Sie sind auf Seite 1von 1

1021-0020, Rev 01

Use the wiring diagram and illustration to assemble a communication cable for use with a
Siemens SIMATIC TI505 PLC.
C A B L E A S S E M B L Y I N S T R U C T I O N
Controller Model: Siemens SIMATIC TI505
Maple OIT Model: MAP460D, OIT3600B
Communication Type: RS-232 with DB25 connector at PLC
10
COM
RXD
TXD
+24V
3
9
2
1
TB1
Black
Green
White
Red
Shield
OIT
PLC
To Chassis Ground
Black
Green
Shield
Black
Red
+24V
GND
Power Supply
RXD 3
DTR 20
DCD
DSR
8
6
CTS
RTS 4
5
Signal Ground
25P
7
TXD 2
PLC END
OIT END
18 AWG Green wire
2 Conductor, 22 AWG
Shielded Cable
Power Supply
To Chassis Ground
4 Conductor, 24 AWG
Shielded Cable
3/8" Heatshrink
Tubing
Shield
3/32" Heatshrink
Tubing
1
4-40 x 1/2 Retainer
Screws, 2 places
DB25P
Connector
Pin 1
DB25 Backshell
Twist together 18 AWG green wire and
shield wire. Solder wires and insulate
with heatshrink tubing to avoid shorting.
Install heatshrink on shield (bare wire)
to avoid shorting to components.
1
NOTES:
2
2
1