Reference Tables

Australian Standard Metric Conductors


AAC - All Aluminium Conductor - AS1531

Metric

Code
Name

7/1.75
7/2.25
7/2.50
7/2.75
7/3.00
7/3.75
7/4.50
7/4.75
19/3.25
19/3.50
19/3.75
37/3.00
37/3.25
19/4.75
37/3.75
61/3.25
61/3.50
61/3.75
91/4.50

5.25
6.75
7.50
8.25
9.00
11.3
13.5
14.3
16.3
17.5
18.8
21.0
22.8
23.8
26.3
29.3
31.5
33.8
49.5

Imperial

Calculated
Calculated
Equivalent Sectional Minimum
Aluminium
Breaking
Area
Area mm2
mm2
Load kN
16.6
27.5
33.9
41.1
48.9
76.3
110
122
154
180
206
256
301
331
400
495
574
659
1410

16.84
27.83
34.36
41.58
49.48
77.28
111.3
124.0
157.6
182.80
209.8
261.60
307.00
336.7
408.50
506.10
586.90
673.40
1447

3.01
4.76
5.71
6.72
7.98
11.8
16.9
18.9
24.7
28.7
31.9
42.2
48.2
51.3
62.2
75.2
87.3
97.2
207

Reference Tables

Gemini
Jupiter
Leo
Leonids
Libra
Mars
Mercury
Moon
Neptune
Orion
Pluto
Saturn
Sirius
Taurus
Triton
Uranus
Ursula
Venus
Virgo

Overall
Diameter
Strands/Wire (Approx)
Diameter mm
mm

17-2

www.dulmison.com.au

Code
Name

Stranding

O.D.
Inches

Bug
Locust
Grub
Wasp
Hornet
Chafer
Cockroach
Butterfly
Centipede
Scorpion
Cicada
-

7/064
7/093
7/118
7/144
7/173
7/186
19/128
19/149
19/166
19/183
37/149
37/168
37/183
-

0.192
0.279
0.354
0.432
0.519
0.558
0.640
0.745
0.830
0.915
1.043
1.176
1.281
-

Reference Tables

Australian Standard Metric Conductors


AAAC - All Aluminium Alloy Conductor - AS1531

Metric

Agate
Amethyst
Diamond
Dolomite
Emerald
Garnet
Jade
Jasper
Opal
Patronite
Pearl
Ruby
Ruthenium
Rutile
Sapphire
Spinel
Tantalum
Topaz
Zircon

7/1.75
7/2.25
7/2.50
7/2.75
7/3.00
7/3.75
7/4.50
7/4.75
19/3.25
19/3.50
19/3.75
37/3.00
37/3.25
19/4.75
37/3.75
61/3.25
61/3.50
61/3.75
91/4.50

5.25
6.75
7.50
8.25
9.00
11.3
13.5
14.3
16.3
17.5
18.8
21.0
22.8
23.8
26.3
29.3
31.5
33.8
49.5

Imperial

Calculated
Calculated
Equivalent Sectional Minimum
Aluminium
Breaking
Area
Area mm2
mm2
Load kN
14.3
23.7
29.3
35.4
42.2
65.8
94.8
106
134
155
178
221
260
285
345
427
495
568
1220

16.84
27.83
34.36
41.58
49.48
77.28
111.3
124.0
157.6
182.80
209.8
261.60
307.00
336.7
408.50
506.10
586.90
673.40
1447

4.71
7.78
9.64
11.6
13.9
21.7
31.2
34.8
44.2
51.3
58.8
73.5
86.1
94.4
115
135
156
179
384

Code
Name

Stranding

O.D.
Inches

Bug
Locust
Grub
Wasp
Hornet
Chafer
Cockroach
Butterfly
Centipede
Scorpion
Cicada
-

7/064
7/093
7/118
7/144
7/173
7/186
19/128
19/149
19/166
19/183
37/149
37/168
37/183
-

