MTTF* prediction for Anybus X-gateway Modbus-TCP


Simulation method: Simulation environment: Simulation temperature: Simulation duty cycle: Simulation software: Telcordia Issue 2, Method 1 Case 3 Ground, Fixed, Controlled 30 C 100 % ReliaSoft Lambda Predict 3, 3.1.1

Remarks: Only electrical components included in the calculation. Discrete components estimated to quality level 1, connectors to level 0. Predicted failure intensity only valid after running-in period. Components normally not mounted are included in the calculation. FIT rates from manufacturers used where available.

Part number AB9000-B AB9001-B AB9002-B AB9003-B AB9004-B AB9005-B AB9006-B AB9007-B AB9008-B AB9009-B

Description; Modbus-TCP to EtherCAT PROFIBUS DeviceNet ControlNet CANopen Modbus-RTU EtherNet/IP PROFINET IO Modbus-TCP CC-Link

MTTF* value; hours 544 000h 1 034 000h 655 000h 742 000h 755 000h [missing] 811 000h 811 000h 811 000h 609 000h

* Note: MTTF = Mean Time To Failure Definition: Estimation of average time to failures with the modeling assumption that the failed system is not repaired (infinite repair rate).
HMS Industrial Networks March 13th 2012 Martin Falkman
Product Line Manager Gateways