Sie sind auf Seite 1von 14

A B C A B C A B C

1 XEN(P) JAISALMER
AEN(P) JAISALMER 554 30 141 31 1 7 70 0 14
AEN(P) BARMER 955 69 260 39 0 8 68 2 16
GRAND TOTAL DIV. 1509 99 401 70 1 15 138 2 30
A # DENOTES TO BE TESTED
B # DENOTES TESTED DURING THE MONTH
C # DENOTES TESTED UP TO THE MONTH
NOTE:-
By AEN(P) J AISALMER
By AEN(P) BARMER
THE STATEMENT SHOWING THE PROGRESS REPORT FOR CHECKING OF PROTECTION EQUIPMENTS & ENERGY METERS AT VARIOUS GSS/POWER
SUBSTATIONS FOR THE MONTH OF APRIL' 2014 W.E.F APRIL 2014 TO MARCH 2015 (5 YEAR BLOCK)
RAJASTHAN RAJYA VIDYUT PRASARAN NIGAM LIMITED
PROTECTION DIVISION JAISALMER
FORMAT FOR PROGRESS OF CHECKING OF
PROTECTION EQUIPMENTS & ENERGY METERS AT VARIOUS
GSS / POWER SUBSTATIONS
S.
NO.
PROTECTION DIVISION
/ SUB
DIVISION
O / C& E / F RELAYS DIFFERENTIAL
RELAYS
DISTANCE RELAYS
ANNEXURE-B
A B C A B C A B C
0 0 0 145 0 29 92 0 21
3 0 1 230 1 47 164 0 37
3 0 1 375 1 76 256 0 58
THE STATEMENT SHOWING THE PROGRESS REPORT FOR CHECKING OF PROTECTION EQUIPMENTS & ENERGY METERS AT VARIOUS GSS/POWER
SUBSTATIONS FOR THE MONTH OF APRIL' 2014 W.E.F APRIL 2014 TO MARCH 2015 (5 YEAR BLOCK)
RAJASTHAN RAJYA VIDYUT PRASARAN NIGAM LIMITED
PROTECTION DIVISION JAISALMER
DOC : RVPN / PROTECTION / F / 01 / 06
issue No. : 01
Page No. : 01 of 01
Page Rev No. : 02
Date : 17 JUN 2013
OTHER RELAYS UNDER FREQUENCY
RELAYS
R.R.V.P.N.L Jaisalmer
ENERGY METERS
Executive Engineer (Prot)
1.POWER TRANSFORMER
0 0
2.FEEDER PROTECTION
0 0
3.METERING EQUIPMENTS
0 0
4.OTHER MISC. WORK SUCH AS
CAP.BANK U/F RELAYS ETC. 0 0
1.POWER TRANSFORMER
0 0
2.FEEDER PROTECTION
0 0
3.METERING EQUIPMENTS
0 0
4.OTHER MISC. WORK SUCH AS
CAP.BANK U/F RELAYS ETC. 0 0
1.POWER TRANSFORMER
0 0
2.FEEDER PROTECTION
0 0
3.METERING EQUIPMENTS
0 0
4.OTHER MISC. WORK SUCH AS
CAP.BANK U/F RELAYS ETC. 0 0
BY AEN(P) JAISALMER: BY AEN(P) Barmer
New Commissioning : New Commissioning :
1. Testing of 1 Sets of CTs of 220 kV Balotra- Giral Line at 220 kV GSS
Balotra.
WORK RELATED TO
NEW COMMISSIONING
WORK (NOS.)
DURING
THE
MONTH
PROTECTION
DIVISION
1
RAJASTHAN RAJYA VIDYUT PRASARAN NIGAM LIMITED
MONTH: APRIL-14 PROTECTION DIVISION JAISALMER Annexure - XI
FORMAT FOR PROGRESS OF OTHER
PROTECTION WORK
DOCUMENT NO. : RVPN / PROTECTION / F / 01 / 07
ISSUE NO. : 01
PAGE NO. : 1 of 1
PAGE REV NO. : 00
3. Testing of 1 Sets of CTs of 11 kV Baldev Nager (O/G feeders) at 132 kV
GSS Barmer.