0.192
0.279
0.354
0.432
0.519
0.558
0.640
0.745
0.830
0.915
1.043
1.176
1.281
-

Reference Tables

Code
Name

Overall
Diameter
Strands/Wire (Approx)
Diameter mm
mm

www.dulmison.com.au

17-3

Reference Tables

Australian Standard Metric Conductors


AAAC 1120 - All Aluminium Alloy Conductor - AS1531

Metric

Code
Name

7/1.75
7/2.25
7/2.50
7/2.75
7/3.00
7/3.75
7/4.50
7/4.75
19/3.25
19/3.50
19/3.75
37/3.00
37/3.25
19/4.75
37/3.75
61/3.25
61/3.50
61/3.75
91/4.50

5.25
6.75
7.50
8.25
9.00
11.3
13.5
14.3
16.3
17.5
18.8
21.0
22.8
23.8
26.3
29.3
31.5
33.8
49.5

Imperial

Calculated
Calculated
Equivalent Sectional Minimum
Aluminium
Breaking
Area
Area mm2
mm2
Load kN
16
26.5
32.8
39.7
47.2
73.7
106
118
150
173
199
248
291
320
387
478
555
636
1360

16.84
27.83
34.36
41.58
49.48
77.28
111.3
124.0
157.6
182.80
209.8
261.60
307.00
336.7
408.50
506.10
586.90
673.40
1447

4
6.61
8.18
9.91
11.8
17.6
24.3
27.1
37.4
41.7
47.8
62.2
72.8
73.6
93.1
114
127
145
300

Reference Tables

Argon
Boron
Chlorine
Chromium
Fluorine
Helium
Hydrogen
Iodine
Krypton
Lutetium
Neon
Nitrogen
Nobelium
Oxygen
Phosphorus
Selenium
Silicon
Sulfur
Xenon

Overall
Diameter
Strands/Wire (Approx)
Diameter mm
mm

17-4

www.dulmison.com.au

Code
Name
Bug
Locust
Grub
Blue-Bottle
Wasp
Hornet
Chafer
Cockroach
Butterfly
Centipede
Scorpion
Cicada
-

Stranding

O.D.
Inches

7/0.064
7/0.093
7/0.118
7/0.144
7/0.173
7/0.186
19/0.128
19/0.149
19/0.166
19/0.183
37/0.149
37/0.168
37/0.183
-

0.192
0.279
0.354
0.432
0.519
0.558
0.640
0.745
0.830
0.915
1.043
1.176
1.281
-

Reference Tables

Australian Standard Metric Conductors


ACSR/GZ - Aluminium Conductor (Galvanised) Steel Reinforced - AS3607

Metric

Almond
6/1/2.50
Apple
6/1/3.00
Banana
6/1/3.75
Cherry
6/4.75 + 7/1.60
Grape
30/7/2.50
Lemon
30/7/3.00
Lime
30/7/3.50
Mango
54/7/3.00
Orange
54/7/3.25
Olive
54/7/3.50
Paw Paw 54/3.75 + 19/2.25
Peach 54/4.75 + 19/2.85
EXTRA HIGH STRENGTH
Quince
3/4/1.75
Raisin
3/4/2.50
Sultana
4/3/3.00
Walnut
4/3/3.75

Imperial

Calculated
Calculated
Equivalent Sectional Minimum
Breaking
Area
Aluminium
mm2
Load kN
Area mm2

Code
Name

Stranding

O.D.
Inches

7.50
9.00
11.3
14.3
17.5
21.0
24.5
27.0
29.3
31.5
33.8
42.8

29.0
41.8
65.2
105
144
207
282
373
438
508
583
936

34.36
49.48
77.31
120.4
181.6
261.5
356.0
431.2
506.0
586.9
671.7
1078

10.5
14.9
22.8
33.2
63.7
90.1
121
118
137
159
179
284

Gopher
Ferret
Mink
Dog
Wolf
Panther
Bear
Bison
Brolga
Moose
Finch
-

6/1/093
40549
6/1/144
6/186 + 7/062
30/7/102
30/7/118
30/7/132
54/7/11
54/7/129
54/7/139
54/143 + 19/086
-

