Calculation of Load Drop Compensation Settings

Substation: Moruya North

Inputs Outputs
Full Load Voltage 1.05 p.u.
Light Load Voltage 1.03 p.u. Float voltage @ no load 111.9 volts
Full Load 22 MW = 33.58 kV
Light Load 5 MW
Power Factor 0.95 Settings
CT primary 600 A for R only 1.08 ohms
CT secondary 5 A X only -5.15 ohms
CT phase Yellow R=X 1.36 ohms
VT primary 33000 volts Note : These settings are not actual dial settings
VT secondary 110 volts
VT connections Y-R

2351413.xls 03/22/2008
Calculation of % Boost for Known LDC settings

Substation: Moruya North

Inputs Outputs
Resistance (R) 1.08 ohms
Reactance (X) ohms Voltage boost @ full load
Float Voltage @ no load 111.9 volts (above nominal) 5.0 %
Full Load 22 MW
Light Load 5 MW Volts @ Light load 1.025 p.u.
Power Factor 0.95
CT primary 600 A
CT secondary 5 A
CT phase Yellow
VT primary 33000 volts
VT secondary 110 volts
VT connections Y-R

_ Boost 2351413.xls 03/22/2008