Consortium GTC/5/2004

GTC/5/2004 Qatar Power Transmission System Expansion Phase VI (Substations)

Clarification to EFC Letter Ref. No. : EFC-SIE/Ph6/DTA/06/1262


SIE-GTC 5/DTS/COM/1537 dated 02/08/2006 (General - 66kV cable):
Item No.
1.

Document No.
05-4/00/SIE/36/3039

Rev. 0

KAHRAMAA Comments
1.

Description:
Type test procedure for 66kV 1x500mm2 XLPE Cable and accessories

Consortium Reply

Accessories
1 .Please provide description and procedure of tests for joints,(Annex
H of IEC 60840) .

Please find enclosed revised document No. 05-4/00/SIE/36/3039 Rev. 1 Type


test procedure for 66kV 1x500mm2 XLPE Cable and accessories including
description and procedure of tests for joints, as per IEC 60840, annex H.

Explain why Test of outer protection of buried joint in planned after


completion of other type tests, it should be during the four days of the
final tests.

Explanation: As per proposed scheme, we have considered the tests on outer


protection of joint from the joint which have undergone all the electrical tests
(SR No. 1.4 1.10 of 4.1) of Type Test Schedule. The joint will be cut from
the test loop after the above tests and then further, the test as mentioned on
S.R. 4.2 3. DC Voltage Test will be conducted.
Depending on actual situation at the time of the test, as mentioned above,
based on the provision as per IEC 60840, annex H (Clause H.2), if we use a
separate joint for the test, then the time gaps for the test will be further
reduced.

2. Approved drawings (min A1 size) and installation manuals for cable


accessories shall be included.

Please find enclosed the following documents (Drawings A1 size):


05-4-00-SIE-18-4021 Straight Through Joint for 1C x 500 Sq mm Cable
05-4/00/SIE/18/4040 Elastimold Joints - Installation Instructions TCJQ

66 kV Cables clarification to EFC DTA 1262 dated 21-08-2006

Page 1 of 2

12-09-2006

Consortium GTC/5/2004
05-4/00/SIE/18/4025 66kV Outdoor Sealing End
05-4/00/SIE/18/4037 Termination, Outdoor Field Filled 138 kV, Brown,
3540mm Nom. Creepage Porc. for Extruded Cables
05-4/00/SIE/18/4038 Installation Instructions for 66 kV Outdoor Sealing End
05-4/00/SIE/36/0049 CONNEX Cable Termination System Size 4
05-4/00/SIE/36/0050 CONNEX Cable Termination System Size 5-S
05-4/00/SIE/36/0051 Instructions for the installation of HV-CONNEX bushings
Size 5S
05-4/00/SIE/36/0052 Operating Instructions CONNEX Separable Connectors
Size 4
05-4/00/SIE/36/0053 Operating Instructions CONNEX Separable Connectors
Size 5-S
3. CV for third party inspector shall be provided for KM review and
approval.

66 kV Cables clarification to EFC DTA 1262 dated 21-08-2006

Page 2 of 2

CV for third party inspector was already sent, please referrer to letter No
887dated 10.09.2006

12-09-2006