FEATURES
State of Art Microcontroller Based Design.
R Y B N R Y B KA
V A
Super bright LED display for crystal clear long distance day light viewing All CT ratios user Programmable through front Key Pad. Built in Transducer Compact Size Four Digit Frequency Meter.
Hz
P
3P4W
2
50 60Hz
KAM-83
PARAMETERS
Volts : R-Y Voltage Y-B Voltage B-R Voltage R-N Voltage Y-N Voltage B-N Voltage : R Phase Y Phase B Phase : System
ADVANTAGES
Reduce Panel Space, Wiring , Installation Time Scale User adjustable reduces inventory
APPLICATION
Control Panel Distribution Systems Generator Sets Motor Control Test Bench
Amps
Frequency
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input Current Input Burden on CT Temp Humidity Weight : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V 110VAC 50Hz (-20% +15%) : < 4 VA : 110 / 415 / 440 VAC ( L - L )500Vmax : 1 Amps / 5 Amps : < 0.2 VA : 0 - 55 C : < 90% RH ( non condensing) : 500 gms Accuracy : Voltage : 0.5 % of FS + 2 Digit Current : 0.5 % of FS + 2 Digit Frequency : + 0.02 Hz Resolution: Volts Hz Amps : 1V : 0.01 Hz : 0 - 99 : 0.1 A 100 - 999 : 1A > 1000 : 0.01 KA Dimension : 96 x 96mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm
FAV+ Meter
KAM 83M
R V Avg
FEATURES
V I1 I
Y I Avg
B L-L
I2 Hz
V Avg I Avg OL
S I UV OV PR
I3
P
3P4W
2
KA
50 60Hz
KAM-83M
POWER ANALYZER
FEATURES
State of Art Microcontroller Based Design. 4 Line Ultra Bright Red LED display to show phase
W VA VAh
Wh YAr
VArh L1 L2 L3
Site Programmable CT & PT Ratio. True RMS measurement. Auto Scrolling Facility. Password protection
EEprom retains Energy Parameters on power fail. Monitors Import & Export Energy. Computer Interface ( RS 485) Pulse Output for PLC / SCADA interface Optional: Data Logging of all Parameters with Date & Time
P
3P4W
2
50 60Hz
KM-161
PARAMETERS
Volts Amps Frequency Power Factor KW KVA KVAr KWh KVArh KVAh : L - L, L - N ( Per Phase & Avg.) : Per Phase & summation : System : Per Phase & Avg : Per Phase & Summation : Per Phase & Summation : Per Phase & Summation : Import, Export & Summation : Capacitive & Inductive : Total
ADVANTAGES
To caution on the Extra Energy Consumption To indentify inefficiency of Machine / Man Reduce Panel Space, Wiring , Installation Time Scale User adjustable reduces inventory
APPLICATION
Control Panel Distribution Systems Generator Sets Motor Control Test Bench APFC Panel Energy Management Process Control & SCADA
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input Current Input Burden on CT Communication Temp Humidity Weight : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V / 110 VAC 50Hz (-20% +15%) : < 4 VA : 110 / 415 / 440 VAC ( L - L )500Vmax : 1 Amps / 5 Amps : < 0.2 VA : RS485 (Modbus - RTU Protocol) 9600 baud : 0 - 55 C < 90% RH ( non condensing) : 700 gms Accuracy : Voltage Current Active Power Reactive Power Apparent Power Power Factor Active Energy Reactive Energy Frequency : 0.5 % of F.S. + 2 Digit : 0.5 % of F.S. + 2 Digit : Class1.0 IEC 61036 : Class1.0 IEC 61036 : Class1.0 IEC 61036 : + 1 Electrical : Class1.0 IEC 61036 : Class1.0 IEC 61268 : + 0.2 Hz
Pulse Output for PLC / SCADA interface Optional: Data Logging of all Parameters with Date & Time stamp ( site programmable logging time interval).
