively steady as outdoor temperature decreases, so the sensible duct load is a lager portion of the total sensible load as outdoor conditions moderate. For cooling, the latent duct load is based on some envelope leakage (the grains difference for computing the duct load is 20% of the Table 1 value). Include a surface area adjustment when duct surface areas are known or estimated.
351
Table 7C-AE -- Trunk and Branch Supply System in 16B Attic, Return Riser In Floor to Ceiling Chase 7C-AE Ambient drybulb temperature = Outdoor db + 11 (heating) and Outdoor db + 35 (cooling) Supply location = Core of floor plan, near airhandler Nominal return Cfm = Blower Cfm Return location = Floor of conditioned space Duct leakage Cfm per SqFt of duct surface area (supply / return) = 0.06/0.06; 0.09/0.15; 0.12/0.24; 0.24/0.47; 0.35/0.70 Duct wall insulation R-value = 2, 4, 6 and 8
Base Case Heat Loss Factor (BHLF) R6 Insulation, ASHRAE Sealed (Supply = 0.12, Return = 0.24) Square Feet of Floor Area OAT 1000 1500 2000 2500 3000 -10 0.138 0.157 0.176 0.195 0.217 0 0.131 0.145 0.164 0.184 0.199 10 0.118 0.133 0.148 0.166 0.188 20 0.111 0.122 0.138 0.150 0.170 30 0.098 0.119 0.129 0.141 0.153 40 0.085 0.103 0.120 0.135 0.148
Base Case Sensible Gain Factor (BSGF) R6 Insulation, ASHRAE Sealed (Supply = 0.12, Return = 0.24) Square Feet of Floor Area 1500 2000 2500 0.170 0.200 0.220 0.161 0.203 0.220 0.175 0.203 0.220 0.180 0.203 0.220 0.185 0.207 0.224
Base Case Latent Gain (BLG) R6 Insulation, ASHRAE Sealed (Supply = 0.12, Return = 0.24) Square Feet of Floor Area Grains 1000 1500 2000 2500 3000 10 111 166 214 264 297 20 157 234 303 373 420 30 205 306 395 487 549 40 255 280 492 606 683 50 307 458 592 730 823 60 361 639 697 859 968 70 417 624 806 994 1119
R2 2.02
R4 1.28
R6 1.00
R8 0.84
R2 2.19
R4 1.30
R6 1.00
R8 0.80
Leakage Correction (LCF) for Heat Loss Leakage R2 R4 R6 0.06 / 0.06 0.87 0.83 0.78 0.09 / 0.15 0.92 0.89 0.86 0.12 / 0.24 1.00 1.00 1.00 0.24 / 0.47 1.40 1.56 1.68 0.35 / 0.70 1.84 2.21 2.47
Leakage Correction (LCF) for Sensible Gain Leakage R2 R4 R6 0.06 / 0.06 0.90 0.85 0.80 0.09 / 0.15 0.95 0.91 0.90 0.12 / 0.24 1.00 1.00 1.00 0.24 / 0.47 1.26 1.35 1.42 0.35 / 0.70 1.56 1.74 1.88
Leakage 0.06 / 0.06 0.09 / 0.15 0.12 / 0.24 0.24 / 0.47 0.35 / 0.70
Leakage Correction (LCF) for Latent Gain Any R-Value 0.28 0.62 1.00 2.81 4.88
Default Duct Wall Surface Area (SqFt) Floor Area Look-Up Value 1000 SqFt 1500 SqFt 2000 SqFt 2500 SqFt Supply Return Supply Return Supply Return Supply Return 189 50 276 70 361 90 431 110 See Sections 6-8 and 23-6 for instruction for determing the floor area look-up value.
