0 Bewertungen0% fanden dieses Dokument nützlich (0 Abstimmungen)
372 Ansichten5 Seiten
The document summarizes air flow calculations for generator rooms on a FPSO. It provides the volume, maximum indoor and outdoor temperatures, and resulting heat dissipation and air flow calculations for the generator room and spare generator room. The calculations determine the supply air, extract air at 20% above supply to create negative pressure, and resulting air flows in m3/h and l/s.
The document summarizes air flow calculations for generator rooms on a FPSO. It provides the volume, maximum indoor and outdoor temperatures, and resulting heat dissipation and air flow calculations for the generator room and spare generator room. The calculations determine the supply air, extract air at 20% above supply to create negative pressure, and resulting air flows in m3/h and l/s.
The document summarizes air flow calculations for generator rooms on a FPSO. It provides the volume, maximum indoor and outdoor temperatures, and resulting heat dissipation and air flow calculations for the generator room and spare generator room. The calculations determine the supply air, extract air at 20% above supply to create negative pressure, and resulting air flows in m3/h and l/s.
w 6000 12 300 h 5000 l 10000 = 3600 m3/h m3 300 m2 60 Air flow = Cp (sepicifiq heat) x delta T x Spare Emergency Generator Room w 5000 Delta T = Max Troom - Max T out h 5000 35 - 24 l 9300 = 11 m3 232.5 m2 46.5 = 83 1.0090188 x 11 x (kJ/kg.K) K = 6 m3/s = 22434 m3/h Total = 26034 m3/h 20% = 31241 m3/h 8678 l/s Q gen set heat dissipation Air flow = ACH x room m3 12 233 = 2796 m3/h Air flow = air density Cp (sepicifiq heat) x delta T x air density Delta T = Max Troom - Max T out 35 - 24 = 11 kJ/s = 83 kJ/s 1.2 1.0090188 x 11 x 1.2 kg/m3 (kJ/kg.K) K kg/m3 = 6 m3/s = 22434 m3/h Total = 25230 m3/h 20% = 27753 m3/h 7709 l/s Q gen set heat dissipation Q gen set heat dissipation Air flow = ACH x room m3 12 233 = 2796 m3/h Air flow = Cp (sepicifiq heat) x delta T x air density Delta T = Max Troom- Max T out 59 - 39 = 20 = 120 kJ/s 1.009019 x 20 x 1.2 (kJ/kg.K) K kg/m3 = 5 m3/s = 17839 m3/h Total = 20635 m3/h 20% = 22699 m3/h 6305 l/s Q gen set heat dissipation QA2134 - Dana FPSO Room Volume Max outdoor air temperature Max indoor air temperature m C C Generator Room 300 24 35 Spare Genrator Room 232 24 35 Room Heat Dissipation kW m/h l/s m/h l/s 83 32568 9047 39082 10856 83 32560 9044 39072 10853 E-20 Calculation Supply Air + 20% Safety factor Extract Air = Supply Air + 20% (to make room negative pressure)