3P4W
P
50 60Hz
KM-161P
PARAMETERS
Volts Amps Frequency Power Factor KW KVA KVAr KWh KVArh KVAh THD Max. Demand : L - L, L - N ( Per Phase & Avg.) : Per Phase & summation : System : Per Phase & Avg : Per Phase & Summation : Per Phase & Summation : Per Phase & Summation : Import, Export & Summation : Capacitive & Inductive : Total : Volts & Amps : KVA / KW
ADVANTAGES
To caution on the Extra Energy Consumption To indentify inefficiency of Machine / Man Reduce Panel Space, Wiring , Installation Time Scale User adjustable reduces inventory
APPLICATION
Control Panel Distribution Systems Generator Sets Motor Control Test Bench APFC Panel Energy Management Process Control & SCADA
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input Current Input Burden on CT Communication Temp Humidity Weight : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V / 110 VAC 50Hz (-20% +15%) : < 4 VA : 110 / 415 / 440 VAC ( L - L )500Vmax : 1 Amps / 5 Amps : < 0.2 VA : RS485 (Modbus - RTU Protocol) 9600 baud : 0 - 55 C : < 90% RH ( non condensing) : 700 gms Accuracy : Voltage Current Active Power Reactive Power Apparent Power Power Factor Active Energy Reactive Energy Frequency : 0.5 % : 0.5 % : Class1.0 IEC 61036 : Class1.0 IEC 61036 : Class1.0 IEC 61036 : + 1 Electrical : Class1.0 IEC 61036 : Class1.0 IEC 61036 : + 0.2 Hz
Energy Meter
Kwh
P
REV
3P4W
z 50 60H
KM-34L
Energy Meter
FEATURES
State of Art Microcontroller Based Design. 6 Digit Ultra Bright Red LED Display for Clear long distance day light viewing
INT
KWh
Pulse Output for PLC / SCADA interface Reverse indication for wrong wiring polarity
3P4W
50 60Hz
KM-513
ADVANTAGES
Energy Management System To caution on the Extra Energy Consumption CT Ratio Site Programmable reduces inventory
APPLICATION
Energy Audit Control Panel Distribution Systems Generator Sets
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input Current Input Burden on CT Temp Pulse Width : 3 Phase 4 Wire / 3 Phase 3 wire : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 110 / 415 / 440 VAC ( L - L ) 500 V max : 1 Amps / 5 Amps ( Flush Model) : < 0.2 VA : 0 - 55 C : 400 msec. + 50 msec. Humidity : < 90% RH ( non condensing) Accuracy : Class1.0 IEC 61036 Dimension :Bezzel: 96 x 96mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm Weight :500 gms Resolution : 1Amps / 5 Amps 5A - 50 A 50A - 500A > 500 Amps : 0.01 & above : 0.1 & above : 1 & above : 10
All CT Ratio Site Programmable. True RMS measurement. Direct 60 Amps. (continuos) Din rail enclosure Password protection
REV
KWh
Computer Interface ( RS 485) Pulse Output for PLC / SCADA interface EEprom retains Energy Parameters on power fail. Reverse Indication for wrong wiring polarity Optional
P
3P4W
2
50 60Hz
KM-513P
Dual Source Energy Meter with individual Energy Registering Counters for Source1 & Source 2
APPLICATION
Energy Audit Control Panel Distribution Systems Generator Sets
ADVANTAGES
Energy Management System To caution on the Extra Energy Consumption To indentify in efficiency of Machine / Man Power Billing.