Surface Area Factors Leakage Ks Kr 0.06 / 0.06 0.975 0.025 0.09 / 0.15 0.972 0.028 0.12 / 0.24 0.969 0.031 0.24 / 0.47 0.965 0.035 0.35 / 0.70 0.962 0.038
Surface Area Adjustment Factor (SAA) for Heat Loss or Sensible Gain SAA = Ks x (Actual supply area / Default supply area) + Kr x (Actual return area / Default return area) Example: Floor area lookup value = 2,000 SqFt; duct leakage = 0.09 / 0.15; default areas = 361 and 9 SqFt. Actual system has 285 SqFt on supply side and 19 SqFt on return side Ks = 0.972, Kr = 0.028 SAA =0.972 x (285 / 361) + 0.028 x (19 / 9) = 0.826
Surface Area Adjustment (SAA) for Latent Gain SAA = Actual return-side area / Default return-side area Example: Floor area lookup value = 2,000 SqFt; default duct surface areas = 229 and 51 SqFt. Actual system has 285 SqFt on supply side and 95 SqFt on return side SAA = 95 / 51 = 1.863
Procedure for Heat Loss and Sensible Gain Factor Adjustment Step 1: Select the default heat loss factor or the default sensible gain factor. Step 2: Apply R-value correction to default value. Step 3: Apply leakage correction to Step 2 value. Step 4: Apply the surface area adjustment to the Step 3 value.
Procedure for Latent Gain Adjustment Step 1: Select the default latent gain factor. Step 2: Apply leakage correction to Step 1 value. Step 3: Apply surface area adjustment to the Step 2 value.
Notes 1) This table provides load factors for systems that features one large return because such designs are common (but not recommended by ACCA). 2) Multiple returns improve comfort and room air motion, stabilize room pressures and blower Cfm (as interior doors open and close) and reduce the noise level in the conditioned space. 3) The load factors in this table are compatible with duct systems that are designed according to Manual J , Manual S and Manual D procedures. 4) Duct systems designed by other procedures may not provide adequate air distribution (surface area adjustment does produce an acceptable duct load estimate for such systems). 5) ACCA recommends sealing duct systems that have leakage rates greater than the 0.12 / 0.24 scenario. Use the data for leakier scenarios to evaluate the benefit of the sealing work.
Table 7
Vented attic or attic knee wall space above 16C ceiling (120 F attic when OAT = 95 F). Vented attic or attic knee wall space above 16D ceiling (110 F attic when OAT = 95 F). Vented attic or attic knee wall space above 16E ceiling (105 oF attic when OAT = 95 F). Vented attic or attic knee wall space above 16F ceiling (95 F attic when OAT = 95 F). Open crawl space or garage (95 F ambient when OAT = 95 F). Closed crawl space below insulated floor, no wall insulation. Unconditioned basement or closed crawl space with: a) No wall or ceiling insulation b) Wall insulation only c) Wall and ceiling insulation Supply runs below ground slab. Return runs in conditioned space or in attic. Riser or drop in exterior wall. Encapsulated attic
On roof -1 = Reflective surface in sun -2 = White surface in sun -3 = Dark surface in sun -4 = Any surface in shade
1) 2) 3) 4) 5)
Floor plan size and duct system geometry determine the default heating cooling loads, the default blower Cfm, and the duct surface area defaults. Duct wall insulation R-values = R2, R4, R6 ord R8 (use "Powered by Manual J" software for R0). Duct leakage Cfm per SqFt or duct surface area (supply-side / return-side) = 0.06/0.06, 0.09/0.15, 0.12/0.24, 0.24/0.47 or 0.35/0.70. The default surface areas for these duct tables are compatible with systems designed by Manual D procedures. ACCA recommends sealing duct systems that have leakage rates greater than the 0.12/0.24 scenario. Use leakier scenarios to evaluate sealing benefit.
361
387
Table 7
388
Table 7
389
Table 7
390
Table 7
391
Table 7
392
Table 7
393
Table 7
394
Table 7
395
Table 7
Table 7
Notes
1) The Table 7 load factors account for the conduction loads and leakage loads that occur on the supply and return sides of the duct system. These factors also include an adjustment for an increase or decrease in the envelope infiltration load (per a set of power law equations), depending on the relative amount of supply-side and return-side leakage. 2) The Table 7 data is compatible with duct systems that have dominant supply-side leakage (with the exception of return runs located in exterior walls). The load factors and latent load values are compatible with duct system surface areas generated by theManual D sizing pro- cedure and the five default leakage ratesprovided by Table 7. Computerized duct load solutions (models) are required for duct systems that have dominant return side leakage or a leakage rate that is substantially different than the default values. 3) The Table 7 heat loss factors depend on the temperature of the supply air. These factors tend to get smaller as the discharge temperature increases because (by the sensible heat equation) the supply CFM values and airway sizes (exposed area) get smaller as the supply temperature increases. Table 7 uses a 100 F default for discharge temperature because it produces conservative duct load values and because the heat loss factors are compatible with airway sizes required for cooling. Computerized duct load solutions (models) are required for other supply air temperatures. 4) Table 7 produces values duct load values if a duct system installation is reasonably similar to one of the default scenarios. The Table 7 data is based on assumptions pertaining to the floor plan of the home, the location of the air handler, the number of supply runs, the number of the return runs and a set of leakage rate values. These assumptions are listed here.
