Sie sind auf Seite 1von 2

Registered Office:

"Ashirwad" E-2/57,
Arera Colony, Bhopal, M.P.
INDIA 462016
Tel: +91-755-2463593/4276335
Mob: +91-9993091168
SOLONICS LTD
BTS 2000
THE FAST BUS TRANSFER SYSTEM
For Your High Speed Motor Bus Transfer Needs:-
l Fast Transfer with less than 2 cycles of dead bus time
l In Phase Transfer Mode -Transfer at first slip cycle phase
nd
coincidence with 2 Order Prediction Algorithm
l Residual Voltage Transfer Mode
l Momentary Paralleling Mode
l Protective as well as Intelligent Automatic Transfer
Initiation - Voltage / Frequency / | df/dt| Criterion
l ANSI C50.41 Compliant
l Comprehensive Online Testing
l Continuous Breaker Trip and Close Circuit Monitoring
l Smart Breaker Failure Processing
l Integrated System Interlocks
l Multiple breaker scheme configurations in a single
platform
l Standard communication protocols.
l Advanced Software Tools for Virtual Testing, Transfer
Event Upload, Replay What If Analysis, Oscillography
& SOE.
l And many more advanced features...
Email: info@aartechsolonics.com URL: http://www.aartechsolonics.com
Unit#1 - Mandideep :
35-A/36 Sector-B
Industrial Area, Mandideep
Dist. Raisen, M.P.
INDIA 462046
Tel: +91-7480-233020
Unit#2 - Parwanoo :
Khasra No. 311,
Near Him Cold Storage
Sector-1A, Parwanoo
Dist. Solan, H.P.
INDIA 173220
Copyright 2012 Aartech Solonics Ltd. Rev-4
AARTECH SOLONI CS LI MI TED
BTS 2000: 3 Breaker Scheme
Station-to-Station (STS) / Main-Tie-Main Configuration
BTS 2000: 2 Breaker Scheme
Unit-to-Station (UTS) / Main-Tie Configuration
Meeting Customer Specific Application Requirements such as
- Islanded Transfer between Asynchronous Systems, Custom
Logics, SCADA Integration etc.
For any queries, please write to bts@aartechsolonics.com
or contact us at our Registered Office
Finally . . . . . . . .
A System Solution For
POWER GENERATION UTILITIES & CONTINUOUS PROCESS INDUSTRIES
that keeps them running when
CONTINGENCY STRIKES . . . . .
Thermal Power | Nuclear Power | Captive Power
[Metals | Petrochemical | Mining | Water Handling]
New

Programmable LED indications Human Machine Interface
20x4 Character Backlit LCD
Softkey Menu Pushbuttons
Menu Navigation Pushbuttons
Hotkey Menu Pushbuttons
BTS IN/OUT Service
Selection Toggle Switch
Front RS-232 Dataport
Fixed Function Pushbuttons
with LED Indications
BTS IN/OUT Indication
BTS Readiness Disable Fuse
Test Transfer Pushbutton
(Green)
Manual Transfer Pushbutton (Red)
SPIN DOWN CHARACTERISTICS OF AN OPEN CIRCUIT MOTOR BUS
FAST TRANSFER
IN PHASE TRANSFER
RESIDUAL VOLTAGE OR
SLOW TRANSFER
NORMAL SOURCE
VOLTAGE PHASOR
(V NORMAL)
MOTOR BUS
VOLTAGE PHASOR
VOLTAGE COLLAPSE
AND PHASE DECAY
CHARACTERISTICS
OF THE MOTOR BUS

