TYPICAL VOLTAGE DROP CALCULATION (FOR DOL START MOTOR )

For 63 KW DOL Feeder:


63 x 1000

Motor current : Im

------------------------------ =
0.8x 0.94x 1.732X435

111.1951 Amps

Impedence of the Cable Selected (95 Sq. mm XLPE Cable ) = Zc (say)


AC Resistance (at 70 0 C) of 95 Sq. mm Cable = 0.41 Ohm /Km.
For 570 Mtr length of Cable Rac = 0.41 x 0.570 = 0.2337 Ohm.
AC Reactance (at 70 0 C) of 95 Sq. mm Cable = 0.0724 Ohm /Km.
For 570 Mtr length of Cable Xac = 0.0724 x 0.570 = 0.0412 Ohm.
Therefore Impedance of the Cable Zc

= SQRT{ (Rac)2 +(Xac)2 }

= SQRT (0.0375) = 0.208 Ohm.

Running Voltage drop Vr in Motor Cable = ImX Ze = 117*0.208


24.336 =24.336x100/415= 5.59 %
Starting Voltage drop Vr in Motor Cable = 6 ImX Ze

=6X24.336 =6x 24.336x100/415= 33.5669%

24.336
5.594483 %
33.5669 %

AC Resistance (at 70 0 C) of 240 Sq. mm Cable Rac

0.152

AC Reactance (at 70 0 C) of 240 Sq. mm Cable Xac

0.073

Impedence of the Cable Zc


For two runs of 240 Sq. mm Cable effective Impedence Z e
Losses in volts =

Losses in percentage=

SQRT{ (Rac)2 +(Xac)2 }


0.169
0.084
Total current* effective impedance
42.155
42.155/415*100%
10.158

Ohms/Km

5.776

Ohms/Km

1.33225

0.076 (D5/2)
19000 (I2*R)
5700 (I6*300mtrs)
136800 For 24 hrs

Ohms
Rs

ective impedance
Volts
%

373

136.8 Units
41040 For 300 days
246240