Rectangular floor plan with a 2:1 aspect ratio. Air handler located in the center of the floor plan. One supply branch per 100 CFM of supply air. One return branch per 400 CFM of return air (the four AE tables and the eight O and P tables are for 1,000 cfm per return). Supply ducts not sealed (0.35 / .070 scenario) have 35 CFM of leakage per 100 SqFt duct surface area. Return ducts not sealed (0.35 / .070 scenario) have 70 CFM of leakage per 100 SqFt duct surface area. Supply ducts sealed (0.12 / 0.24 scenario) have 12 CFM of leakage per 100 SqFt duct surface area. Return ducts sealed (0.12 / 0.24 scenario) have 24 CFM of leakage per 100 SqFt duct surface area. Duct runs below slab have an average of 3 CFM leakage per 100 SqFt duct system surface area. (Duct runs below the slab have no leakage and are water tight. The leakage occurs along the above grade duct runs). Table 4E provides default dry-bulb temperatures for the ambient air in an encapsulated attic; and the default for grains of moisture difference (for the attic air and return air) is 20% of the Table 1A or Table 1B value. For heating, the default value for ambient dry-bulb temperature for duct on a roof equals the Table 1A or1B value. For cooling, the default value for ambient dry-bulb temperature for duct on a roof depends on the color of the outside surface of the duct, and weather the duct is in the sun or shade.
a) For a reflective surface in the sun, the ambient dry-bulb equals the Table 1A or 1B dry-bulb plus 20F. b) For a white or light surface in the sun, the ambient dry-bulb equals the Table 1A or 1B dry-bulb plus 35F. c) For a black or dark surface in the sun, the ambient dry-bulb equals the Table 1A or 1B dry-bulb plus 65F. d) For any surface in continuous shade, the ambient dry-bulb equals the Table 1A or 1B dry-bulb plus 10
For cooling, the default value for grains of moisture difference (for the outdoor air and return air) is equal to the Table 1A or Table 1B value.
5) The average leakage rate for duct systems that are carefully sealed by approved methods may be substantial lower than the sealed leakage rates listed by the previous note. Performance should be certified by test or quality control program before taking credit for this type of sealing effort. 6) When using Table 7, use the load factors and latent gain values for unsealed duct systems ( 0.35 / .070 scenario) when duct tape is used to seal the leakage points. (Duct tape is not and approved sealing method. Sealing work must conform to industry standards.) 7) If a duct run is located in a garage, use Table 7G. If a duct run is located behind an attic knee wall or between the joists in a roof-ceiling sandwich, use Table 7A. 8) The Table 7 load factors are compatible with the ambient temperatures listed by Figure 23-6. If the load estimating software performs an energy balance on an unconditioned space, the estimated space temperature should be used to generate load factors for the duct runs that pass through the space (providing the software use the Manual J duct load model, see note 12). 9) Table 7 can be used to produce load factors and latent gain values for duct runs that pass through different types of spaces, and run segments that have different leakage rates and insulation R-values. See Worksheet G1. 10) When duct runs are in an exposed wall, the duct load factor for the riser or drop is added to the load value for the system (see Worksheet G1). This procedure applies to all the exposed-wall load factors (heating percentage, cooling percentage or latent load value.). Note that the load factor for a two-story riser or drop is twice the single-story value, etc..