PROTECTION
SUB
DIVISION
Assistant
Engineer
(Prot.)
Jaisalmer
Complaints Attended: Complaints Attended:
Executive
Engineer
(Prot.)
Jaisalmer
Assistant
Engineer
(Prot.)
Barmer
2. Testing of 1 Sets of CTs of 33 kV Dudhu (O/G feeders) at 220 kV GSS
Gudamalani.
TOTAL DIVISION
S NO.
PROGRESSIVE
TOTAL
1. Complete Testing of 400/220 kV ICT-1 at 400 kV GSS Akal.
1 1
0 0
0 0
0 0
0 0
3 3
0 0
0 0
1 1
3 3
0 0
0 0
1. Testing of 1 Sets of CTs of 220 kV Balotra- Giral Line at 220 kV GSS
Balotra.
COMPLAINTS ATTENDED (NOS)
RAJASTHAN RAJYA VIDYUT PRASARAN NIGAM LIMITED
MONTH: APRIL-14 PROTECTION DIVISION JAISALMER Annexure - XI
DOCUMENT NO. : RVPN / PROTECTION / F / 01 / 07
ISSUE NO. : 01
PAGE NO. : 1 of 1
PAGE REV NO. : 00
3. Testing of 1 Sets of CTs of 11 kV Baldev Nager (O/G feeders) at 132 kV
GSS Barmer.
PROGRESSIVE TOTAL
Complaints Attended:
2. Testing of 1 Sets of CTs of 33 kV Dudhu (O/G feeders) at 220 kV GSS
Gudamalani.
DURING
THE
MONTH
S. NO. PROT.DIV. /SUB.DIV.
S. NO. NAME OF PROT DIV / SUB DIV
TOTAL
TO BE
INSTALLE
D
INSTALLE
D
BALANCE
TO BE
INSTALLE
D
TOTAL
TO BE
INSTALLE
D
INSTALLE
D
1 2 3 4 5 6 7
1 AEN(P) JAISALMER 18 18 0 0 0
2 AEN(P) BARMER 30 30 0 0 0
TOTAL DIV.JAISALMER 48 48 0 0 0
On various Generating plants at and near Barmer and Jaisalmer
AEN(P) JAISALMER
At 132 KV GTPP Ramgarh on 132 KV Lines to Jaisalmer and Amarsagar GSS
At 220 KV GSS Amarsagar on 220/132 KV Lines to GTPP Ramgarh.
At 132 KV GSS Jaisalmer on 132 KV Lines to GTPP Ramgarh
AEN(P) BARMER
At 220 KV GSS Bhadresh M/s Raj Westpower on 220 KV Lines to Barmer GSS
At 220 KV GSS Bhadresh M/s Raj Westpower on 220 KV Line to Dhorimanna GSS
At 400 KV GSS Bhadresh M/s Raj Westpower on 400 KV Lines to 400 kV GSS Jodhpur
At 400 KV GSS Bhadresh M/s Raj Westpower on 400 KV Lines to 400 kV GSS Barmer
At 220 KV GLTPP Giral (Barmer) on 220 KV Lines to Barmer and Mada GSS
At 220 KV GSS Barmer on 220 KV Lines to GLTPP Giral and Mada (Bhu) GSS
RAJASTHAN RAJYA VIDYUT PRASARAN NIGAM LTD.
PROTECTION DIVISION JAISALMER
FORMAT FOR PROGRESS OF STATIC TVM INSTALLED FOR
ENERGY AUDIT/ACCOUNTAL AND PROGRESS OF INSTALLTION
PROGRESS OF INSTALLTION OF STATIC TVM FOR THE MONTH OF APRIL-14 ANNEX.-VI
Details of Inter Utility Meters :
LV SIDE OF EHV INTERSTATE METERING
BALANCE
TO BE
INSTALLE
D
TOTAL
TO BE
INSTALLE
D
INSTALLE
D
BALANCE
TO BE
INSTALLE
D
TOTAL
TO BE
INSTALLE
D
INSTALLE
D
BALANCE
TO BE
INSTALLE
D
8 9 10 11 (3+6+9) (4+7+10) (5+8+11)
0 6 6 0 24 24 0
0 21 21 0 51 51 0
0 27 27 0 75 75 0
:
: 3 Nos.