0.279
8.354
0.432
0.558
0.714
0.826
0.924
81.062
1.162
1.251
1.293
-

5.25
7.50
9.00
11.3

8.77
17.9
31.6
49.4

16.84
34.36
49.48
77.31

12.7
24.4
28.3
43.9

Reference Tables

Code
Name

Overall
Diameter
Strands/Wire (Approx)
Diameter mm
mm

www.dulmison.com.au

17-5

Reference Tables

Australian Standard Metric Conductors


ACSR/AZ - Aluminium Conductor (Aluminised) Steel Reinforced - AS3607

Strands/Wire
Diameter mm

Barley
Bean
Cabbage
Carrot
Corn
Garlic
Millet
Oats
Onon
Parsnip
Potato
Rice

6/1/2.50
6/1/3.00
6/1/3/75
6/4.75 + 7/1.60
30/7/2.50
30/7/3.00
30/7/3.50
54/7/3.00
54/7/3.25
54/7/3.50
54/3.75 + 19/2.25
54/4.75 + 19/2.85

7.50
9.00
11.3
14.3
17.5
21.0
24.5
27.0
29.3
31.5
33.8
42.8

Calculated
Equivalent
Aluminium Area
mm2
29.0
41.8
65.2
105
144
207
282
373
438
508
583
936

Reference Tables

Code
Name

Overall
Diameter
(Approx)
mm

17-6

www.dulmison.com.au

Calculated
Sectional Area Minimum Breaking
mm2
Load kN
34.36
49.48
77.31
120.4
181.6
261.5
356.0
431.2
506.0
586.9
671.7
1078

10.3
14.5
21.5
31.9
61.6
87.2
116
115
132
153
177
277

Reference Tables

Australian Standard Metric Conductors


ACSR/AC - Aluminium Conductor (Aluminium Clad) Steel Reinforced - AS3607

Strands/Wire
Diameter mm

Angling
Archery
Baseball
Bowls
Cricket
Darts
Diving
Golf
Gymnastics
Hurdles
Lacrosse
Rugby

6/1/2.50
6/1/3.00
6/1/3.75
6/4.75+7/1.60
30/7/2.50
30/7/3.00
30/7/3.50
54/7/3.00
54/7/3.25
54/7/3.50
54/3.75+19/2.25
54/4.75+19/2.85

Skating
Soccer
Swimming
Tennis

3/4/1.75
3/4/2.50
4/3/3.00
4/3/3.75

Calculated
Equivalent
Aluminium Area
mm2

7.50
30.7
9.00
44.1
11.3
68.9
14.3
109
17.5
155
21.0
224
24.5
305
27.0
390
29.3
457
31.5
530
33.8
608
42.8
976
EXTRA HIGH STRENGTH
5.25
10.4
7.50
21.2
9.00
35.2
11.3
54.9

Calculated
Sectional Area Minimum Breaking
mm2
Load kN
34.36
49.48
77.31
120.4
181.6
261.5
356.0
431.2
506.0
586.9
671.7
1078