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input Current Input Burden on CT Temp Humidity Accuracy Communication Pulse Width : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 415 / 440 VAC ( L - L ) 500 V max : 1 Amps / 5 Amps ( Flush Model) : 60 Amps. Direct continuos ( Din Model) : < 0.2 VA : 0 - 55 C : < 90% RH ( non condensing) : Class1.0 IEC 61036 : RS485 ( Modbus - RTU Protocol )9600 baud :400 msec. + 50 msec. Dimension : Flush Model: Weight : 550 gms Dim.: Bezzel : 96 x 96mm Depth (behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm Din Model: Weight : 800 gms Dim.: Size : 150 x 72 mm (L x B) Height (From wall) : 115 mm Base :35 mm Rail / 2 x m4Screw Resolution: 1Amps / 5 Amps : 0.01 < 50 Amps : 0.1 < 500 Amps :1
Energy Meter
ON
000
Kwh
REV
3P4W
z 50 60H
KM-34
LED indication for Reverse Connection Power On LED ( flashing ) for Meter Healthyness LED indication for Energy Consumption Pulse output Standard feature Self Power Supply , Aux. Sup. 115 V AC / 230 V AC
KWh
Rev
Earth
1P
TRUE
50...60Hz
RMS
KM-1513C
SPECIFICATION
System Voltage : 1 Phase 2 wire : 230 V AC (P - N ).
PRODUCT DESCRIPTION
Kam Electronic Energy Meter is designed with precision IC's to compute active energy consumption of the load at any power factor under balanced or unbalanced condition. The meter is designed to accept Voltage & Current input directly, ( 415 V AC L-L) and 60 Amps. (max) respectively. No need to have any Multiplication Factor and direct energy consumption record is available with 0.1 resolution.
Current Burden : 0.2 VA max. Frequency Display Accuracy : 50 - 60 Hz : Electro Mech. Counter (6+1 Dgt.) : Class 1 ( EN61036)
LED Indication : A) Power ON B) Cal. / Int. C) Reverse Polarity Housing Dimension Mounting : ABS Material : 105 x 90 x 95 mm ( L x W x H) : Din Rail ( 35 mm Rail )
ON
KWh
Cal
Rev
TRUE
RMS
3P4W
50...60Hz
SPECIFICATION
System Voltage : Three Phase, Unbalanced Load : 415 V AC ( L - L ). Display Accuracy Pulse Output Pulse Width Housing Dimension Mounting
KM-3513C
: Electro Mech. Counter (6+1 Dgt.) : Class 1 ( EN61036) : Opto Isolated; : 400 m Sec. : ABS Material :105 x 90 x 95 mm ( L x W x H) : Din Rail ( 35 mm Rail )
Built in Solid state selector switch for phase selection Super bright LED display for crystal clear long distance day light viewing Built in Transducer True RMS measurement
Y B
COS
3P4W
50 60Hz
KM-166
PARAMETERS
Power Factor: R Phase Y Phase B Phase System
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input Current Input Burden on CT Temp Humidity : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V /110VAC 50Hz (-20% + 15%) : < 3 VA Accuracy : + 1 Electrical Resolution : 0 .01 count
: 110 / 415 / 440 VAC ( L - L )500Vmax Dimension : Bezzel: 96 x 96mm : 1 Amps / 5 Amps Depth ( behind bezzel) : 80 : < 0.2 VA mm Panel Cut out : 92 x 92 mm : 0 - 55 C : < 90% RH ( non condensing) Weight : 500 gms
Watt Meter
FEATURES
State of Art Microcontroller Based Design. Built in Solid state selector switch for phase selection Super bright LED display for crystal clear long distance day light viewing All CT ratios user Programmable through front keypad Built in Transducer True RMS measurement
P
SYS
R Y B
KW
KM-2313
3P4W
50 60Hz
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input )500Vmax Current Input Burden on CT Temp Humidity : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V /110VAC 50Hz (-20% +15%) : < 3 VA : 110 / 415 / 440 VAC ( L - L : 1 Amps / 5 Amps : < 0.2 VA : 0 - 55 C : < 90% RH ( non condensing) Accuracy : Class 1.0 IEC 61036 Dimension : Bezzel : 96 x 96mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm Weight : 500 gms Resolution: 1A - 10A : 0.001KW 11A - 100A : 0.01 KW 101A - 1000A : 0.1 KW 1001A - 9999A : 1 KW
