DETALLE HUMIDIFICADOR Y CALENTADOR DE AIRE


FECHA: ELABORADO: REVISADO: APROBADO: 21 de enero de 2014

HUMIDIFICADOR / CALENTADOR ELCTRICO

HUMIDIFIER SELECTION DESIGN LEVEL SPACE SUPPLY @CFM 750 T c HR % (2) R2 (gr/pie3) DB 45 (1) WEATHER CONDITIONS (F) WINTER SUMMER WB 36.4 POWER INPUT (kW) (3) R1 (gr/pie3) 1.652 STEAM OUTPUT (lbs/hr) DB 72 NOMINAL AMPS WB 54 CIRCUIT BREAKER 30 FAN INTERLOCK OK

10.50

Area de Animales (4) HUMIDIFICATION LOAD (lbs/hr)

18 +/- 2 50 3.605 HUMIDIFICADOR DUCT (in) MODEL

HUMIDIFICATION

V/F/f

WIDTH 16 WATER SOURCE TEP WATER

HEIGHT

FPM

ELECTRIC 12.56 NON-WETTABLE VAPOR DISTANCE AVAILABLE (ft) 3

10 750 HC-6100 240/3/60 9 MAXIMUM ALLOWABLE AIR PRESSURE DROP (in. wc.) 0.2 ELECTRIC DUCT HEATER

27.00 22 DUCT HIGH - LIMIT HUMIDISTAT OK

BTU/H 16500

CALETADOR ELECTRICO - WARREN TECNOLOGYS CARGA LATENTE Kw 4.84

MODELO SL5A

(1): Tomado de HAP 4.7, Hourly Analysis Program de CARRIER (2): Moisture content of required indoor condition air in gr/ft3 (3): Moisture content of air to be humidified (From outdoor condition) in gr/ft3 (4): Humidification Load, ARMSTRONG

PROYECTO
DETALLE HUMIDIFICADOR Y CALENTADOR DE AIRE
FECHA: ELABORADO: REVISADO: APROBADO: 16 de enero de 2014

HUMIDIFICADOR / CALENTADOR ELCTRICO

HUMIDIFIER SELECTION DESIGN LEVEL SPACE SUPPLY @CFM 200 T c HR % (2) R2 (gr/pie3) DB 45 (1) WEATHER CONDITIONS (F) WINTER SUMMER WB 36.4 POWER INPUT (kW) (3) R1 (gr/pie3) 1.652 STEAM OUTPUT (lbs/hr) DB 72 NOMINAL AMPS WB 54 CIRCUIT BREAKER 15 FAN INTERLOCK OK

10.50

Area de Animales (4) HUMIDIFICATION LOAD (lbs/hr)

22 +/- 2 80 5.258 HUMIDIFICADOR DUCT (in) MODEL

HUMIDIFICATION

V/F/f

WIDTH 8 WATER SOURCE TEP WATER

HEIGHT

FPM

ELECTRIC 6.18 NON-WETTABLE VAPOR DISTANCE AVAILABLE (ft) 3

8 500 HC-6100 208/3/60 3 MAXIMUM ALLOWABLE AIR PRESSURE DROP (in. wc.) 0.2 ELECTRIC DUCT HEATER

8.30 7.7 DUCT HIGH - LIMIT HUMIDISTAT OK

BTU/H 5720

CALETADOR ELECTRICO - WARREN TECNOLOGYS CARGA LATENTE Kw 1.68

ETAPAS 3

(1): Tomado de HAP 4.7, Hourly Analysis Program de CARRIER (2): Moisture content of required indoor condition air in gr/ft3 (3): Moisture content of air to be humidified (From outdoor condition) in gr/ft3 (4): Humidification Load, ARMSTRONG

PROYECTO
DETALLE HUMIDIFICADOR Y CALENTADOR DE AIRE
FECHA: ELABORADO: REVISADO: APROBADO: 16 de enero de 2014

HUMIDIFICADOR / CALENTADOR ELCTRICO

HUMIDIFIER SELECTION DESIGN LEVEL SPACE SUPPLY @CFM 200 T c HR % (2) R2 (gr/pie3) DB 45 (1) WEATHER CONDITIONS (F) WINTER SUMMER WB 36.4 POWER INPUT (kW) (3) R1 (gr/pie3) 1.652 STEAM OUTPUT (lbs/hr) DB 72 NOMINAL AMPS WB 54 CIRCUIT BREAKER 30 FAN INTERLOCK OK

10.50

Area de Animales (4) HUMIDIFICATION LOAD (lbs/hr)

33 +/- 2 80 14.2722 HUMIDIFICADOR DUCT (in) MODEL

HUMIDIFICATION

V/F/f

WIDTH 8 WATER SOURCE TEP WATER

HEIGHT

FPM

ELECTRIC 21.63 NON-WETTABLE VAPOR DISTANCE AVAILABLE (ft) 3

8 500 HC-6100 240/3/60 9 MAXIMUM ALLOWABLE AIR PRESSURE DROP (in. wc.) 0.2 ELECTRIC DUCT HEATER

27.00 22 DUCT HIGH - LIMIT HUMIDISTAT OK

BTU/H 10120

CALETADOR ELECTRICO - WARREN TECNOLOGYS CARGA LATENTE Kw 2.97

MODELO SL5A

(1): Tomado de HAP 4.7, Hourly Analysis Program de CARRIER (2): Moisture content of required indoor condition air in gr/ft3 (3): Moisture content of air to be humidified (From outdoor condition) in gr/ft3 (4): Humidification Load, ARMSTRONG

Das könnte Ihnen auch gefallen