: 1 No.
: 2 Nos.
: 4 Nos.
: 2 Nos.
At 400 KV GSS Bhadresh M/s Raj Westpower on 400 KV Lines to 400 kV GSS Jodhpur : 4 Nos.
At 400 KV GSS Bhadresh M/s Raj Westpower on 400 KV Lines to 400 kV GSS Barmer : 2 Nos.
: 5 Nos.
: 4 Nos.
RAJASTHAN RAJYA VIDYUT PRASARAN NIGAM LTD.
PROTECTION DIVISION JAISALMER
FORMAT FOR PROGRESS OF STATIC TVM INSTALLED FOR
ENERGY AUDIT/ACCOUNTAL AND PROGRESS OF INSTALLTION
DOCUMENT NO.RVPNL/PROT/F/01/05
ISSUE NO.01
PROGRESS OF INSTALLTION OF STATIC TVM FOR THE MONTH OF APRIL-14 ANNEX.-VI
INTER UTILITY TOTAL REQUIRMENT FOR
RVPNL, JAISALMER
EXECUTIVE ENGINEER (PROTECTION)
INTERSTATE METERING
ANNEXURE 2
S.No.
NAME OF
RELAY /
SCHEME
NAME OF
PROTECTION
SUB DIVISION
NAME OF GSS NAME OF FEEDER RELAY DETAILS TYPE OF DEFECT OBSERVED
DATE OF
OBSERVATION
ACTION TAKEN & PRESENT STATUS
1
O/C & E/F
RELAYS
AEN(P)
BARMER
132 KV GSS
Mahloo
33 kV I/C JVS / JRP 021
The green LED of healthy supply
does not glow and the relay does
not operate at all.
07.01.2010
Replaced with relays of B/C and intimated to GSS
Incharge for arranging repair/ replacement.
2
O/C & E/F
RELAYS
AEN(P)
BARMER
132KV GSS,
Gadra Road
33 kV Bus coupler JVS / JRC 053/57R
All the three LEDs (R,B and
E/F)are glowing continuously with
D.C. Supply. This relay is placed
on 33 kV Incomer.
28.01.2010
Intimated to GSS Incharge for arranging repair/
replacement.
3
O/C & E/F
RELAYS
AEN(P)
BARMER
220kV GSS
Dhorimana
132 kV Guda line
E/R make TJM-12
406a4096(H)
Relay is not operating with fault. 07.05.2010
Intimated to GSS Incharge for arranging repair/
replacement.
4
O/C & E/F
RELAYS
AEN(P)
JAISALMER
132KV GSS,
Chandan
33 kV Bus Coupler
Make- ALSTOM , Type-
MCTGM
Relay contacts are not woking of
the B-Phase .
20.07.2012
Intimated to GSS Incharge for arranging repair/
replacement.
5
O/C & E/F
RELAYS
AEN(P)
JAISALMER
132kV GSS
Sheo
132 kV Jaisalmer line E/R make 2TJM-10
Relay is not operating properly as
per IDMT Charateristics. .
25.10.2012
Intimated to GSS Incharge for arranging repair/
replacement.
6
O/C & E/F
RELAYS
AEN(P)
BARMER
220 kV GSS
Balotra
220 KV B/C JVS / JRC 054/19T Relay is not operating with fault. 15.7.2013
Intimated to GSS Incharge for arranging repair/
replacement.
7
O/C & E/F
RELAYS
AEN(P)
BARMER
132 KV GSS
BARMER
33 KV Barmer feeder
Gec.Alstom/CDG31FF0
03SB(M)
Relay is not operating with fault. 10.7.2013
Intimated to GSS Incharge for arranging repair/
replacement.