PARAMETERS
Watts: R Phase Y Phase B Phase System
10
light viewing All CT ratios user Programmable through front Key Pad
KW R Y B SYS
P
3P4W
2
ADVANTAGES
Reduce Panel Space, Wiring , Installation Time
50 60Hz
KM-1623
PARAMETERS
Power Factor : R Phase Y Phase B Phase System : R Phase Y Phase B Phase System
APPLICATION
Control Panel Distribution Systems Generator Sets Test Bench
Watts
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input Current Input Burden on CT Temp Humidity Weight : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V / 110VAC 50Hz (-20% + 15%) : < 4 VA : 110 / 415 / 440 VAC ( L - L )500Vmax : 1 Amps / 5 Amps : < 0.2 VA : 0 - 55 C : < 90% RH ( non condensing) : 500 gms Resolution : Power Factor Watts 0.001KW : 0.01 : 1A - 10A 11A - 100A 101A - 1000A : 0.01 KW : 0.1 KW : Dimension : Bezzel: 96 x 96mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm Accuracy : Power Factor Watts : + 1 Electrical : Class 1.0 IEC 61036
11
V
1P
1
V
50 60Hz
1P
50 60Hz
KM-122
Ranges
DC mV : 0 - 200 mV DC V : 0 - 2 / 20 / 200V
SPECIFICATION
System Aux. Supply +15%) Burden on Aux. Voltage Input Temp Humidity Accuracy Weight : 1 Phase : 230V / 110VAC 50Hz (-20% : < 3 VA : See Range : 0 - 55 C : < 90% RH ( non condensing) : 0.5 % of FS + 2 Digit : 350 gms Dimension : 96 x 96 Model: Bezzel : 96 x 96 mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm 48 x 96 Model: Bezzel: 48 x 96 mm Depth ( behind bezzel) : 80 mm Panel Cut out : 44 x 92 mm
1 Phase Ammeter
FEATURES
3 1/2 Digit - Dual Slope A/D Conversion Super bright LED display for crystal clear long distance day light viewing Built in Transducer compact size
1P
1
A A
1P
2
50 60Hz
50 60Hz
KM-011
SPECIFICATION
System Aux. Supply Burden on Aux. Current Input Temp Humidity Accuracy Weight : 1 Phase : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : See Range : 0 - 55 C : < 90% RH ( non condensing) : 0.5 % of FS + 2 Digit : 350 gms. 48 x 96 Model: Bezzel: 48 x 96 mm Depth ( behind bezzel) : 80 mm Panel Cut out : 44 x 92 mm Dimension : 96 x 96 Model: Bezzel: 96 x 96 mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm
Ranges
DC mA : 0 - 200 mA 4 - 20 mA DC A : 0 - 2 / 20 A
AC mA : 0 - 200 mA AC A : 0 - 2 / 20 A
12
Built in Solid state selector switch for phase selection Super bright LED display for crystal clear long distance day light viewing Built in Transducer Compact size
V
3P4W
50 60Hz
KM-322
PARAMETERS
Volts: R-Y Voltage Y-B Voltage B-R Voltage R - N Voltage Y - N Voltage B - N Voltage
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input )500Vmax Temp Humidity : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 110 / 415 / 440 VAC ( L - L : 0 - 55 C : < 90% RH ( non condensing) Weight : 400 gms Accuracy : 0.5 % of F.S. + 2 Digit Resolution : 1 Volt Dimension : Bezzel: 96 x 96mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm
3 Phase Ammeter
FEATURES
State of Art Microcontroller Based Design. Built in Solid state selector switch for phase selection Super bright LED display for crystal clear long distance day light viewing All CT ratios user Programmable, reduces inventory Built in Transducer Auto Ranging
3P4W
2
R Y B KA
A
50 60Hz
KM-031
SPECIFICATION
System Aux. Supply Burden on Aux. Current Input Burden on CT Temp Humidity Accuracy : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V 110VAC 50Hz (-20% +15%) : < 3 VA : 1 Amps / 5 Amps : < 0.2 VA : 0 - 55 C : < 90% RH ( non condensing) : 0.5% of F.S. + 2 Digit Dimension : Bezzel : 96 x 96mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm Weight : 450 gms
PARAMETERS
Amps: R Phase Y Phase B Phase
13
Frequency Meter
FEATURES
State of Art Microcontroller Based Design.