396
Appendix 1 same with the J1AE form. Then repeat the process for Sections 8 and 9. Refer to Sections 3 and 6; and Appendices 4, 7, 8 and 9, as required. Learn to use the MJ8AE spreadsheet (redo the example dwellings in the book, or investigate a simple dwelling that is available for survey). Read Sections 2 and Appendix 6 internalize this guidance Go to Appendix 2 and read the capabilities and sensitivities material. Make sure that you understand the limitations of MJ8AE. Use advanced Manual J procedures for applications that are not compatible with MJ8AE. Read Appendix 3 and make sure you understand these concepts. Make sure you understand the limitations of MJ8AE. Use advanced Manual J procedures for applications that are not compatible with MJ8AE. Read the Introduction of this manual and internalize this guidance. Read Section 10 and acquire the necessary knowledge and skills. Pay particular attention to the error checking procedure. constructions exclusively supported by advanced Manual J procedures can be imported to Form J1AE, or the MJ8AE spreadsheet. See advanced procedures for:
n n n n n
More types of opaque panels (Table 4A) NFRC glass (Table 3D-1) Alternative infiltration load methods (Section 21) More internal load options (Tables 6A and 6B) More duct system options (Table 7)
Note 1: AED excursions are common, even for fenestration plans that seem to have begin attributes. The AE procedure will not be equivalent to the full procedure if the dwelling's AED excursion is greater than zero. There is no simple way to simulate the information provided by the AED curve, and no simple way to estimate the AED excursion value. Note 2: When using Manual J for attic duct systems, make sure the Table 4A construction number for the attic ceiling and the Table 7 option (7A through 7F) are compatible. Note 3: For duct loads, "Powered by Manual J" software can be used to evaluate the attributes of the "as-installed" system (user-specified R-values, sealing options and surface areas).
A1-6 Expanding MJ8AE Capability The HTM x Load Area concept applies equally to MJ8AE and to Manual J . Therefore, HTM values for
401
Appendix 2
Window and glass door framing shall be metal, metal with break, wood or vinyl. Windows can have a fixed or operable sash (sliding glass doors have an operable sash). Windows and glass doors shall not be equipped with external sun screens. The foreground reflectance for window and glass door heat-gain shall be 0.20. Use advanced Manual J procedures for Fenestration rated by the NFRC, for other internal and external shading options, for other foreground reflectance options, and for latitude-adjusted HTM's for generic fenestration.
Skylights n Skylights shall have clear (single pane or double pane) glass. n Skylight glazing shall be flat. n Skylights shall not be equipped with a light shaft. n Use advanced Manual J procedures for Fenestration rated by the NFRC, for internal shading options, for curb and light-shaft options, and for latitude-adjusted HTM's for generic fenestration. Walls n Above grade wall construction shall be woodstud frame or empty-core block. n Exterior finish options shall be brick veneer or stucco/siding. n Interior finish shall default to gypsum board (i.e. plaster board, dry-wall, sheet rock, etc.) n Below grade wall construction shall default to empty-core block. n Block walls may have board insulation and/or wood-stud framing with blanket or fill insulation. n Use advanced Manual J procedures for other structural material options (logs, stress-skin foam, concrete-foam matrix, aerated concrete, brick, poured concrete), insulation arrangements and R-value options, block with filled cores, and metal studs. Ceilings and Attic Knee Walls n The ceiling options shall be attic ceiling, ceiling on exposed beams or joist ceiling sandwich. n The roofing material shall be dark-shingles. n The roof deck material shall be plywood for all types of roof construction. n Attic construction shall be FHA-vented with no radiant barrier or attic foam.
Windows and glass doors shall be reasonably distributed around the dwelling. There shall be no large skylights in any room (skylight load area does not exceed 5% of room floor area). The dwelling shall have adequate exposure diversity (see Appendix 3). There shall be no excursion adjustment for the sensible fenestration load (see Appendix 3). Simple default values shall be used for the occupancy loads and appliance load. Use advanced Manual J procedures for applications that do not have these attributes.
Comfort System n A central, single-zone air system, or electric baseboard elements shall provide heat. n Cooling shall be provided by a central, singlezone, constant volume system. n Use advanced Manual J procedures for zoned systems, variable volume systems and distributed equipment. Windows and Glass Doors n Window and glass doors shall have clear (single, double or triple pane) glass.