1 OTHER RELAYS
AEN(P)
JAISALMER
132KV GSS,
Ramgarh
132/33KV,10/12.5MVA
Transformer
English Electric,over
flux,GTTM
Relay burnt 16.07.2008
Intimated to GSS Incharge for arranging repair/
replacement.
2 OTHER RELAYS
AEN(P)
JAISALMER
132KV GSS,
Pokran.
33KV Cap Bank
English
Electric,VDG,NDR,160
A
Relay doesnot pickup with D.C.
Supply.
26.06.2008
Intimated to GSS Incharge for arranging repair/
replacement.
3 OTHER RELAYS
AEN(P)
BARMER
132KV GSS,
Barmer
33KV Cap Bank II(2Nos)
English
Electric,VDG,NDR,260
A
Relay not operating 26.03.2009
Intimated to GSS Incharge for arranging repair/
replacement.
4 OTHER RELAYS
AEN(P)
BARMER
220 kV GSS
Balotra
132/33KV,10/12.5MVA
Transformer
English Electric,over
flux,GTTM
One Resistance in the Relay found
burnt.
05.05.2010
Intimated to GSS Incharge for arranging repair/
replacement.
Executive Engineer (Prot)
R.R.V.P.N.L Jaisalmer
FORMAT FOR STATUS OF DEFECTIVE
RELAYS / SCHEMES
DOCUMENT NO. : RVPNL / PROTECTION / F / 01 / 09
ISSUE NO. : 01
PAGE NO. : OF 3
PAGE REV. NO : 00
DATE : 19 OCT 2005
Month: APRIL -14
NAME OF OFFICE :- EXECUTIVE ENGINEER (PROTECTION), RVPNL, JAISALMER
S.NO. TYPE OF ENERGY METERS TOTAL NUMBER
TO BE TESTED THIS
YEAR
1 2 3 4
1 INTERFACE METERS 6 2
2
ENERGY ACCOUNTING
AND AUDIT METERS
18 5
3 OTHER METERS 68 14
GRAND TOTAL 92 21
1 INTERFACE METERS 21 5
2
ENERGY ACCOUNTING
AND AUDIT METERS
30 7
3 OTHER METERS 113 25
GRAND TOTAL 164 37
1 INTERFACE METERS 27 7
2
ENERGY ACCOUNTING
AND AUDIT METERS
48 12
3 OTHER METERS 181 36
GRAND TOTAL 256 55
XEN (P)
Jaisalmer
STATEMENT SHOWING THE PROGRESS REPORT FOR CHECKING OF PROTECTION EQUPIMENTS & ENERGY METERS AT
VARIOUS GSS/POWER SUB STATION FOR THE MONTH OF:- APRIL-14
Name of Sub
Div./Div
AEN (P)
Jaisalmer
AEN (P) Barmer
1 No.Energy Meter are added for 33 kv O/G Feeder Solar Bay at 220 kv GSS Balotra.
1 No.Energy Meter are added for 33 kv Incommer-2 at 132 kV Sheo GSS.
1 No. Energy Meter is added for 33 kV Incomer 2 at 132kV GSS Undu.
ANNEXURE -X
NAME OF OFFICE :- EXECUTIVE ENGINEER (PROTECTION), RVPNL, JAISALMER (DETAILS)
TESTED DURING
THE MONTH
TESTED UP TO THE
MONTH
5 6
0 2
0 5
0 14
0 21
0 5
0 7
0 25
0 37
0 7
0 12
0 39
0 58
EXECUTIVE ENGINEER (PROTECTION)
STATEMENT SHOWING THE PROGRESS REPORT FOR CHECKING OF PROTECTION EQUPIMENTS & ENERGY METERS AT
VARIOUS GSS/POWER SUB STATION FOR THE MONTH OF:- APRIL-14
RVPNL, JAISALMER
1 No.Energy Meter are added for 33 kv O/G Feeder Solar Bay at 220 kv GSS Balotra.
1 No.Energy Meter are added for 33 kv Incommer-2 at 132 kV Sheo GSS.
1 No. Energy Meter is added for 33 kV Incomer 2 at 132kV GSS Undu.