Hi
Super Bright Red LED Display for Clear long distance day light viewing Four Digit Read out with 0.01 Resolution Built in Transducer Optional A) With High / Low Frequency Cutoff B) With High & Low Frequency Cutoff
P
Low
Hz
Hysterisis, Delay & Set point site selectable through front Keypad
KM-613P
APPLICATION
Automatic Mains Failure Panel Control Panel Distribution Systems Generator Sets
ADVANTAGES
To caution on the Frequency Level To indentify the faulty Generator To protect Motors & other Electrical & Electronic Equipments.
Hz
KM-613
SPECIFICATION
Aux. Supply Burden on Aux. Voltage Input Weight Temp Humidity Accuracy : 230V /110VAC 50Hz (-20% +15%) : < 3 VA : 30 - 500 VAC : 450 gms : 0 - 55 C : < 90% RH ( non condensing) : + 0 .02 Hz For Relay Output: Relay status : Energise on Trip Delay : 0.1 Sec. to 9.9 Sec. Hysterisis : 0.1 Hz to 3 Hz Relay contact : 6A / 230V AC / 28 VDC Resolution Dimension : 0.01 Hz :Bezzel: 96 x 96mm Depth ( behind bezzel) : 80 mm Panel Cut out : 92 x 92 mm
14
PVAF METER
KW v Hz
P
3P4W
2
50 60Hz
KM-1215
15
R1
R2
PV
SV
SET
KM-209
ADVANTAGES
APPLICATION
KAM 100T
SET
KM-2019
SPECIFICATION
KAM KAM
16
Process Indicator
KM-169
Counter
KM-003
17
75
n % lD
60
0.6 1 2.5 5 10 0.25 0.5
45
10
20
n % lD TAIP
0.5 1 3
30 5
30
0.1
0.03
n(A) lD
0.15 0.06 0
ON
0.3
t(S) D
e Earth L Relay
TEST
a ka g e
RESET
KM-512R(PS)
Fixed ELR
KM-512R (F)
18
FEATURES
State of Art Microcontroller Based Design Bar Graph display to indicate Leakage Current in percentage Consistent reliability with high accuracy Trip setting through Dip Switch selection Time Delay setting through Dip Switch selection Power ON indication for system Healthiness. Front Panel Sealing for Tamper proof. Alarm Relay at 50% of set Range to caution on Leakage current.
Sensitivity Ranges
Model 1 : Range : 30mA, 100mA,300mA, 500mA, 1 A & 3A Model 2 : Range : 1A, 2A, 3A, 5A, 7.5 A & 10 Amps. Also user specified Ranges
APPLICATION
Protection : Control Panel Feeder / motor Generator Transformer Electrical Dist.
SPECIFICATION
Aux. Supply Burden on Aux. Trip Point Delay Relays Relay Contacts Contact Rating Temp Humidity Dimension Mounting Weight : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : +/- 15% of the set range : 0.1 , 0.2, 0.3, 0.5, 1 & 3 Seconds. : 2 Nos. (Trip Relay & 50% Alarm Relay) : Potential Free Contact (NO&NC)SPDT : 6 Amps / 230 V AC/ 28 V DC : 0 - 55 C : < 90% RH ( non condensing) : 90 x 45 x 75 mm ( L x B x H) : Din ( 35 mm rail ) : 350 gms
KM-512R
SPECIFICATION
Aux. Supply Burden on Aux. Delay Relay Contacts Contact Rating Temp Humidity Dimension Mounting Weight : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 0.1 Sec. to 10 Sec. : 2 Potential Free Contact ( NO&NC) ( Energise on Trip) : 6 Amps / 230 V AC/ 28 V DC : 0 - 55 C : < 90% RH ( non condensing) : 78 x 55 x 97 mm ( L x B x H) : Din ( 35 mm rail ) / 2 x m4 screw : 450 gms
APPLICATION
Protection : Control Panel Feeder / motor Generator Transformer Electrical Dist.