403
Appendix 2
n
Knee walls shall be installed in a FHA-vented attic space. Insulation shall be blanket and/or board or fill (as appropriate for the type of roof construction). Use advanced procedures for other types of roofing material, roof color, attic with radiant barrier, encapsulated foam, unvented attic or knee-wall space.
The engineered ventilation system shall not have a heat recovery device or a ventilation dehumidifier. Use advanced Manual J applications for engineered ventilation systems and ventilating dehumidifer equipment.
Floors n All floors shall be passive (no heating elements below the floor). n Floors over an open space shall have carpet or tile cover with floor insulation options. n Slab floors shall have vertical insulation that covers the edge, or no insulation. n Slab floor soil conditions may be heavy-moist; heavy-dry; light-wet; or light-dry. n Basement floors shall be uninsulated. n Use advanced Manual J procedures for radiant floors, other combinations of crawlspace tightness and wall R-value, insulated basement floor, and other slab insulation options. Infiltration n All infiltration estimates shall be based on the ACH values provided by Table 5A of MJ8AE. n Dwellings shall be rated: very-tight, semi-tight, average, semi-loose and loose (definitions are provided). n There shall be no space pressure adjustment for engineered ventilation (50 Cfm or less). n Infiltration induced or reduced by duct runs in an unconditioned space is evaluated by the duct-table factors. n Use Section 21 procedures to estimate infiltration rates (and loads) by blower door test or component leakage method, or to adjust infiltration rate for pressurization (or depressurization) caused by an engineered ventilation system. Duct System n A duct system shall be entirely in the conditioned space, or shall be compatible with one of the system scenarios in Figure 1-1 of Section 1. n Duct systems (trunks and runouts) shall be (essentially) installed in one horizontal plane. n Use the unabridged version of Table 7 for other locations and combinations of airway shape and system geometry. Engineered Ventilation n Engineered ventilation may be provided by piping a small amount (50 Cfm or less) of fresh air to the return-side of the duct system.
Other Loads n Internal load (choice of two default values) n Blower heat (one default value) n Use Section 22 procedures for other internal load options (occupants, appliances, lighting, etc.), any blower motor power, winter humidification load, hot-water piping loss, and moisture migration load.
404
Appendix 4 and latent capacity. Supply-side gains reduce the cooling capacity of the airflow delivered by the supply air outlets. Duct loads are caused by conduction through the duct wall and by leakage. Duct leakage also causes negative or positive pressure in the conditioned space. The space pressure condition depends on the difference between the return side leakage rate and the supply side leakage rate. If the return side leakage rate is greater than the supply side leakage rate, there is a net flow of air from outside the conditioned space to the conditioned space. This causes a positive pressure in the conditioned space, exfiltration from the conditioned space and a direct load on the central equipment (the air that leaks into the return duct passes through the central equipment before it enters the conditioned space). If the supply side leakage rate is greater than the return side leakage rate, the flow rate through the return grilles is greater than the flow rate through the supply outlets. This causes a negative pressure in the conditioned space, the infiltration to the conditioned space is increased and the load on the central equipment is larger. The heating and sensible cooling loads generated by duct systems are sensitive to a collection of parameters and interactions that include the piping geometry, the location of the duct runs, the temperature and moisture content of the air in the duct runs, the temperature and moisture content of the air in the surrounding environment, the tightness of seams and joints and the amount of duct-wall insulation. Duct loads also depend on the size of the dwelling and the construction details because equipment size, blower CFM, the size of the duct airways and the total surface area of the duct system depend on the size of the heating and cooling loads. An attic is a hostile environment for duct runs if attic temperature is significantly higher than the outdoor temperature in the summer (white shingles, tile roofs, radiant barriers and foam encapsilation moderate this condition); and almost as cold as the outdoor air in the winter. In addition, the absolute humidity in a properly vented attic is about the same as the outdoor humidity (the absolute humidity in a foam encapsulated attic will be closer to the conditioned space value). Open crawlspace locations are undesirable because there is little difference between the crawlspace condition and the condition of the outdoor air. Enclosed crawlspaces and unconditioned spaces represent environments that range from benign to hostile, depending on the ambient conditions in the space. Duct heat transfer to an unconditioned space can be significantly reduced if the surface area of the system is minimized. In this regard, research indicates that if the thermal envelope is efficient, an acceptable level of comfort is provided by an attic system that has a central air handler and short supply runs that feed diffusers located near the interior walls of the rooms. There are no duct loads when a duct system is installed within a conditioned space. The model used to generate the default duct factor tables applies to system designs that are compatible with the procedures documented in Manuals J, S and D. This is important because duct surface area estimates are based on the assumption that the blower CFM is compatible with the calculated loads and that the size of the duct airways are compatible with the blower performance and the total effective length of the duct system. In other words, the duct factor tables do not apply to heating and cooling systems that have been designed by whimsical guidelines and unreliable rules of thumb.
