NAPIT Periodic Report on an existing Electrical Installation

Requirements for Electrical Installations – BS 7671 [IEE Wiring Regulations] NA/PIR 0000000000
Only for the reporting on the condition of an existing installation Page 1 of 4

Details of the installation

A Owner*/Occupier*/Customer*/ (*Delete as necessary)


Address C D SMITH
Installation HILL HOUSE
Address 47 HIGH STREET
47 HIGH STREET OLD TOWN
OLD TOWN
Postcode A21 BY2 Postcode A21 BY2

Purpose of the report This form to be used only for reporting on the condition of an existing installation.

B CHANGE OF OWNERSHIP
Purpose for which this report is required

Details of the installation

C n n
Domestic
3
Commercial
n
Industrial Other (please state)

Estimated age of the electrical installation n


Description of premises

Evidence of alterations or addition n Yes n No n


15 years
3 If ‘Yes’, estimated 5 years

E n Yes n3 No
Date of previous inspection N/A/ / Electrical Installation Certificate No. or previous Periodic Inspection Report No. N/A
Records of installation available Records held by NONE

L
Extent of electrical installation covered by this report (note 4)
ELECTRICAL INSTALLATION TO HOUSE AND GARAGE

Limitations

MP
NO REMOVAL OF FLOOR COVERING IN ATTIC OR BUILT-IN UNITS IN KITCHEN AND BEDROOMS

D A
This inspection has been carried out in accordance with BS 7671:

S
Periodic Inspection Summary
Date(s) of the inspection from
General conditions of the Installation
12 / 01 / 2006 to
n
2001 (IEE Wiring Regulations), amended to n

30 / 01 / 2006
POOR CONDITION DUE TO AGE OF PROPERTY, IMPROVEMENTS AND RECTIFICATION OF LISTED DEFECTS.
2004 (date)
Cables concealed within the trunkings and conduits, and/or cables and conduits concealed under floors, in roof spaces and generally
within the fabric of the building or underground have not been inspected.

n
Unsatisfactory 3 n
n
Overall assessment Satisfactory
We recommend that this installation is further inspected and tested after an interval of not more than 10 months/years, provided
that any observations ‘requiring urgent attention’ are attended to without delay.

Declaration

E To the best of our knowledge and belief we confirm that the details recorded in this report, including any attached schedules and the
recommendations are an accurate assessment of the condition of the Electrical Installation within the limitations described in Section C.
DECLARATION: To the best of our knowledge the details recorded in this report are an accurate indication of the Electrical Installation with
Inspection findings listed in the attached schedules.
© Copyright NAPIT July 2005

Name A B BROWN LTD Signature


Inspector
Address
A B BROWN A B Brown
21 NEW ROAD Position
OLD TOWN INSPECTOR
Date 25/01/2006
Postcode AB1 CD2 NAPIT Membership No. 66332211

NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL Sheet 1 of 4 NA/PIR/001 (V1)
NAPIT Periodic Report on an existing Electrical Installation
Requirements for Electrical Installations – BS 7671 [IEE Wiring Regulations]