Sensitivity Ranges
Range: 30 - 300 mA , 30 - 3000 mA 300mA - 3Amps,1- 4 Amps 1 - 8 Amps, 1- 10 Amps Also user specified Ranges
19
KM-512R(IB)
SPACE HEATERS
MORGAIN Inc. manufactures "Anti Condensation' Panel heaters in a wide range. KAM series heaters are extremely robust in construction and provide heating for a wide variety of applications. This type of heaters finds its specific use as "Anti-Condensation Heater" in most of the control gear and switchgear panel applications. The costing being economical makes this ideal for these applications.
FEATURES
KM-198
SPECIFICATIONS
Kam
20
MODELS
KAM KAM KAM
SPECIFICATION
KM-2112R
KAM KAM
KM-212R
21
Current Relay
KA
PF
AS
OV
UV
KM 003R
KM 003R
22
PR
PF
Hz
AS
OV
UV
VF
KM-228R
KM-228R
23
FEATURES
Consistent reliability with high accuracy Trip setting through Front Panel Potentiometer Time Delay user settable LED indication for healthy / faulty status Auto / Manual Reset option Compact size
L N AUX.SUP.
A/M
C1 C2 INPUT
10%
30%
0-1SEC 10SEC
SET
UL A
TEST
DELAY
RESET
TY
NO
COM
NC
NO
COM
NC
APPLICATION
KM-560R
Protection : Control Panel Feeder / motor Generator Transformer Electrical Dist.
Temp : 0 - 55 C
Input Ranges
Range: CTR / 1 Amps CTR / 5 Amps. DC V : 0 - 1 / 5 / 10 V DC mA : 0 - 1 / 10 / 16 / 20 mA 4 - 20 mA 2 - 10 mA
SPECIFICATION
Aux. Supply Burden on Aux. Delay Set Point Relay Contacts NC) Contact Rating : < 3 VA : 0.1 Sec. to 10 Sec.
Humidity : < 90% RH ( non condensing) Dimension : 78 x 55 x 97 mm ( L x B x H) Mounting : Din ( 35 mm rail ) / 2 x m4 screw Weight : 450 gms
: 20% - 80% : 2 Potential Free Contact (2 NO & ( Energise on Trip) : 6 Amps / 230 V AC/ 28 V DC
APPLICATION
Protection : Control Panel Feeder / motor Generator Transformer Electrical Dist.
L N AUX.SUP.