The North American Insulation Manufacturers Association (NAIMA). The Sheet Metal and Air Conditioning Contractors National Association (SMACNA). Underwriters Laboratories (UL-181 and UL-181A). Air Diffusion Council (ADC).
In some cases a duct sealing effort can create a health hazard that can cause discomfort, sickness or death. The most dangerous condition occurs when the sealing work creates a negative pressure condition that causes a combustion appliance to back draft. Other undesirable scenarios involve transfer of contaminated air from space to space, reduced ventilation rates and objectionable pressure conditions. Information about this subject is found in documents that pertain to duct testing and duct sealing. Also refer to the safety-test procedures in the appendices of ASHRAE Standard 62 and the National Fuel Gas Code.
428
Appendix 5
Indoor drybulb temperature for heating = 70F Indoor drybulb temperature for cooling = 75F Indoor relative humidity for a dry-coil (insignificant latent load) climate = 45% RH Preferred indoor relative humidity for a wet-coil (latent load climate) = 50% RH Acceptable indoor relative humidity for a large latent load application = 55% RH
An arrow or directional rosette that points north. A dimensioned outline of the floor plan for each level. The location of stairwells, partitions, chases and cavities. The length, width and height of every room with the room name. An alphanumeric code (WN-1, WN-2, etc.) next to each type of window or glass door. An alphanumeric code (S1, S2, etc.) next to each type of skylight. An alphanumeric code (DR-1, DR-2, etc.) next to each type of wood or metal door. An alphanumeric code (CL-1, WL-2, FL-1, etc.) next to each type of ceiling, wall or floor. Room assignments for occupants, appliances, lighting, plants and equipment.
or at the wall and ridge), the type of space that is above the ceiling (include detail that will help determine the temperature in enclosed, unconditioned spaces); the type of vapor retarder; the air leakage that might occur at hard-wired lighting fixtures and ceiling penetrations, and the quality of the sealing and caulking effort at the top plate. The use of a radiant barrier under an attic roof, or encapsulated foam attic (if applicable). Attic vent locations, vent areas and powered attic ventilation equipment. A record of the location, size and type of skylights (preferably, with a Manual J construction number). Wall construction detail (preferably with a Manual J construction number and overall R-value), wall heights, the type of space that is on the nonconditioned side of a partition (include detail that will help determine the temperature in enclosed, unconditioned spaces); the type of vapor retarder, the type of infiltration retarder, the potential for leakage around electrical outlets and wall penetrations, and the quality of the sealing and caulking effort at plates, headers, sills, band joists and rough openings. The location, type and size of the window and glassdoor assemblies and wood and metal door assemblies, with notes pertaining to U-values, SHGCs, construction details, bug screens, sun screens, projections and tightness. Internal and external shading devices and overhangs. The type of floor, floor construction details (preferably with a Manual J construction number and overall R-value), the type of space that is under the floor (include detail that will help determine the temperature in enclosed, unconditioned spaces); the type of vapor retarder, the leakage that might occur at floor penetrations, and the quality of the sealing and caulking effort. Observed pathways that connect the conditioned space with an attic space, stud space, chase, crawl space or basement. The location of the appliances, display lighting, ceiling fans, waterbeds or any equipment that generates internal loads. The location of vents and exhaust equipment, with observations pertaining to the use of back draft dampers. The location and type of combustion equipment and fireplaces, with notes pertaining to the source of combustion air, type of vent or chimney and the use of vent dampers.
