DOC. NO. 44LK-5100/E.

04/004A/A4
DATA SHEET FOR REQN.NO.
LIGHTING TRANSFORMER
APPD. BY VDV
44LK-5100 CHKD. BY VDV
MUMBAI PRPD. BY MSJ
DHT PROJECT DATE 28.02.09
CLIENT HPCL LTD. REV. 0
PART - A : SPECIFIC REQUIREMENTS
THIS DATA SHEET IS APPLICABLE FOR LIGHTING TRANSFORMER IN BOILER
A CLIMATIC CONDITIONS PACKAGE
1 DESIGN AMBIENT TEMPERATURE 45 C
2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS.
3 RELATIVE HUMIDITY 74 %
4 MAX. RAINFALL PER DAY
5 LOCATION OF INSTALLATION INDOOR
6 SITE ENVIRONMENT TROPICALIZED, MARINE, WITH PRESENCE OF CORROSIVE FUMES
B SYSTEM PARTICULARS
1 PRIMARY SYSTEM LIGHTING - DRY TYPE
1.1 VOLTAGE 0.415 kV 10%
1.2 FREQUENCY 50 Hz 5 %
1.3 COMBINED VOLTAGE & FREQUENCY 10 %
VARIATION
1.4 NO. OF PHASES / WIRE 3 PHASE / 3 WIRE
1.5 SYSTEM GROUNDING Solidly Grounded
1.6 FAULT LEVEL 50 kA 3 PH SYMM
2 SECONDARY SYSTEM
2.1 VOLTAGE 0.415 kV
2.2 NO. OF PHASES / WIRE 3 PHASE / 4 WIRE
2.3 SYSTEM GROUNDING SOLIDLY GROUNDED
C TECHNICAL PARTICULARS
1 RATING *
2 NO. OF PHASES THREE
3 NO LOAD VOLTAGE RATIO : 0.415 / 0.415 kV
PRIMARY/SECONDARY /ANY
4 VECTOR GROUP Dyn11
5 % IMPEDANCE : *
6 TYPE OF COOLING ANAN

PROJECT TITLE
PROJECT NO
PROJECT LOCATION

FORM NO. E 004 DS.xls
X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 1 OF 8
APPLICABLE STANDARD SPECIFICATION :44LK-5100-E.02-004 032
DATE : 3/18/2009 TIME : 3:35 PM
DOC. NO. 44LK-5100/E.04/004A/A4
DATA SHEET FOR REQN.NO.
LIGHTING TRANSFORMER
APPD. BY VDV
44LK-5100 CHKD. BY VDV
MUMBAI PRPD. BY MSJ
DHT PROJECT DATE 28.02.09
CLIENT HPCL LTD. REV. 0
PROJECT TITLE
PROJECT NO
PROJECT LOCATION
PART - A : SPECIFIC REQUIREMENTS ( CONTD...)
C TECHNICAL PARTICULARS ( CONTD..)
7 INSULATION LEVEL
a ) FOR IMPULSE TEST (KVP)
b ) FOR POWER FREQUENCY
WITHSTAND (RMS)
8 TEMPERATURE RISE :
a ) WINDING 90 C ABOVE AMBINET TEMPERATURE OF 45 C
b ) OIL NOT APPLICABLE
9 ADDITIONAL OUTDOOR BUSHING FOR
NEUTRAL EARTHING :
a ) FOR PRIMARY NOT REQUIRED
b ) FOR SECONDARY REQUIRED
c ) EARTH CONDUCTOR SIZE
10 TAP CHANGER : HV SIDE OFF LOAD
11 RANGE OF TAPS / STEPS :
12 ON LOAD TAP CHANGER : AUTO & MANUAL NOT APPLICABLE
13 PROTECTIVE BUSHING CT'S :
13.1 HV. SIDE : RATIO : NA
ACCURACY CLASS : NA
BURDEN : NA
13.2 LV. SIDE : RATIO : NA
ACCURACY CLASS : NA
BURDEN : NA
13.3 NEUTRAL SIDE: RATIO : NA
ACCURACY CLASS : NA
BURDEN : NA
14 MOUNTING OF CT's HV. SIDE : NA
LV. SIDE : NA
NEUTRAL : NA
D CONSTRUCTION
1 TERMINAL BOX ARRANGEMENT ; HV & LV OPPOSITE
2 PRIMARY TERMINAL TYPE CABLE BOX WITH DISCONNECTING CHAMBER
2.1 CABLE / CONDUCTOR SIZE : *
3 SECONDARY TERMINAL TYPE CABLE BOX WITH DISCONNECTING CHAMBER FOR LIGHTING TRANSFORMER

3.1 CABLE / CONDUCTOR / BUS BAR SIZE : *
4 RADIATORS NA
5 PAINTING : EPOXY PAINT SHADE NO. 632 AS PER IS : 5
6 FITTINGS & ACCESSORIES AS PER STD. SPECIFICATION. :44LK5100ESS-04
+/- 2.5 % IN STEPS OF 2.5 %
HV : - KV, LV : - KV
HV : 3 KV, LV : 3 KV
75 X 10 G.I EARTH STRIP





FORM NO. E 004 DS.xls
X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 2 OF 8
APPLICABLE STANDARD SPECIFICATION :44LK-5100-E.02-004 032
DATE : 3/18/2009 TIME : 3:35 PM
DOC. NO. 44LK-5100/E.04/004A/A4
DATA SHEET FOR REQN.NO.