10.7
15.0
22.4
32.6
64.6
91.3
121
119
138
159
181
287

16.84
34.36
49.48
77.31

12.3
24.9
28.8
42.8

Reference Tables

Code
Name

Overall
Diameter
(Approx)
mm

www.dulmison.com.au

17-7

Reference Tables

Australian Standard Metric Conductors


SC/GZ - Steel Conductor / Galvanised - AS1222

Metric

Imperial

Strands/Wire
Diameter mm

Overall
Diameter
(Approx)
mm

Calculated
Equivalent
Aluminium
Area mm2

3/2.00
3/2.75

7/2.00
7/2.75
7/3.25
7/3.75
19/2.00

19/2.75
19/3.25

4.31
5.93

6.00
8.25
9.75
11.30
10.00

13.80
16.30

1.40
2.60

3.20
6.10
8.60
11.00
8.80

17.00
23.00

Calculated
Minimum
Sectional Area Breaking Load
mm2
kN
9.43
17.82

21.99
41.58
58.07
77.28
59.70

112.90
157.60

11.70
22.20

26.00
49.00
68.70
91.30
70.50

133.00
186.00

Australian Standard Metric Conductors

Reference Tables

SC/AC - Steel Conductor / Aluminium Clad - AS1222

Strands/Wire
Diameter mm

Overall
Diameter
(Approx)
mm

Calculated
Equivalent
Aluminium
Area mm2

3/2.75
3/3.00
3/3.25
3/3.75
7/2.75
7/3.00
7/3.25
7/3.75
7/4.25
19/2.75
19/3.00
19/3.25
19/3.75
19/4.25

5.93
6.47
7.00
8.08
8.25
9.00
9.75
11.30
12.80
13.80
15.00
16.30
18.80
21.30

5.91
7.03
8.26
11.00
13.70
16.30
19.20
25.50
32.80
37.10
44.10
51.80
68.90
88.60

17-8

Calculated
Minimum
Sectional Area Breaking Load
kN
mm2
17.82
21.21
24.89
33.12
41.58
49.48
58.07
77.28
99.33
112.90
134.30
157.60
209.80
269.60

www.dulmison.com.au

22.70
27.00
31.60
39.30
50.10
59.70
69.90
86.90
105.00
136.00
162.00
189.00
236.00
286.00

Stranding

O.D.
Inches

3/.080
3/.104
7/.064
7/.080
7/.104
7/.128
7/.144
19/.080
7/.160
19/.104
19/.128

0.172
0.224
0.192
0.240
0.312
0.384
0.432
0.400
0.480
0.520
0.64

Reference Tables

Australian Standard Metric Conductors


HDC Hard Drawn Copper Conductor - AS1746

Metric

Imperial

Strands/Wire
Diameter mm

Overall
Diameter
(Approx)
mm

Calculated
Equivalent
Aluminium
Area mm2

7/1.00
7/1.25
7/1.75
7/2.00
7/2.75
19/1.75
19/2.00
7/3.50
7/3.75
37/1.75
19/2.75
19/3.00
37/2.50
37/2.75
37/3.00
61/2.75

3.00
3.75
5.25
6.00
8.25
8.75
10.00
10.50
11.30
12.30
13.80
15.00
17.50
19.30
21.00
24.80

8.68
13.60
26.60
34.70
65.30
71.70
93.60
106.00
121.00
139.00
177.00
211.00
284.00
344.00
409.00
566.00

Calculated
Minimum
Sectional Area Breaking Load
mm2
kN
2.32
3.59
6.89
8.89
16.20
18.30
23.60
25.40
28.80
35.60
43.10
50.80
70.30
83.90
98.90
138.00

O.D.
Inches

7/036
7/048
7/064
7/080
19/064
7/118
7/136
19/083

37/072

19/116
37/093
37/103
37/118
91/093

0.108
0.144
0.192
0.240
0.320
0.354
0.408
0.415

0.504

0.580
0.651
0.721
0.826
1.023

Reference Tables

5.498
8.589
16.840
21.990
41.580
45.700
59.700
67.350
77.280
88.990
112.900
134.300
181.600
219.800
261.600
362.300

Stranding

www.dulmison.com.au

17-9

Reference Tables

Australian Standard Metric Conductors


HV ABC Non Metallic Screened Cables - AS3599

Conductor

Conductor Screen
Support Conductor
xlpe insulation
Phase Cable

Insulation

11kV
Phase

Reference Tables

Insulation Screen
Thickness Thickness
Size
mm
mm
35
50
70
95
120
150
185

3.4
3.4
3.4
3.4
3.4
3.4
3.4

1.0
1.0
1.0
1.0
1.0
1.0
1.0

AAAC/1120 Support Conductor (Catenary)