NOTES: NAPIT Periodic Report


1. This Periodic Report shall only be used for the Information for recipients (to be appended to the
reporting on the condition of an existing report).
installation. This Periodic Report shall only be used for the
2. This Report, normally comprising of at least four reporting on the condition of an existing installation.
pages and shall include an Inspection Schedule You should have received an original Report and the
and a Test Result Schedule. Additional Report and contractor should have retained a duplicate. If you
Test Sheets should be added as necessary. All were the person ordering this Report, but not the
additional pages shall be incorporated within the owner of the installation, you should pass this Report,
page numbering sequence to show, page number or a copy of it, immediately to the owner.
and total number of pages. The individual Periodic The original Report is to be retained in a safe place
Report Number shall appear on each additional and be shown to any person inspecting or
sheet to indicate the report it relates to. undertaking work on the electrical installation in the
3. The maximum prospective fault current recorded future. If you later vacate the property, this Report will
should be the greater of either the short circuit provide the new owner with details of the condition of
current or the earth fault current. the Electrical Installation that it refers to.
4. The ‘Extent and Limitations’ box shall fully identify The ‘Extent and Limitations’ box should fully identify
the elements of the installation that are covered by the extent of the installation covered by this Report
the report and those that are not, this aspect and any limitations on the inspection and tests. The
having been agreed with the client, or other Inspector should have agreed these aspects with you
interested parties before the final inspection and before the inspection was carried out.
testing is carried out. For safety reasons, the electrical installation will need
5. The time interval recommended for the next to be re-inspected at appropriate intervals by a
periodic inspection and testing shall be given. The competent person. The maximum recommended
IEE Guidance Note 3 provides guidance on the time interval before the next inspection is stated in the
maximum interval between inspections for various Report under ‘Next Inspection’. i.e. the Institute of
types of buildings. i.e. every 10 years or on change Electrical Engineers recommend every 10 years or on
of occupancy for Domestic Electrical Installations. change of occupancy for Domestic Electrical
6. This Periodic Report is based upon the format of Installations.
the Periodic Inspection Report for an Electrical The Report is only valid if an Inspection Schedule And
Installation, issued by the Institute of Electrical Schedule of Test Results are appended.
Engineers and published in BS7671:2001. The Report will usually contain a list of recommended
actions necessary to bring the installation up to the
current standard.
For items classified as ‘requires urgent attention’,
the safety of those using the installation may be at
risk, and it is recommended that a competent
person undertakes the necessary remedial work
without delay.
NAPIT Periodic Report on an existing Electrical Installation
Requirements for Electrical Installations – BS 7671 [IEE Wiring Regulations] NA/PIR 0000000000
Can be used for the reporting on the condition of an existing installation only. Page 2 of 4

F n n n n n
Supply characteristics and earthing arrangements
Supply systems TN-S 3 TN-C-S TT Number & type of live conductors 1-phase, 2 wire 3 3-phase, 4 wire

n 230 n v Normal frequency, f n


Nature of Supply Parameters Note: (1) by enquiry* or by measurement*, (2) by enquiry* or by measurement* (*Delete as necessary)

Prospective fault current, Ipf (note 3)n External loop impedance, Ze n


Normal voltage, U/Uo
(1)
50 (1)
Hz

Supply Protective Device Characteristics Typen Nominal Current Rating n Max Demand n
(2)
16 kA 0.12 V
(2)

1361 60 N/V
Means of Earthing Distributor’s facility n 3 Installation earth electrode n
A A

Type (e.g. rod(s), tape etc) n


N/A nn
Location n N/A nn Electrode resistance to earth nN/A nV
Details of Installation Earth Electrode (where applicable)

Main Protective Conductors Material Csa (mm2) Verified Location


3

E
Main Earthing COPPER 10 DB CUPBOARD
3
Water n3 Gas n Oil n Steel structure n Other services n N/A n
Main equipotential bonding COPPER 6 UNDERSTAIRS
Incoming Services Verified 3

BS:Type n 60947/3 Location n nn No. of Poles n Fuse or Settingn Current ratingn

L
Main Switch or Circuit Breaker
DB CUPBOARD 2 N/A 100A
Voltage ratingn
230 Rated residual operating current IDn = n N/A mA and operating time of nN/A ms (at IDn)

P
(applicable only where an RCD is suitable and is used as a main circuit-breaker)

Gn
Observations and recommendations for actions to be taken Explanation of codes

n
Referring to the attached schedule of inspection and test results, and subject to the limitations at Section C. 1. Requires urgent attention
3 The following observations and

M
2. Requires improvement
No remedial work required OR
3. Requires further investigation
recommendations are made 4. Does not comply with
BS 7671: 2001 (as amended)

A
Item No. Defect details Code

1 MAIN EQUIPOTENTIAL BONDING CONDUCTORS HAVE CROSS SECTIONAL AREA BASED ON


PREVIOUS EDITION OF IEE REGS 4

5
S
NO RCD PROTECTION FOR SOCKETS ACCESSIBLE FOR EXTERNAL USE

DAMAGED LAMPHOLDER IN BEDROOM

INCORRECT PROTECTIVE DEVICE FITTED FOR WATER HEATER

NO SUPPLEMENTARY BONDING CONDUCTORS BETWEEN SHOWER AND WATER PIPES IN BATHROOM


1

6 NO GREEN AND YELLOW SLEEVING ON CPCS AT SOCKETS 2

7 NO PHASE IDENTIFICATION ON BLACK CONDUCTORS USED AS SWITCHLINES 2

8 NO LABELS INDICATING PRESENCE OF TWO WIRING COLOURS 2

9 NO SMOKE DETECTORS INSTALLED 2


© Copyright NAPIT July 2005

Note: For additional report pages use the continuation report form with the relevant serial number and page numbers detailed on each page.
Urgent remedial work recommended for items 2, 3, 4, 5
Corrective action(s) recommended for items 1, 5, 6, 7, 8, 9

NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL Sheet 2 of 4 NA/PIR/001 (V1)
NAPIT Periodic Report on an existing Electrical Installation
Requirements for Electrical Installations – BS 7671 [IEE Wiring Regulations] NA/PIR 0000000000
Can be used for the reporting on the condition of an existing installation only. Page 3 of 4

H nnn
1 to nnn
Schedule of Inspections
2
nnn
N/A to nnn
Schedule of Inspection Reports: Page no(s)

N/A
Schedule of Circuit and Test Results for the Periodic Inspection Page no(s) nnn
4 to nnn
Additional pages, including additional source(s) data sheets: Page no(s)

4
The attached Schedules are part of this document and this Report is valid only when they are attached to it.
Inspected Schedule of Inspections
N/A If previous certificate or reports exists have there been any alterations
3 Inspection of Incoming Supply and equipment
3 Main System Earth Conductor is present, securely connected and a warning label fitted
7
n n n
Main System Earth Conductor of the correct size
3 Main Equipotential Bonding Conductors present at: Gas 3 Water 3 Other N/A

E
7 Main Equipotential Bonding Conductors correctly sized
3 Main Equipotential Bonding Conductors securely connected and a warning label fitted
3

L
Consumer Unit position accessible
7 Correct Circuit Protection Devices fitted and identified for each circuit
3 Correct Cable type and size used, allowing for external influences
3

P
Cable run in ‘safe’ zones or mechanically protected (where readily accessible to inspect)
3 Cables securely fastened or in appropriate wiring protection systems (where readily accessible to inspect)
7 All Cable cores correctly identified at joints and in accessories (at samples inspected)
3 All cable joints correctly terminated, secure and accessible (at samples inspected)
3

M
Modifications to the Building Fabric appropriate and safe (Structure) (where readily accessible to inspect)
3 Modifications to the Building Fabric appropriate and safe (Fire) (where readily accessible to inspect)
N/A All Accessories correctly placed as per Approved Document M and BS 8300 (where applicable)
7 Appropriate Supplementary Bonding present and adequately sized

A
7 Supplementary Bonding securely connected and a warning label fitted if required
7 High Shock Risk Circuits are protected by a 30mA RCD
3 All Accessories have environmental protection appropriate for external influences
3

S
All covers replaced, Accessories secure and neatly aligned
N/A The number of points and their location agree with the original design (if available)
3 Original circuit details correct on the installation schedule
7 Periodic Label, RCD label and other Safety Labels fitted
7 If installation has wiring colours of two versions to BS 7671, has warning label been fitted?
7 Appropriate measures taken in Special Locations
7 Smoke Detection units installed
N/A Other (please state)
N/A Other (please state)
N/A Other (please state)
N/A Other (please state)
N/A Other (please state)
N/A Other (please state)

Schedule of Test
3 External earth loop impedance 3 Insulation Resistance between Live conductors
N/A Installation earth electrode 3 Insulation Resistance between Live conductors & earth
3 Prospective short circuit current 3 Polarity
3 Continuity of Earth Conductors 3 Earth fault loop impedance
3 Continuity of Circuit Protective Conductors 7 Residual current devices
3 Continuity of Supplementary Bonding Conductors 3 Functional testing of devices
© Copyright NAPIT July 2005

The sections above are –


Yes (Y), No (N), Not Known (N/K), Satisfactory (3), Not Satisfactory (X), Not Checked (N/C), Not Applicable (N/A) or Limitations (Lim)
Inspector’s Name A B BROWN
Signature A B Brown Date 30/1/2006

NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL Sheet 3 of 4 NA/PIR/001 (V1)
This sheet forms part of Report Number
NAPIT Electrical Test Sheet
Requirements for Electrical Installations – BS 7671 [IEE Wiring Regulations] NA/PIR 0000000000
Can be used for the reporting on the condition of an existing installation only. Please complete all the unshaded areas.
Page 4 of 4
C D SMITH 47 HIGH STREET, OLD TOWN
i
Client Address Postcode AZ1 BY2
Complete in every case Complete only if the distribution board is not connected directly to the origin of the installation Test instrument number

SA
Location of MAINS Supply to distribution No. of Nominal V Characteristics at this distribution board Earth fault loop imped.
N/A 1 230 321
distribution board CUPBOARD board is from phases Voltage
Distribution board Overcurrent protective device Associated RCD Ze V Operating At IDn ms Continuity 321
designation DB1 for the distribution circuit: (if any): BS (EN) N/A 0· 1 2 times of N/A
Insulation resistance 321
Number of ways Type Rating A RCD IDn mA Ipf k associated at 150 mA ms
16 SPN N/A N/A N/A N/A 16 A RCD(if any)
N/A RCD 321
BS(EN) No of
Poles

CIRCUIT DETAILS TEST RESULTS


Overcurrent

current IDn
RCD operating
BS7671

time (BS:7671)
disconnection
Maximum
Circuit conductors

J protective devices Max. Continuity Insulation resistance RCD testing


csa
Type of wiring

permitted
No. of points
BS:Type 60898
Ref. method

CPC (mm2)
value Zs Between

Figure 8
Live (mm2)
Maximum

Polarity
and phase
Circuit No.

check
Short Other Ring final circuits only All circuits to be Date live Phase / Neutral / measured Date
Type Rating circuit Zs at IDn
served

No.
capacity 80 (measured end to end) complete of test conductors Earth Earth of test X5

Circuit description (S) (A) (kA) (mA) V r1 rN r2 (3) R1+R2 R2 (Dead) (MV) (MV) (MV) (3) (V) (Live) ms ms

900+ 3 1· 0 3

MP
1 LOUNGE LTG A 1 4 1·5 1·0 5 B 6 10 N/A 6 · 4 N/A N/A N/A N 0· 9 1 0· 4 6 25/1 900+ 900+ 25/1 N/A N/A
2 KITCHEN LTG A 1 6 1·5 1·0 5 B 6 10 N/A 6 · 4 N/A N/A N/A N 0· 6 4 0· 3 2 25/1 900+ 900+ 900+ 3 10· 7 6 25/1 N/A N/A
3 BED & BATH LTG A 1 10 1·5 1·0 ·4 B 6 10 N/A 6 · 4 N/A N/A N/A N 0· 5 2 0· 2 6 25/1 900+ 900+ 900+ 3 0· 6 4 25/1 N/A N/A
4 KITCHEN SOCKETS A 1 12 2·5 1·5 ·4 B 32 10 N/A 0 · 6 0· 1 6 0· 1 6 0· 2 7 3 0· 1 1 0· 0 6 25/1 900+ 900+ 900+ 3 0· 2 3 25/1 N/A N/A
5 DOWNSTAIRS SOCKETS A 1 16 2·5 1·5 ·4 B 32 10 30 0·6 0· 2 4 0· 2 4 0· 4 0 3 0· 1 6 0· 0 8 25/1 900+ 900+ 900+ 3 0· 2 8 25/1 24· 2 14· 4
6 UPSTAIRS SOCKETS A 1 14 2·5 1·5 ·4 B 32 10 N/A 0 · 6 0· 6 0 0· 6 1 1· 0 0 3 0· 4 0 0· 2 5 25/1 900+ 900+ 900+ 3 0· 5 2 25/1 N/A N/A
7 COOKER A 1 1 6 2·5 5 B 32 10 N/A 0 · 6 N/A N/A N/A N 0· 1 0 0· 0 5 25/1 900+ 900+ 900+ 3 0· 2 2 25/1 N/A N/A

LE

© Copyright NAPIT July 2005


Wiring Types: A PVC/PVC B Single insulated in conduit or trunking C Mineral Insulated D BS:7629-1 (FP200) E Xlpe/Swa F Other

NONE N/A of N/A

K
Comments on installation See attached sheets page(s)

Tested by: Name (capital letters) A B BROWN Signature A B Brown Position INSPECTOR Date(s) 25 / 01 /2006

NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL Sheet 4 of 4 NA/PIR/001 (V1)