02 Ratio of Output Voltage to Sensing Voltage 2 03 Generator Type 4 04 Rated Generator Output Current (A) 2510 05 CT Voltage At Rated Generator Current (V) 4,57 06 Knee Frequency (Hz) 59,8 07 Decreasing Volts/Hz Slope 1 (V/Hz) 2,0 08 Decreasing Volts/Hz Slope 2 (V/Hz) 2,0 09 Minimum Voltage (%) 60,0 10 Underfrequency Point (Hz) 25,0 11 Overvoltage Trip Point (%) 115 12 Overvoltage Trip Time (s) 3 13 Undervoltage Trip Point (%) 85 14 Undervoltage Trip Time (s) 30 15 Voltage Gain (IR Compensation) (%) 0 16 Integral Gain 6,0 17 Proportional Gain 5,0 18 Single Phase Sensing Select 0 = Three phase ; 1 = Single phase 0 19 Diode Monitor Trip Point 4,0 20 Reverse VAR Trip Time 5,0 21 Reverse VAR Fault Selection 1,0 22 Droop/CCC Select (0 = Droop, 1 = CCC) 0 30 Droop Percentage (%) 5,0 31 PF/KVAR Select (0 = PF, 1 = KVAR) 0 32 PF Reference 0,82 33 KVAR Reference 1,0 34 Reverse Power Trip Point (%) 7,0 35 Reverse Power Trip Time (s) 5,0 36 Paralleling Integral Gain - 37 Paralleling Proportional Gain - 38 PF Switch Point (%) - 50 Generator Output Frequency (Hz) 51 Generator Output Voltage (V) 52 Generator Output Current (A) 53 Generator Reactive Output Current (A) 54 Generator Real Current (A) 55 Exciter Field Current (A) 56 Three Phase Kilowatts (KE and later) (kW) 57 Power Factor (PF) 58 Three Phase KVAR (KE and later) 60 Hours (h) 70 Voltage Adjust 71 PF/KVAR Adjust 90 Password 91 Software ID 92 Latest Fault 93 Previous Fault 94 Fault Clear 95 Alarm Fault 96 Shutdown Fault Reset