LIGHTING TRANSFORMER
APPD. BY VDV
44LK-5100 CHKD. BY VDV
MUMBAI PRPD. BY MSJ
DHT PROJECT DATE 28.02.09
CLIENT HPCL LTD. REV. 0
PROJECT TITLE
PROJECT NO
PROJECT LOCATION
7 BIDIRECTIONAL RAILWHEEL / ROLLER RAIL WHEEL

E PERFORMANCE PARTICULARS AS SPECIFIED ELSEWHERE IN FEED DOCUMENT
F DRAWING, DATA & TEST AS SPECIFIED ELSEWHERE IN FEED DOCUMENT
CERTIICATES
G INSPECTION & TESTING AS PER INSPECTION TEST PLAN ATTACHED
ELSEWHERE.
H NOTES & ADDITIONAL REQUIREMENTS:
1) INSULATION SHALL BE CLASS H WITH TEMPERATURE RISE LIMITED TO CLASS F.
* - BOILER VENDOR TO SPECIFY
FORM NO. E 004 DS.xls
X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 3 OF 8
APPLICABLE STANDARD SPECIFICATION :44LK-5100-E.02-004 032
DATE : 3/18/2009 TIME : 3:35 PM
DOC. NO. 44LK-5100/E.04/004A/A4
DATA SHEET FOR REQN.NO.
LIGHTING TRANSFORMER
APPD. BY VDV
44LK-5100 CHKD. BY VDV
MUMBAI PRPD. BY MSJ
DHT PROJECT DATE 28.02.09
CLIENT HPCL LTD. REV. 0
PROJECT TITLE
PROJECT NO
PROJECT LOCATION
PART - B : PERFORMANCE PARTICULARS.
( TO BE FURNISHED BY MANUFACTURER )
THE PARTICULARS MARKED WITH ASTERISK ( * ) SHALL BE GUARANTEED , SUBJECT TO THE TOLERANCE
SPECIFIED IN IS - 2026
REF. 44LK5100ESS 004 UNIT
1 NAME OF THE MANUFACTURER .
2 TRANSFORMER DESIGNATION
3 QUANTITY NOS.
4 INSTALLATION
5 RATED KVA AS PER IS - 2026 KVA
6 CONTINUOUS MAXIMUM RATING FOR SITE
CONDITIONS SPECIFIED IN PART - A KVA
7 ( * ) NO LOAD VOLTAGE RATIO
8 VECTOR GROUP REFERENCE
9 ( * ) NO LOAD LOSSES AT RATED VOLTAGE * KW
10 ( * ) LOAD LOSSES AT RATED CURRENT , 75 C * KW
11 RESISTANCE VOLTAGE (AT RATED KVA,75C & 50 Hz) %
12 REACTANCE VOLTAGE (AT RATED KVA,75C & 50 Hz) %
13 ( * ) IMPEDANCE VOLTAGE ( AT RATED KVA, 75 C
& 50 Hz. ) * %
14 RESISTANCE OF WINDINGS , AT 75 C
a ) H.V. PER PHASE OHMS
b ) L.V. PER PHASE OHMS
15 WINDING INSULATION
16 ZERO PHASE SEQUENCE IMPEDANCE ( ESTIMATED ) %
17 EFFICIENCY ( AT 75 C ) AT FULL LOAD
a ) 1.0 P.F %
b ) 0.8 P.F. (LAG) %
18 EFFICIENCY ( AT 75 C ) AT 75 % OF FULL LOAD
a ) 1.0 P.F %
b ) 0.8 P.F. (LAG) %
19 EFFICIENCY ( AT 75 C ) AT 50 % OF FULL LOAD
a ) 1.0 P.F %
b ) 0.8 P.F. (LAG) %
20 LOAD AT WHICH MAX. EFFICIENCY SHALL OCCUR %
FULL LOAD
21 MAXIMUM EFFICIENCY : %
FORM NO. E 004 DS.xls
X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 4 OF 8
APPLICABLE STANDARD SPECIFICATION :44LK-5100-E.02-004 032
DATE : 3/18/2009 TIME : 3:35 PM
DOC. NO. 44LK-5100/E.04/004A/A4
DATA SHEET FOR REQN.NO.
LIGHTING TRANSFORMER
APPD. BY VDV
44LK-5100 CHKD. BY VDV
MUMBAI PRPD. BY MSJ
DHT PROJECT DATE 28.02.09
CLIENT HPCL LTD. REV. 0
PROJECT TITLE
PROJECT NO
PROJECT LOCATION
PART - B : PERFORMANCE PARTICULARS. ( CONTD... )
( TO BE FURNISHED BY MANUFACTURER )
22 PERCENTAGE REGULATION AT FULL LOAD :
a ) 1.0 P.F. %
b ) 0.8 P.F. ( LAG ) %
23 EXCITING CURRENT REFERRED TO PRIMARY ,
50 Hz. :
a ) 90 % RATED VOLTAGE AMPS.
b ) 100 % RATED VOLTAGE ( NO LOAD CURRENT ) AMPS.
c ) 110 % RATED VOLTAGE AMPS.
24 POWER FACTOR OF EXCITING CURRENT AT
RATED VOLTAGE AND 50 Hz. :
25 TAPPING ON H.V. WINDING
a) TYPE OF TAP CHANGER
b) TAPPING RANGE WITH STEPS
26 TERMINAL CONNECTION
a) TERMINAL BOX ARRANGEMENT ; HV & LV
b) PRIMARY TERMINAL TYPE
c) CABLE / CONDUCTOR SIZE :
d) SECONDARY TERMINAL TYPE
e) CABLE / CONDUCTOR / BUS BAR SIZE :
f) BUS DUCT TAKE OFF
27 RADIATORS
28 TERMINAL BUSHINGS
a) VOLTAGE CLASS
b) RATED CURRENT
c) IMPULSE WITHSTAND VOLTAGE
d) POWER FREQUENCY WITHSTAND VOLTAGE
e) CLAREANCE IN AIR
f) PHASE TO PHASE
g) PHASE TO EARTH
h) MINIMUM CREEPAGE/ PROTECTIVE CREEPAGE DISTANCE
29 BUSHING CTs REQUIRED
30 DRY TYPE, CAST RESIN CTs LOATED IN CABLE BOX
REQUIRED
31 CT DETAILS
a) NUMBER OF CTs REQUIRED
b) APPLICATION OF CTs
c) NUMBER OF CORES
e) CT RATIO
f) CLASS OF ACCURACY
g) BURDEN
h) PARAMETERS FOR Vk, Imag, Rct AND Vct AS PER
DATA SHEET
FORM NO. E 004 DS.xls
X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 5 OF 8
APPLICABLE STANDARD SPECIFICATION :44LK-5100-E.02-004 032
DATE : 3/18/2009 TIME : 3:35 PM
DOC. NO. 44LK-5100/E.04/004A/A4
DATA SHEET FOR REQN.NO.
LIGHTING TRANSFORMER
APPD. BY VDV
44LK-5100 CHKD. BY VDV
MUMBAI PRPD. BY MSJ
DHT PROJECT DATE 28.02.09
CLIENT HPCL LTD. REV. 0
PROJECT TITLE
PROJECT NO
PROJECT LOCATION
PART - B : PERFORMANCE PARTICULARS. ( CONTD... )
( TO BE FURNISHED BY MANUFACTURER )
32 MAGNETISING INRUSH CURRENT ( PEAK )
UNDER WORSE CONDITIONS OF RESIDUAL
MAGNETISM & INSTANT OF SWITCHING : KA.
