Sie sind auf Seite 1von 1

TAC AB

TECHNICAL PRODUCT
INFORMATION
ERROR NOTIFICATION
Date: 17 Aug.-2005
Binder: Field E Valves
Ref No: D-40-40
Index: C-4
Author: WLC/rira
Approved: WLC/rira

1 (1)
This TPI replaces D-40-40 C-3

SHD100 / SHD100-T / SHD101-T5 / SHO100 / SHO100-T / SHO101-T5

We have received a number of cases where the electrical capacitor has exploded in the SHD sensors
if connected to AC. Sensors connected to DC works OK.
The following products are known to have this problem:

Product name Article
number
From
Production
date 1)

Production
week 2)
Until:
Production
date 1)

Production
week 2)
SHD100 00690232-0 2005-06-13 0524 2005-08-14 0532
SHD100-T 00690233-0 2005-06-13 0524 2005-08-14 0532
SHD101-T5 00690238-0 2005-06-13 0524 2005-08-14 0532
SHO100 00690236-0 2005-06-13 0524 2005-08-14 0532
SHO100-T 00690237-0 2005-06-13 0524 2005-08-14 0532
SHO101-T5 00690240-0 2005-06-13 0524 2005-08-14 0532
1) Date on box label
2) Production week on the product label

Replacement procedure

Note: All sensors, which are already powered and functional, should not be replaced.

Order new sensors from WLC, which will be invoiced. You will get a credit note when the defected
or not used sensors is send back to WLC. For those who already send defected sensors to WLC
there will not be any invoice, you will get an replacement product The hole replacement procedure
will take 3 to 4 weeks. During this period the delivery time will differ from normal.

Replacement should be done before 30
th
November 2005

The cause to malfunction
1) From manufacturing date of 14
th
of June 2005 a conventional wired diode was changed to a
SMD diode. The technical datas are fully equal, exceptional in one point, which is the
resistance against high switch-on-currents.
.
2) There was a malfunction in the final factory test equipment, which caused a to high switch-
on-current and stress the rectifier diode above its limitations.

This is relevant only for AC-applications. In DC-applications, independent on 0-10 V or 4-20 mA
output this problem can not happen.

Applying 24V AC, this is a destroying error, so that all Humidity transmitters, which are already
powered and in function, will work without influencing the measurement.