A/M
C1 C2 INPUT
20%
SET
UL A
DELAY
RESET
TEST
TY
OVER LOAD RE
NO COM NC NO
LAY
COM NC
KM-1512R
SPECIFICATION
Aux. Supply Burden on Aux. Delay Set Point Relay Contacts Contact Rating : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 0.1 Sec. to 10 Sec. : 20% - 120% : 2 Potential Free Contact (2 NO & NC) ( Energise on Trip) : 6 Amps / 230 V AC/ 28 V DC Temp : 0 - 55 C Humidity : < 90% RH ( non condensing) Dimension : 78 x 55 x 97 mm ( L x B x H) Mounting : Din ( 35 mm rail ) / 2 x m4 screw Weight : 450 gms
Input Ranges
Range: CTR / 1 Amps CTR / 5 Amps. DC V : 0 - 1 / 5 / 10 V DC mA : 0 - 1 / 10 / 16 / 20 mA 4 - 20 mA 2 - 10 mA
24
POWER ON
ZERO
Ripple Free, Stable and High Accuracy Output External Span & Zero adjustment Low Internal consumption compact size Optional : Multiple output
SPAN
ISOLATOR
SIGNAL
OUTPUT + -
KM-199
Input Ranges
DC mV : 0 - 100 mV DC V : 0 - 1 / 5 / 10 V DC mA : 0 - 1 / 10 / 16 / 20 mA 4 - 20 mA 2 - 10 mA
Output Ranges
DC V : 0 - 1V ( Burden : 1K ) ) ) 0 - 5 / 1 - 5 V ( Burden : 5K DC mA : 0 - 1mA( Burden : 10K 0 - 5 mA( Burden : 2K ) ) ) ) 0 - 10 / 2 - 10 V ( Burden : 10K
SPECIFICATION
Aux. Supply Burden on Aux. Temp Humidity Accuracy Over Load Cap. Response time Isolation Dimension Mounting : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 0 - 55 C : < 90% RH ( non condensing) : Class 1.0 : 1.2 x rated voltage continuos 1.5 x rated voltage for 10 sec. : 0.5 Sec. : 2 KV ( 4 KV on request) : 78 x 55 x 97 mm ( L x B x H) : Din ( 35 mm rail ) / 2 x m4 screw
APPLICATION
INPUT to : Data Logging PLC SCADA Indicators Telemetering Recoders
WATT TRANSDUCER
+ OUTPUT
SPECIFICATION
Aux. Supply Burden on Aux. Temp Humidity Accuracy Response time Isolation Dimension Mounting Weight : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 0 - 55 C : < 90% RH ( non condensing) : Class 1.0 : 0.5 Sec. : 2 KV ( 4 KV on request) : 100 x 70 x 112 mm ( L x B x H) : Din ( 35 mm rail ) / 2 x m4 screw : Temperature : 500 gms Watt : 700 gms
Aux SUP. L N
KM-2032
Output Ranges
DC V : 0 - 1V ( Burden : 1K ) ) ) 0 - 5 / 1 - 5 V ( Burden : 5K DC mA : 0 - 1mA( Burden : 10K 0 - 5 mA( Burden : 2K ) ) ) ) 0 - 10 / 2 - 10 V ( Burden : 10K
25
AC / DC Voltage Transducer
FEATURES
Stable and High Accuracy Output
L N AUX.SUP.
INPUT
POWER ON
ZERO
SPAN
TRANSDUCER
VOLTAGE
OUTPUT + -
Input Ranges
AC V
KM-2220
DC V
Output Ranges
DC V : 0 - 1V ( Burden : 1K ) ) ) 0 - 5 / 1 - 5 V ( Burden : 5K DC mA : 0 - 1mA( Burden : 10K 0 - 5 mA( Burden : 2K ) ) ) ) 0 - 10 / 2 - 10 V ( Burden : 10K
APPLICATION
INPUT to : Data Logging PLC SCADA Indicators Telemetering Recoders
SPECIFICATION
Aux. Supply Burden on Aux. Temp Humidity Accuracy Response time Over Load Cap. Isolation Dimension Mounting Weight : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 0 - 55 C : < 90% RH ( non condensing) : Class 1.0 : 0.5 Sec. : 1.2 x rated Voltage continuos 1.5 x rated Voltage for 10 sec. : 2 KV ( 4 KV on request) : 78 x 55 x 97 mm ( L x B x H) : Din ( 35 mm rail ) / 2 x m4 screw : 400 gms
Current Transducer
FEATURES
Stable and High Accuracy Output
ZERO
L N AUX.SUP.