The type of ceiling, ceiling construction detail (preferably with a Manual J construction number and overall R-value), the ceiling height (at the wall
The preceding list applies to load estimates, but there are other items that should be noted during the survey.
440
Appendix 5 (U-value and SHGC) for window assemblies and sliding glass door assemblies. Rated values are preferred because they eliminate uncertainty about window and glass door performance. When such information is not available, use the Table 2A values. Also record the following information:
n n n n n n
n n n
The direction the glass faces Type of window (see Figure A5-11) The number of lites (panes) in the assembly The type of glass used in the assembly The frame material Frame conduction path (thermal break or no thermal break) The use of a storm window The type and color of internal shading devices The shading coefficient of external shade screens (when applicable and available) The X and Y dimensions (see Table 3E-1) of external overhangs (when applicable)
Also evaluate the tightness of the window and door assemblies. Collect data pertaining to tested leakage ratings as listed in the manufacturers performance data, documented by the NFRC directory or displayed on a performance label. If quantitative information is not available, make notes that summarize the findings of a site inspection. Also try to evaluate the seal between the structural framing and the frame of the window or door assembly. Ceilings Ceiling performance depends on the type of construction (attic, roof-ceiling sandwich or ceiling on exposed beams) and the construction details associated with the ceiling assembly (or attic knee wall). Ceiling and attic knee wall performance is also depends on the temperature in the attic, which depends on the roofing material, the roof color, the use of a radiant barrier or encapsulating foam, and the amount of attic ventilation. Such observations are used to select a construction number (see Table 4A), to evaluate structural tightness and to estimate resistance to moisture migration. Record the following information:
n n n n n
In regard to opaque doors, record observations pertaining to style (see Figure A5-12), construction material (wood or metal) and insulation. If a door has a rating label, record the tested U-value.
n n n n n
n n
French Door
n n
Type of construction (attic, beamed or roof-ceiling) Size and type of framing Primary insulating material (type and R-value) Secondary insulating material Overall R-value of the attic-ceiling, partition-ceiling or roof-ceiling assembly Type of roofing material (shingles or tile with air space) Long-term roof color and texture Details pertaining to attic ventilation The use of radiant barrier in attic (when applicable) Description of an unconditioned space above a ceiling Secondary insulation (sheathing material and R-value) Type and quality of vapor retarder Sealing effort at seams, light fixtures and penetrations Sealing effort at partitions, wall cavities, chases and stair wells
Skylights For generic skylights, use qualitative observations and Table 2A to determine the U-value, SHGC value. Use Table 3C for the cooling HTM value.
Wood or Metal Panel Door
Table 3D (-1 through -4) procedures apply to all types of skylights. Always try to obtain the NFRC rating (U-value and SHGC) for skylight assemblies. Rated values are preferred because they eliminate uncertainty about window and glass door performance. When such information is not available, use the Table 2A values. Also record the following information:
Figure A5-12
446
Number of People
Table 8 OA Cfm
Type of Const.
Space ACH
AGV (CuFt)
Space ICFM
Fireplace ICFM
Total ICFM
(Note 1) (Note 2)
Table 8 OA CFM
Step 2, Option 2 Component Leakage Area Method Operating Mode HTD and CTD Wind Velocity (MPH) Table 5C ELA4 (SqIn) Table 5D Cs Shielding Class Cw ICFM Table 8 OA CFM Table 8 Vent CFM
Heating Cooling
Default heating season velocity = 15 MPH Default cooling season velocity = 7.5 MPH Detail from Worksheet E1 ICFM = ELA4 x ( Cs x TD + Cw x V2 ) 0.50 T8 vent CFM = T8 OA CFM - Cooling ICFM If cooling ICFMis greater than T8 OA CFM, the T8 vent CFM is zero.
Step 2, Option 3 Blower Door Method Operating Mode HTD and CTD Wind Velocity (MPH) Blower Door ELA4 Table 5D Cs Shielding Class Cw ICFM Table 8 OA-CFM Table 8 Vent-CFM
Heating Cooling
Default heating season velocity = 15 MPH Default cooling season velocity = 7.5 MPH Provided by field test ICFM = ELA4 x ( Cs x TD + Cw x V2 ) 0.50 T8 vent-CFM = T8 OA CFM - Cooling ICFM If cooling ICFMis greater than T8 OA CFM, the T8 vent CFM is zero.
