Sie sind auf Seite 1von 2

Basic Model 1030FDH1250

Test Report No. H-S1000439

Date: 05/25/11

TYPICAL SUBMITTAL DATA


Kilowatt ratings at kW (kVA) 1500 RPM 3 Phase Class B 80 C Continuous 1830 (2288) 50 Hertz 0.8 Power Factor 105 C Continuous 2110 (2638) 6 Leads w/ 4 Bus Bars Dripproof or Open Enclosure Class F 130 C Standby 2270 (2838)

Voltage* 10500Y/6062

Rise by resistance method, per IEEE 115.

Submittal Data: 10,500 Volts, 2838 kVA, 1500 RPM, 50 Hz, 3 Phase Mil-Std-705B Mil-Std-705B Value Method Description Value Method Description 301.1b Insulation Resistance > 10 Meg --Overspeed 1875 RPM 302.1a High Potential Test 507.1c Phase Sequence CCW-ODE ABC Main Stator 22,000 Vac --Voltage Balance, L-L or L-N 0.2% Main Rotor 1500 Vac --L-L Harmonic Maximum - Total 5.0% Exciter Stator 1500 Vac (Distortion Factor) Exciter Rotor 1500 Vac --L-L Harmonic Maximum - Single 3.0% --Stator Resistance, Line to Line --Deviation Factor 5.0% High Wye Connection 0.6232 Ohms --TIF (1960 Weightings) <50 --Rotor Resistance 0.7064 Ohms --Mechanical Strength (Sustained --Exciter Stator 19.5 Ohms 3 Phase Short Circuit Current) >250% --Exciter Rotor 0.044 Ohms --PMG Stator 2.1 Ohms --No Load Exciter Field Amps at 10500 Volts Line to Line 0.74 A DC --Short Circuit Ratio 0.492 Additional Prototype Data --Xd Synchronous Reactance 2.565 pu --X2 Negative Sequence Reactance 0.336 pu -Generator Frame 1030 --X0 Zero Sequence Reactance 0.039 pu -Type Ext. Voltage Regulated, Brushless --X'd Transient Reactance 0.242 pu -Insulation Class F --X''d Subtransient Reactance 0.222 pu -Bearings Double --T'd Transient Short Circuit -Amortisseur Windings Full Time Constant 0.336 sec. -Cooling Air Volume 6250 CFM --T''d Subtransient Short Circuit -Exciter Rotating Time Constant 0.042 sec. -Voltage Regulator DVR2000E+ --T'do Transient Open Circuit -Voltage Regulation 0.25% Time Constant 2.907 sec. -Sensing 1 or 3 Phase --Ta Short Circuit Time Constant of Armature Winding 0.067 sec.
* Voltage refers to wye (star) connection, unless otherwise specified.

www.marathonelectric.com

Date: 07/08/11

Basic Model 1030FDH1250

Test Report No. H-S1000439

TYPICAL DYNAMIC CHARACTERISTICS


50 HERTZ
Recovery Time (Sec.) 1 Recovery Time (Sec.) 1

LOAD APPLICATION
30 20 10 0 0 500 1000 1500 2000 2500 kW at 0.8 Power Factor 40.0 10.5 kV 30.0 % Voltage Dip % Voltage Rise 10.5 kV % Voltage Dip 30 10.5 kV 20 10 0 0 500

LOAD REJECTION

1000

1500

2000

2500

kW at 0.8 Power Factor

TYPICAL MOTOR STARTING CHARACTERISTICS

20.0

10.0

0.0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 Locked Rotor kVA

TYPICAL GENERATOR EFFICIENCY


100 10.5 kV % Efficiency % Efficiency 100 10.5 kV

95 0.8 pf 90 500

95 1.0 pf 90 500

1000

1500 2000 kW Output

2500

3000

1000

1500 2000 kW Output

2500

3000

Voltage refers to wye (star) connection, unless otherwise specified.