INPUT
POWER ON
External Span & Zero adjustment Low Internal consumption compact size Optional : Multiple Output
SPAN
TRANSDUCER
CURRENT
OUTPUT + -
KM-320
SPECIFICATION
Aux. Supply Burden on Aux. Temp Humidity Accuracy Response time Over Load Cap. Isolation Dimension Mounting Weight : 230V / 110VAC 50Hz (-20% +15%) : < 3 VA : 0 - 55 C : < 90% RH ( non condensing) : Class 1.0 : 0.5 Sec. : 2 x rated current continuos 10 x rated current for 10 sec. : 2 KV ( 4 KV on request) : 78 x 55 x 97 mm ( L x B x H) : Din ( 35 mm rail ) / 2 x m4 screw : 400 gms
Input Ranges
AC A : 0 - 1 A, 5A(direct) CTR / 1A, CTR / 5A
Output Ranges
DC V : 0 - 1V ( Burden : 1K ) ) ) 0 - 5 / 1 - 5 V ( Burden : 5K DC mA : 0 - 1mA( Burden : 10K 0 - 5 mA( Burden : 2K ) ) ) ) 0 - 10 / 2 - 10 V ( Burden : 10K
26
VDC
Over Speed
Stop Interval(S
ecs)
ON
Start
Reset
Ack
KM-516
V
I1
Y I Avg
I
I2
B L-L
Hz
V Avg I Avg
S I
OL UV OV PR
I3
P
3P4W
2
KA
50 60Hz
27
Timer
KM-020T
100 ON
0 100 REV
0 FOR
KM-618T
28
100 ON
KM-194T
CYCLIC TIMER
100 ON
100
REV
KM-003T
29
Customised Panel
V
VDC
Y B VL-L KA V Avg
A
Over Speed
Stop Interv al(Secs)
P
2
Hz
ON
Start
Reset
Ack
3P4W
50 60Hz
KM-316
30
Customised Panel
START
RESET STOP
KM-613A
31
Customised Panel
Wh R Vah Varh K
A V(L-N) W PF M V(L-L)
S Hz
KM-316B
32
Customised Panel
Amp Amp
L1 L1
Amp Amp
L2 L2
Amp Amp
L3
KW KW
L1
L2 L2 L3 L3
Hz Hz
P P
3P4W
2
50 60Hz
KM-316C
33
KM-5119
PARAMETERS
Volts Amps Frequency Power Factor KW KVA KVAr KWh KVArh KVAh THD Max. Demand : L - L, L - N ( Per Phase & Avg.) : Per Phase & summation : System : Per Phase & Avg : Per Phase & Summation : Per Phase & Summation : Per Phase & Summation : Import, Export & Summation : Capacitive & Inductive : Total : Volts & Amps : KVA / KW
FEATURES
State of Art Microcontroller Based Design. Suitable for 1 Phase & 3 phase measurement 2 Solid state Relay Out Put configurable for cutoff setting of any Parameter to give Alarm Rugged portable casing Clamp on CT's Programmable CT & PT Ratio. True RMS measurement. Auto Scrolling Facility. Password protection
APPLICATION
Load Study & Analysis Energy Audit Plant Maintance Power Management Data logging
EEprom retains Energy Parameters on power fail. Monitors Import & Export Energy. Computer Interface ( RS 485) optically isolated Inbuilt Data Logger for storing all Parameters with Date & Time stamp for long duration Audit without manual intervention / operation
SPECIFICATION
System Aux. Supply Burden on Aux. Voltage Input Current Input Burden on CT Communication Temp Humidity : 3 Phase 4 Wire / 3 Phase 3 Wire : 230V / 110VAC 50 Hz (-20% +15%) : < 4 VA : 110 / 415 / 440 VAC ( L - L )500Vmax : 1 Amps / 5 Amps : < 0.2 VA : RS 485 (Modbus - RTU Protocol) : 0 - 55 C : < 90% RH (non condensing) Dimension: 455 x 360 x 150 mm ( L x B x H) Accuracy : Voltage Current Active Power Reactive Power Apparent Power Power Factor Active Energy Reactive Energy Frequency : 0.5 % : 0.5 % : Class1.0 IEC 61036 : Class1.0 IEC 61036 : Class1.0 IEC 61036 : + 1 Electrical : Class1.0 IEC 61036 : Class1.0 IEC 61036 : + 0.2 Hz
34