Step 3 Infiltration Loads on Central Equipment Type of Load Heat Load Sens Load Lat Load
The room infiltration load equals the load on the central equipment multiplied by the gross wall area ratio (WAR). WAR = Gross room wall area / Gross wall area for all rooms served by the central equipment
Exhaust CFM
CFMimb
The sign in the NCFM equation is determined by the sign of the Heat Load = 1.1 x ACF x NCFM x HTD CFMimb Sensible Load = 1.1 x ACF x NCFM x CTD value. Latent Load = 0.68 x ACF x NCFM x Grains
496
Appendix 12 eight-hour period beginning at 11 am and ending at 7 pm, standard time. This aggregate value is used for all roof-ceiling construction, regardless of exposure direction or time of day. ASHRAE Base-Case CLTD Values for Ceilings
(8 Hour Average) Group Construction 1" wood, 1" Insulation 1" wood, 2" Insulation 2-1/2" wood, 1" Insulation 2-1/2" wood, 2" Insulation 4" wood, 2" Insulation Roof Deck On Beams 66 55 39 35 27 Roof-Ceiling Sandwich 50 45 31 30 27
These averaging rules are applied to five types of wood deck roofs (ASHRAE Group 2, 5, 7, 10 and 13). The resulting collection of 8-hour averages are summarized by Figure A12 -13. (This figure lists base-case CLTD values, which means they are compatible with a 20 oF temperature difference and a medium daily range.) The HTM value for a specific type of construction is obtained by multiplying the appropriate CLTD value by the panel U-value:
HTMpanel = CLTD x Uceiling
5 7 10 13
1)
Figure A12-13
Ceiling Under Attic The cooling load temperature difference for an attic ceiling panel depends on the attic temperature, which depends on the amount of insulation above the ceiling, the amount of attic ventilation, the use of a radiant barrier, encapsulating foam, attic fan, or extra attic vent area, and the type of roofing. Since the absorptivity and emittance of roofing products may not be known, roofing is classified by material (asphalt shingles, wood shakes, tile, slate, concrete, metal, membrane or tar and gravel) and color. The attic temperature also is affected by attic duct runs, but the temperature moderating effect is conditional, so it is (conservatively) ignored. Figure A12-14 (next page) summarizes the attic temperatures used to generate CLTD values for ceilings under an attic. These values are for the peak (late afternoon) load condition. They are used to estimate ceiling loads for all Manual J applications. Ceiling on Exposed Beams The cooling load temperature difference for a ceiling on exposed beams depends on the type of deck material, the thickness of the decking, the amount of insulation in the deck sandwich, the type of roofing and color. Figure A12-15 (ahead two pages) summarizes the base case CLTD values for deck-on-beam construction. These values represent the average ceiling load condition that occurs during the afternoon. They are used to estimate ceiling loads for all Manual J applications. Roof-Joist-Ceiling Sandwich T h e co o l i n g l o a d te m p e r a t u r e d i f f e r e n c e f o r roof-joist-ceiling sandwich depends on the type of deck material, the thickness of the decking, amount of insulation on the deck, the amount of insulation in the joist space, the ceiling material, the type of roofing and color. Figure A12-16 (ahead two pages) summarizes the base
case CLTD values for this type of construction. These values represent the average ceiling load condition that occurs during the afternoon. They are used to estimate ceiling loads for all Manual J applications.
The heat transfer through below grade walls and the crawl space floor is ignored. Crawl space duct runs do not produce a regain effect. The floor area of a tight crawl space is 4 times larger than the crawl space wall area exposed to the outdoor air (assume the crawl space floor has a 2:1 aspect ratio and that it has three feet of exposed wall height). For tight construction, the conductive heat flow through the crawl space ceiling equals the conductive heat flow through the crawl space walls, as indicated here:
(U x A x TD)ceiling = (U x A x TD)wall
A loose or vented crawl space has 500 square feet of wall exposed to the outdoor air and 2,000 square feet of floor area.
522