Sie sind auf Seite 1von 1

Voltage Drop for 11KV cable.

"Author: LJ"
"Case: InternationalStadiumProject, Kochi"
(Contact mail@dkarcade.com for more details)
Considering 3core 185Sq mm XLPE cable;
Cable resistance and Reactance per KM
Length of cable, L

= 0.164 + j 0.082
= 900 meter

Maximum current carried by the cable, I


(At ful load of both 1600 KVA Transformers)

2x1600
= -------3 x 11
= 168 Amperes
===========

Voltage drop in cable

% Voltage drop

3 x I2 x L R +X2
=
---1000
= 3 x 1682 x 900 0.164 + 0.0822
-----1000
= 48V
===
48x100
= --------= 0.44%
11000
=====

Acceptable since % voltage drop is much below the permissible 3%


============================================================

Das könnte Ihnen auch gefallen