Phase
Cable
Dia.
mm

No. & Nominal Dia.


of Wires in
Conductor prior to
Compaction

18
19
21
23
24
26
27

7/5.00
7/5.00
7/5.00
7/5.00
19/3.65
19/3.65
19/3.65

Bundled
Cable Dia.
Compacted
Conductor
Calculated
Dia.
Breaking Load Circumscribing
Circle mm
mm
kN
14.1 - 14.4
14.1 - 14.4
14.1 - 14.4
14.1 - 14.4
17.3 - 17.7
17.3 - 17.7
17.3 - 17.7

27.1
27.1
27.1
27.1
41.7
41.7
41.7

51
53
56
60
66
69
72

22kV
Phase
Insulation Screen
Thickness Thickness
Size
mm
mm
35
50
70
95
120
150
185
17-10

5.5
5.5
5.5
5.5
5.5
5.5
5.5

1.0
1.0
1.0
1.0
1.0
1.1
1.1

AAAC/1120 Support Conductor (Catenary)


Phase
Cable
Dia.
mm

No. & Nominal Dia.


of Wires in
Conductor prior to
Compaction

23
24
25
27
29
30
32

7/5.00
7/5.00
7/5.00
7/5.00
19/3.65
19/3.65
19/3.65

Bundled
Cable Dia.
Compacted
Conductor
Calculated
Dia.
Breaking Load Circumscribing
Circle mm
mm
kN
14.1 - 14.4
14.1 - 14.4
14.1 - 14.4
14.1 - 14.4
17.3 - 17.7
17.3 - 17.7
17.3 - 17.7

www.dulmison.com.au

27.1
27.1
27.1
27.1
41.7
41.7
41.7

59
62
65
68
75
78
82

Reference Tables

Australian Standard Metric Conductors


HV ABC Metallic Screened Cables - AS3599

Conductor

Conductor

Conductor Screen
Insulation (XLPE)

Conductor Screen

Semiconductive
Insulation Screen
Metallic Screen
Separator tape
Sheath
Support Catenary

Insulation XLPE
Insulation Screen
Water swellable tape
Metallic screen (copper wire)
Separator tape
Sheath (HDPE)

11kV

Insulation Screen
Thickness Thickness
Size
mm
mm
35
35
50
70
95
120
150
185

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

Support Catenary
Phase
Cable
Dia.
mm
24
24
25
27
29
31
32
34

Bundled
Cable Dia.

No. & Nominal Dia. Calculated


Breaking Load Circumscribing
of Wires in
Circle mm
kN
Conductor
7/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00

26
70.5
70.5
70.5
70.5
70.5
70.5
70.5

58
54
62
66
69
72
75
78

Reference Tables

Phase

22kV
Phase
Insulation Screen
Thickness Thickness
Size
mm
mm
35
35
50
70
95
120
150
185

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

0.8
0.8
0.8
0.8
0.8
0.8
1.0
1.0

Support Catenary
Phase
Cable
Dia.
mm
28
28
29
32
33
35
37
39

Bundled
Cable Dia.

