Sie sind auf Seite 1von 2

HEAVY DUTY PORTABLE AIR COOLED CHILLER MODEL PY-300 Nominal Tons 315.

STANDARD FEATURES
Compact rugged steel transport frame Fork lift tubes and tie-down eyes Top mounted 4 point lifting lugs Industrial grade chiller suitable for commercial or process cooling duty Three screw compressors with independent refrigerant circuits Chilled liquid settings from 15-50F Victaulic water connections, 6 Automatic air vents Single point drain and fill connections Differential pressure gauge with flow safety interlock Unit mounted capacity and flow charts Twist-lock connections for main power Enclosed main power breaker with lockable external handle Pump power output connection, 460/60/3 Shore power input connection, 115/60/1 Complete DDC control center Chilled water pump interface for automatic operation Push-to-Test phase rotation indicator Network compatible controls interface

ELECTRICAL REQUIREMENTS
Main Power Breaker Range (Chiller Only): 700 Amps Min., 800 Amps Max. With 50 HP Pump: 765 Amps Min., 800 Amps Max. With 60 HP Pump: 791 Amps Min., 800 Amps Max. Overall Length 34-6, Width 8-3, Height 9-0 Approximate Shipping Weight 29,800 lbs., Operating Weight 31,900 lbs.

HEAVY DUTY PORTABLE AIR COOLED CHILLER MODEL PY-300 Nominal Tons 315.5
CAPACITY
400

350
75 85 95 105 115

CAPACITY (TONS)

300

250

Ambient Air F

200

150
Use 10% Glycol Use 15% Glycol Use 20% Glycol
Use 25% Glycol Use 30% Glycol

100

50

45

40

35

30

25

20

15

LEAVING WATER TEMP F (10F RISE) PRESSURE DROP


16
Minimum Flow: 255 GPM (1.7 PSI)

PRESSURE DROP (PSI)

14 12 10 8 6 4 2

Nominal Flow: 756 GPM (12.2 PSI) Maximum Flow: 800 GPM (13.5 PSI)

Nom. GPM

0 250

300

350

400

450

500

550

600

650

700

750

800
www.CAT-ElectricPower.com 2003 Caterpillar All rights reserved. Printed in U.S.A.

GALLONS PER MINUTE (GPM)

LEHE3442 (11-03)

Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication.