How do you define the "TRUE" constant in the LAD/FDB editor in STEP 7 (TIA Portal)?

Entry ID:87149213 Date:2014-02-03


STEP 7 (TIA Portal) -- Creating S7 programs -- Addressing variables and data structures
S7-1200 CPU 12xx -- Creating S7 programs -- Addressing variables and data structures
S7-1500 CPU 15xx -- Creating S7 programs -- Addressing variables and data structures
How do you define the "TRUE" constant in the LAD/FDB editor in STEP 7 (TIA Portal)?
Description
You can only set the "TRUE" constant for binary links for the S7-300/S7-400 in the STL programming
language, but not in the LAD/FDB editor. For this you must set a variable to "1" (=TRUE) in the LAD
and FBD programming languages. Then you can use the variable with its given value in any network
of the program.
Option 1: Set variable to TRUE
Fig. 01 gives an example of how to set the "Always_True" variable always to "1". For this you can also
use any other variable in the program that now always has the value "TRUE".

Fig. 01
Option 2: Define system memory
In the S7-1200/S7-1500 you can define the system memory in the device configuration. System
memories are memories with defined values.
1. Open the device configuration of your S7-1200/S7-1500 CPU and in the navigation area you
click "System and clock memory".
2. Enable the "Enable the use of system memory byte" option.
3. Assign a number for the "Address of system memory byte". The default value "1" is entered
here.
4. Save and compile your program.
The example below (Fig. 02) the system memory byte is defined as "1". The M1.2 variable then
always has the value "TRUE".
http://support.automation.siemens.com/WW/view/en/87149213
Page 1 of 2 9/5/2014 3:32:06 PM

Fig. 02
Note
The selected memory byte cannot be used for buffering.
Note on the Programming Guidelines for S7-1200/1500
Since the system memory and the clock memory depend on the hardware we recommend that you
follow the programming guidelines for programming and configuring the S7-1200/S7-1500. More
information about the programming guidelines is available in Entry ID: 81318674.
Creation environment
The screens in this FAQ response were created with STEP 7 (TIA Portal) V12.
Entry ID:87149213 Date:2014-02-03