No. & Nominal Dia. Calculated


Breaking Load Circumscribing
of Wires in
Circle mm
kN
Conductor
7/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00
19/2.00

www.dulmison.com.au

26
70.5
70.5
70.5
70.5
70.5
70.5
70.5

67
63
71
75
78
81
85
88
17-11

Reference Tables

Units

Conductor Size and Type

Reference Tables

www.dulmison.com.au

Characteristics

Nominal cross-sectional area


mm2
80
120
180
Stranding and nominal wire diameter No./mm
7/3.75
7/4.75
19/3.50
Material
AAAC/1120 or AAAC/6201 or AAAC/1350
Approximate conductor diameter*
mm
11.3
14.3
17.5
Voltage rating
kV
6.35/11
12.7/22
19.1/33
6.35/11
12.7/22
19.1/33
6.35/11
12.7/22
19.1/33
Covering thickness:
(a) Minimum average
mm
3.40
5.50
8.00
3.40
5.50
8.00
3.40
5.50
8.00
(b) Minimum at any point
mm
2.96
4.85
7.10
2.96
4.85
7.10
2.96
4.85
7.10
(c) Maximum at any point
mm
4.00
6.40
9.30
4.00
6.40
9.30
4.00
6.40
9.30
Resultant overall diameter range*
mm 17.9 to 19.4 22.1 to 24.2 27.1 to 30 20.9 to 22.4 25.1 to 27.2 30.1 to 33.0 24.1 to 25.7 28.3 to 30.5 33.3 to 36.3
Approximate mass#
kg/km
450
635
900
640
845
1145
870
1105
1440
Colour code
Red
Red
Red
Yellow
Yellow
Yellow
Blue
Blue
Blue

Australian Standard Metric Conductors

17-12

Technical Requirements for Covered Conductors (CCT)

Reference Tables

Cross
Section
Area
Strand No./Wire O.D. of
mm2
Diameter mm
Cond.
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

1/1.13
7/0.40
1/1.3
7/0.50
7/0.67
7/0.85
7/1.04
7/1.35
7/1.70
19/1.35
19/1.53
19/1.7
19/2.14
37/1.7
37/2.03
37/2.25
37/2.52
61/2.25
61/2.52
61/2.85
61/3.20
127/2.52

1.13
1.20
81.38
1.5
2.01
2.55
3.12
4.05
5.1
6.75
7.65
88.9
10.7
812.46
14.21
15.75
17.64
20.25
22.68
25.65
28.8
32.76

O.D. of O.D. of
PVC
PVC Ins. O.D. of
Single
Single
Single
Core
Core
Core
Cable Sheathed Xlpe/PVC

Two
Core

Two
Core
+
Earth

Three
Core
+
Earth

Four
Core
+
Earth

2.8

4.1

3.2

4.4

9.4

3.7
4.6
5.2
6.1
7.2
8.9
10.1
11.9
13.5
15.9
17.4
19.5
-

5.1
6
6.6
8.1
9.3
-

11.4
12.6
14.1
16
18.2
20
22.2
24.4
27.4
30.3
33.8
35.7
40.2

10.8
12.2
13.4
-

16.6
18.6
22.1
24.4
28
31.5
-

18.1
20.4
23.8
26.5
30.6
34.8
39.6
43.3
48.4
53.7
61
67.6
-

20
22.6
26.5
29.5
34.3
39
44.6
48.8
54.6
60.7
69.1
76.6
-

www.dulmison.com.au

17-13

Reference Tables

Nominal Cable Dimensions

Reference Tables

Cable Cross Sections

Annealed Aluminium and Copper Stranded Conductors


Metric

Imperial

Reference Tables

Number and Nominal


Nominal Cross
Nominal
Diameter Nominal Cross
Sectional Area
Diameter
of Cond. Sectional Area
mm2
of Wires
mm
mm2
1

