An inspection report documents an anomaly found on July 10, 2008 at 2:38pm on structure 391 of line XYZ-123 for client ABC Power & Light. The inspection found a non-tension splice on the bottom phase low side jumper loop with a temperature rise of 52°C above ambient, deemed a serious issue rated as a severity level II.
An inspection report documents an anomaly found on July 10, 2008 at 2:38pm on structure 391 of line XYZ-123 for client ABC Power & Light. The inspection found a non-tension splice on the bottom phase low side jumper loop with a temperature rise of 52°C above ambient, deemed a serious issue rated as a severity level II.
An inspection report documents an anomaly found on July 10, 2008 at 2:38pm on structure 391 of line XYZ-123 for client ABC Power & Light. The inspection found a non-tension splice on the bottom phase low side jumper loop with a temperature rise of 52°C above ambient, deemed a serious issue rated as a severity level II.
Picture Number: 31 Time of Inspection: 14:38z Located on Video: 071008-001 Anomaly Description: Bottom Phase, Low Side Jumper Loop Non-Tension Splice Structure 391 Anomaly Location: Line XYZ-123 Additional Information: None
Problem Area Temperature: 76 C Ambient Area Temperature: 24 C Total Temperature Rise: 52 C
Severity of Problem: II (Serious)
CONFIDENTIAL Infrared Trouble Shooting Report
Weather Conditions Sunny Wind Velocity (Knots) 230 @ 7 Line Load (Amps) 126 Distance to Target (Feet) 25
Prepared By: Christopher M. Cox Certification: 3422 Repaired By:________________________________ Comment:_______________________ Date: ___/___/___