Sie sind auf Seite 1von 3

Branch

From Bus

To Bus

1
2
3
4
5
6
7

1
1
2
2
2
3
4

2
3
3
4
5
4
5

Se tiene datos en p.u.


SBASE
100

(MVA)

VBASE

230

(kV)

IBASE

0.251

(kA)

Z BASE =

( V BASE )

S BASE
o
ZL

Z p.u. =

Z BASE

()

(p.u)

Y =

G + jB

(S)

Z BASE =

529

()

Y BASE =

(1/Z BASE )

(S)

Y BASE =

0.001890359

(S)

1.00E-06 S =

Branch

Tabla 3 Datos de Lineas en p.u.


Impedance
Resistance R Reactance jX Line Charching Line Charching
Y/2 (p.u)
Y (p.u)
(p.u)
(p.u)
0.02
0.06
0.03
0.06
0.03
0.24
0.025
0.05
0.06
0.18
0.02
0.04
0.06
0.18
0.02
0.04
0.04
0.12
0.015
0.03
0.01
0.03
0.025
0.05
0.08
0.24
0.025
0.05

1 uS

From Bus

Tabla 3 Datos de Lineas en unidades reales


Impedance
To Bus
Resistance
Reactance Line Charching Rated Current
B (uS)
(kA)
()
()

1
2
3
4
5
6
7

1
1
2
2
2
3
4

2
3
3
4
5
4
5

10.58
15.87
31.74
31.74
21.16
5.29
42.32

31.74
126.96
95.22
95.22
63.48
15.87
126.96

113.42
94.52
75.61
75.61
56.71
94.52
94.52

0.251
0.126
0.126
0.126
0.126
0.126
0.126

Flow Limit
(MW)
100
50
50
50
50
50
50

Das könnte Ihnen auch gefallen