1.5

2.5

10

16

25
35

50

70

95
120
150

185

240

300

400

500
630

800
1000
17-14

1/1.13

1/1.38

7/0.67

7/0.85

7/1.04

7/1.35

7/1.70

7/2.14
19/1.53

19/1.78

19/2.14

19/2.52
37/2.03
37/2.25

37/2.52

61/2.25

61/2.52

61/2.85

61/3.20
127/2.52

127/2.85
127/3.20

1.13

1.38

2.01

2.55

3.12

4.05

5.10

6.75
7.65

8.90

10.7

12.60
14.21
15.75

17.64

20.25

22.80

25.65

28.80
32.76

37.05
41.60

0.97
1.25

1.93

2.93

4.52

6.75
9.43

14.28

18.29
25.5

38.7

65.1

75.3
95.3
126.7

159.1

195.1

262.2

321.6
391.1

479.7

669.4
800
1000

Number and
Nominal Diameter
of Wires
Inches
mm
1/.044
3/.029

3/.036

7/.029

7/.036

7/.044
7/.052

7/.064

19/.044
19/.052

19/.064

19/.083

37/.064
37/.072
37/.083

37/.093

37/.103

61/.093

61/.103
91/.093

91/.103

127/.103
127/.112
127/.125

www.dulmison.com.au

1/1.12
3/.737

3/.914

7/.737

7/.914

7/1.12
7/1.32

7/1.63

19/1.12
19/1.32

19/1.63

19/2.11

37/1.63
37/1.83
37/2.11

37/2.36

37/2.62

61/2.36

61/2.62
91/2.36

91/2.62

127/2.62
127/2.84
127/3.18

Nominal
Nominal Cross
Diameter
Sectional Area of Conductor
inches2
mm
0.0015
0.0019

0.0030

0.0045

0.0070

0.0100
0.0146

0.0025

0.0300
0.0400

0.0600

0.1000

0.1200
0.1500
0.2000

0.2500

0.3000

0.4000

0.5000
0.6000

0.7500

1
1.2400
1.5000

1.12
1.59

1.97

2.21

2.74

3.35
3.96

4.88

5.59
6.60

8.13

10.50

11.40
12.80
14.80

16.50

18.30

21.30
23.50
26

28.80

34
36.92
41.34

Reference Tables

Conversion Tables for Non-Metric Cable Sizes

33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
10

0.0507
0.0591
0.0682
0.0779
0.0937
0.0111
0.0136
0.0164
0.0203
0.0245
0.0292
0.0397
0.0519
0.0657
0.81
1.17
1.59
2.08
2.63
3.24
4.29
5.48
8.30

Imperial
Inches2

Metric
Equivalent
mm2

0.001
0.0015
0.002
0.003
0.0032
0.0045
0.007
0.01
0.0145
0.0225
0.03
0.04
0.06
0.075
0.1
0.12
0.15
0.2
0.25
0.3
0.4
0.5
0.6
0.75
0.85
1.0
1.25
1.5

0.657
0.981
1.28
1.97
2.08
2.98
4.6
6.81
9.59
14.5
18.6
26
39.4
49.9
66.3
76.8
97.2
129
162
199
267
328
399
489
557
683
807
1050

American
Metric
Metric
American
Wire Gauge Equivalent Wire Gauge Equivalent
AWG
mm2
mm2
AWG
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
2/0
3/0
4/0

www.dulmison.com.au

0.0507
0.0645
0.0806
0.102
0.128
0.163
0.205
0.259
0.324
0.412
0.519
0.652
0.826
1.04
1.31
1.65
2.08
2.63
3.31
4.17
5.26
6.63
8.37
10.6
13.3
16.8
21.2
26.7
33.6
42.4
53.5
67
85
107

250 MCM
300 MCM
350 MCM
400 MCM
450 MCM
500 MCM
550 MCM
600 MCM
650 MCM
700 MCM
750 MCM
800 MCM
850 MCM
900 MCM
950 MCM
1000 MCM
1100 MCM
1200 MCM
1300 MCM
1400 MCM
1500 MCM
1600 MCM
1700 MCM
1800 MCM
1900 MCM
2000 MCM
-

127
152
177
203
228
253
279
304
329
355
380
405
431
456
481
507
557
608
659
709
760
811
861
912
963
1010
-

Reference Tables

Metric
British Equivalent
Standard
mm2

17-15

Reference Tables

Reference Tables

Notes

17-16

www.dulmison.com.au