Ver.8.1.9. Control Valve Liquid Program - Calculate Valve Size


GC 01 - HP DRY/WET SEPERATOR # 1
Project . LCV REPLACEMENT .
Tag number GC01- 502B
Input Data
Valve
Data : 6 in Globe : Linear contour. Ports : One. Flow to : Close
Rated Cv : 76. Style Fd : 1
Pipe Sizes
Inlet : 6 in. Outlet : 6 in. Outlet pipe wall : 0.315 in
Fluid Data
Name : oil
Maximum Normal Minimum Units
Percent of nominal flow 150 50 36.11
Liquid flow 27000 9000 6500 bbl/d
Pressure drop 215 215 215 psi
Flow temperature 100 100 100 degF
Inlet pressure 280 280 280 psig
Vapor pressure 23.5 23.5 23.5 psia
Critical pressure 2500 2500 2500 psia
Viscosity @ FTP 11.5 11.5 11.5 cs
Specific gravity @ FTP .87 .87 0.87
Rated FL 0.94 0.94 0.94
Output Data
Required Cv 50.09 16.7 12.06 psi
Percent of valve lift 66 22 16
Cavitation index 1.2614 1.2614 1.2614
Noise level 84 79 77 dbA
Flow status Normal Normal Normal
Cavitation or Flashing None None None
Calculated FL .94 .94 .94
Sizing pressure drop 215 215 215 psi
Modified Volume English, data for all calculations, calculate size
Source - ANSI/ISA-75.01.01-2007 Flow Equations for sizing control valves
InstruCalc Ver.8.1.9.
Selection based on Masoneilan or equal Model 25100