33 SYMMETRICAL SHORT-CIRCUIT CURRENT
(ASSUME INFINITE SOURCE ) : KA.
34 TIME OF WITHSTAND WITHOUT INJURY UNDER
MAX. SYMM. SHORT CIRCUIT CONDITION : SECS.
35 THERMAL TIME CONSTANT : HRS.
36 MAX. FLUX DENSITY IN CORE AT RATED K.LINES /
VOLTAGE : CM
37 CURRENT DENSITY AT RATED LOAD :
a ) H.V. WINDING A / MM
b ) L.V. WINDING A / MM
38 TYPE OF WINDING :
HIGH VOLTAGE :
LOW VOLTAGE :
39 MATERIAL FOR WINDING
40 INSULATION CLASS
41 IMPULSE LEVELS WITH 1.2/50 MICRO-SECOND
WAVE FORM :
a ) HIGH VOLTAGE. KV.
b ) LOW VOLTAGE. KV.
42 POWER FREQUENCY WITHSTAND VOLTAGE
a ) HIGH VOLTAGE. KV.
b ) LOW VOLTAGE. KV.
43 TYPE OF COOLING.
44 MAXIMUM TEMPERATURE RISE ABOVE AMBIENT TEMP.
44.1 TOP OIL BY THERMOMETER
a) FOR ONAN TYPE COOLING
0
C
b) FOR ONAF TYPE COOLING
0
C
c) FOR ONWF TYPE COOLING
0
C
d) FOR OFWF TYPE COOLING
0
C
44.2 WINDING BY RESISTANCE METHOD
a) FOR ONAN TYPE COOLING
0
C
b) FOR ONAF TYPE COOLING
0
C
c) FOR ONWF TYPE COOLING
0
C
d) FOR OFWF TYPE COOLING
0
C
45 COOLING FANS
a) NUMBER OF FANS REQUIRED
b) RATING OF EACH FAN
c) MIN NUMBER OF FANS TO BE IN OPERATION AT FULL
LOAD
d) WINDING TEMPERATURE AT WHICH FORCED COOLING
IS INITIATED
FORM NO. E 004 DS.xls
X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 6 OF 8
APPLICABLE STANDARD SPECIFICATION :44LK-5100-E.02-004 032
DATE : 3/18/2009 TIME : 3:35 PM
DOC. NO. 44LK-5100/E.04/004A/A4
DATA SHEET FOR REQN.NO.
LIGHTING TRANSFORMER
APPD. BY VDV
44LK-5100 CHKD. BY VDV
MUMBAI PRPD. BY MSJ
DHT PROJECT DATE 28.02.09
CLIENT HPCL LTD. REV. 0
PROJECT TITLE
PROJECT NO
PROJECT LOCATION
PART - B : PERFORMANCE PARTICULARS. ( CONTD... )
( TO BE FURNISHED BY MANUFACTURER )
e) TRANSFORMER DERATING FACTOR AFTER FAILURE OF
- ONE COOLING FAN
- TWO COOLING FANS
- ALL COOLING FANS
46 TOTAL WEIGHT WITH OIL & ACCESSORIES . KG.
47 VOLUME OF OIL FOR COMPLETE FILLING LITRES
48 APPROXIMATE OVERALL DIMENSIONS ( L x W x H ) MM.
49 SIZE ( L x W x H ) & WT. OF LARGEST SHIPPING SECTION MM. & KG
51 CLERANCE
a) MINIMUM CLERANCE HEIGHT FOR LIFTING CORE AND MM
WINDING FROM TANK
b) FREE SPACE REQUIRED AT THE TOP FOR REMOVAL MM
OF ACCESSORIES INCLUDING BUSHING
52 WHEELS
a) PLAIN ROLLERS / FLANGED WHEELS
b) MOVEMENT UNIDIRECTIONAL / BIDIRECTIONAL
c) GUAGE
d) QUANTITY
53 ENCLOSURE FOR MARSHALLING BOX, COOLING
CONTROL CABINET, OLTC PANEL ETC
54 VACUUM WITHSTAND CAPABILITY
a) MAIN TANK
b) RADIATORS
55 DETAILS OF FITTINGS & ACCESSORIES.
a) RATING & DIAGRAM PLATE PROVIDED / NOT PROVIDED / NOT APPLICABLE
b) DIAL TYPE MAGNETIC OIL LEVEL GUAGE WITH LOW PROVIDED / NOT PROVIDED / NOT APPLICABLE
LEVEL ALARM CONTACTS
C) SILICA GEL BREATHER WITH A SEAL & CONNECTING PROVIDED / NOT PROVIDED / NOT APPLICABLE
PIPE, IN A TRANSPARENT ENCLOSURE
d) CONSERVATOR WITH FILLING HOLE, CAP AND DRAIN PROVIDED / NOT PROVIDED / NOT APPLICABLE
VALVE & ISOLATING VALVE FOR CONSERVATOR
e) EXPLOSION VENT WITH DIAPHRAGM EQUILISING PIPE PROVIDED / NOT PROVIDED / NOT APPLICABLE
f) PLAIN OIL LEVEL INDICATOR WITH MINIMUM MARKING PROVIDED / NOT PROVIDED / NOT APPLICABLE
g) DOUBLE FLOAT BUCHHOLZ RELAY PROVIDED / NOT PROVIDED / NOT APPLICABLE
h) DIAL TYPE THERMOMETER FOR OIL TEMPERATURE PROVIDED / NOT PROVIDED / NOT APPLICABLE
WITH ALARM AND TRIP CONTACTS
i) MARSHALLING BOX PROVIDED / NOT PROVIDED / NOT APPLICABLE
j) OIL SAMPLING VALVE PROVIDED / NOT PROVIDED / NOT APPLICABLE
k) TOP OIL FILTER VALVE PROVIDED / NOT PROVIDED / NOT APPLICABLE
l) BOTTOM FILTER VALVE PROVIDED / NOT PROVIDED / NOT APPLICABLE
m) DRAIN VALVE WITH PLUG PROVIDED / NOT PROVIDED / NOT APPLICABLE
n) PRESSURE RELEIF VALVE PROVIDED / NOT PROVIDED / NOT APPLICABLE
p) INSPECTION COVER PROVIDED / NOT PROVIDED / NOT APPLICABLE
q) THERMOMETER POCKET (FOR TOP OIL TEMP) PROVIDED / NOT PROVIDED / NOT APPLICABLE
FORM NO. E 004 DS.xls
X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 7 OF 8
APPLICABLE STANDARD SPECIFICATION :44LK-5100-E.02-004 032
DATE : 3/18/2009 TIME : 3:35 PM
DOC. NO. 44LK-5100/E.04/004A/A4
DATA SHEET FOR REQN.NO.
LIGHTING TRANSFORMER
APPD. BY VDV
44LK-5100 CHKD. BY VDV
MUMBAI PRPD. BY MSJ
DHT PROJECT DATE 28.02.09
CLIENT HPCL LTD. REV. 0
PROJECT TITLE
PROJECT NO
PROJECT LOCATION
PART - B : PERFORMANCE PARTICULARS. ( CONTD... )
( TO BE FURNISHED BY MANUFACTURER )
r) BI DIRECTIONAL ROLLERS PROVIDED / NOT PROVIDED / NOT APPLICABLE
s) DRAW EYES PROVIDED / NOT PROVIDED / NOT APPLICABLE
t) LIFTING LUGS PROVIDED / NOT PROVIDED / NOT APPLICABLE
u) JACKING PADS PROVIDED / NOT PROVIDED / NOT APPLICABLE
w) AIR RELEASE VENT PROVIDED / NOT PROVIDED / NOT APPLICABLE
x) TWO EARTHING TERMINALS PROVIDED / NOT PROVIDED / NOT APPLICABLE
y) IMAGE COIL CT FOR WINDING TEMP WITH DIAL TYPE PROVIDED / NOT PROVIDED / NOT APPLICABLE
THERMOMETER
I NOTES & ADDITIONAL REQUIREMENTS
1) DRY TYPE TRANSFORMERS SHALL BE PROVIDED WITH CLASS H INSULATION WITH TEMPERATURE RISE
LIMITED TO CLASS F.
FORM NO. E 004 DS.xls
X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 8 OF 8
APPLICABLE STANDARD SPECIFICATION :44LK-5100-E.02-004 032
DATE : 3/18/2009 TIME : 3:35 PM