ASSIGNMENT

SUBJECT: Industrial Power System Analysis and Design

Speed
Increment

Motor
Torque in %

Load
Torque in %

0 to 20%
84
5
20 to 40%
93
8
40 to 60%
120
20
60 to 80%
175
30
80 to 100%
167
45
N-T Characteristics of motor & load

%kVA
550
540
525
480
350

Solution:
1500 hP
1242 kVA @ 0.9 lag PF
1.05 % of 4.16kV

Rated Power
Voltage at the motor terminal before stating
Motor Full Load Torque
Motor RPM
System Short Circuit capacity
Motor shaft & Load (Wk^2)
Speed
Increment

%kVA

kVA

0 to 20%
550
6831
20 to 40%
540
6706.8
40 to 60%
525
6520.5
60 to 80%
480
5961.6
80 to 100%
350
4347
Total Starting time in seconds
Note: HP = Torque x RPM 5252

4376.66667
1800
40000
10200
% of Motor
Voltage
89.68418355
89.92266651
90.28277856
91.38063079
94.70764651

lb-ft
RPM
kVA
lb-ft^2

Motor
Load
Net
Torque in % Torque in % Torque in %
84
93
120
175
167

5
8
20
30
45

79
85
100
145
122

Net
torque
in lb-ft2
3457.567
3720.167
4376.667
6346.167
5339.534

del time
in seconds
3.448112
3.204716
2.724008
1.878627
2.232794
13.48826