BTS 2000 Specifications
BTS 2000 Human Machine Interface
EDISONIDEAPLUS MANUFACTUREDBYCOOPER POWER SYSTEMS U.S.A. WITH32BIT MICROPROCESSOR BASEDRISC
ARCHITECTURE
HORIZONTAL, FLUSHMOUNTING INTHE SWITCHGEAR CUBICLE / SIMPLEXPANEL / 19RACK FRAME WITHA19RACK
ADAPTER WITHANOPTIONAL DEDICATEDCOMPUTER INTERFACE. WEIGHT: 6KGS.
5UHEIGHT, 19RACK EQUIPMENT [262(W) x222(H) x254(D) mm]
-40DEG C TO+70DEG C CONTINUOUS
-40DEG C TO+85DEG C UPTO16HOURS
250VAC/DC +/- 20%, OTHER STANDARDVOLTAGES E.G. 120/ 48/24VAC/DC ONREQUEST.
25PROGRAMMABLE LEDINDICATIONS
20CHARACTER, 4LINE, WIDE ANGLE, HIGHTEMPERATURE, SUPER TWIST BACKLIT LCDFOR MENUDISPLAY
BTS OUT HIGHINTENSITYLEDINDICATION
8FIXEDFUNCTIONPUSHBUTTONS FOR MENUNAVIGATION
8HOTKEYS FOR DIRECT MENUACCESS
4MULTI FUNCTIONPROGRAMMABLE, CONTEXT SENSITIVE PUSHBUTTONS FOR MENUBASEDCONTROLS
9FIXEDFUNCTIONPUSHBUTTONS WITHLEDINDICATIONS FOR TRANSFER DIRECTIONSELECTION&TRANSFER MODE
SELECTION
1EACHTEST ANDTRANSFER ILLUMINATEDPUSHBUTTONS
BTS SERVICE SELECTIONIN/OUT TOGGLE SWITCH
BTS READINESS DISABLE FUSE
UPTO17CONTACT INPUTS, 4TRIPRATEDELECTROMECHANICAL CONTACT OUTPUTS, 9TRIPRATEDSOLIDSTATE
CONTACT OUTPUTS, 45ACURRENT INPUTS, 6110VAC VOLTAGE INPUTS, FRONT ANDREAR RS-232PORTS, RS-485
PORT/RJ-45PORT, IRIG-B PORT. (INDIVIDUAL CONFIGURATIONS VARY)
GRAPHICAL USER INTERFACE BASEDSCHEME IMPLEMENTATION, VIRTUAL TEST SET SIMULATION, MODULAR OBJECT
ORIENTEDPROGRAMMING, SETTINGS, ONLINE VIEWING, SCADAMIMIC APPLICATIONDIAGRAM, SEQUENCE OF EVENT
RECORDING, STEP-BY-STEPREPLAY, WHAT-IFANALYSIS, OSCILLOGRAPHY, DATAPROFILER, REMOTE CONTROL.
IMPULSE / DIELECTRIC WITHSTAND: IEC 60255-5
ELECTROSTATIC DISCHARGE: EN61000-4-2
RADIOFREQUENCYINTERFERENCE EN61000-4-3
SURGE WITHSTAND: ANSI / IEEE C37.90.1
CONDUCTEDIMMUNITYTEST15Hz 150kHz: IEC 61000-4-16
CONDUCTEDIMMUNITYTEST: 150kHz 80MHz: IEC 61000-4-6
RADIATEDIMMUNITYTEST: 80MHz 1GHz: EN61000-4-3, IEEE C37.90.2
MAKE ANDCARRYRATING: IEEE C37.90
MULTIPLE TRANSFER DIRECTIONS: BASEDONBREAKER CONFIGURATIONS
MULTIPLE TRANSFER INITIATION: MANUAL, PROTECTIVE &AUTOINITIATION(U/V, U/F &|df/dt| BASED)
TRANSFER MODES: FAST, IN-PHASE, RESIDUAL VOLTAGE / SLOW, MOMENTARYPARALLELING
COMPREHENSIVE TRANSFER READINESS &BTS BLOCKING INTERLOCKS
CONTINUOUS BREAKER TRIP/CLOSE CIRCUIT MONITORING
SMART BREAKER FAILURE PROCESSING
COMPREHENSIVE ONLINE / OFFLINE TESTING MODES
ANSI C50.41/ NEMAMG-1COMPLIANT
ELECTROMAGNETIC COMPATIBILITY:
CONTACT RATING TEST:
Note: Aartech reserves the right to modify technical specifications without notice.
PLATFORM
MOUNTING
&WEIGHT
DIMENSIONS
TEMP. RANGE
POWER SUPPLY
VISUAL INTERFACE
CONTROL INTERFACE
SYSTEMINTERFACE
SOFTWARE INTERFACE
HARDWARE STANDARDS
BUS TRANSFER SCHEME
FEATURES
BTS 2000 Software Screenshots
ENVIRONMENTAL TESTING:
COLDTEMPERATURE TEST: IEC 60068-2-1
HIGHTEMPERATURE TEST: IEC 60068-2-2
HUMIDITYTEST: IEC 60068-2-30
ENVIRONMENTAL WITHSTAND: IEC 60068-2-30
VIBRATIONTEST: IEC 255-21-1
BUMP&SHOCK TEST: IEC 60255-21-2
PENETRATION: IEC 60259, IP3X
BTS 2000 LT