Prepared by: ECHO ARCHITECTURE 04:14PM Ai r System Informati on AirSystemName AHU-122 EquipmentClass CW AHU AirSystemType VAV Number of zones 8 Floor Area 3178.0 ft Location Najran, Saudi Arabia Si zi ng Cal cul ati on Informati on Zone and Space Sizing Method: ZoneCFM Peak zone sensible load SpaceCFM Individual peak space loads Calculation Months Jan to Dec Sizing Data Calculated Central Cool i ng Coi l Si zi ng Data Totalcoilload 21.7 Tons Totalcoilload 260.5 MBH Sensiblecoilload 228.8 MBH CoilCFMatJun1500 8976 CFM MaxblockCFMatJun1500 9835 CFM SumofpeakzoneCFM 10158 CFM Sensibleheatratio 0.878 ft/Ton 146.4 BTU/(hr-ft) 82.0 Waterflow@10.0Frise 52.12 gpm Load occurs at Jun 1500 OA DB / WB 105.0 / 63.3 F Entering DB / WB 76.8 / 59.6 F Leaving DB / WB 49.5 / 47.9 F Coil ADP 46.5 F Bypass Factor 0.100 Resulting RH 40 % Design supply temp. 55.0 F Zone T-stat Check 8 of 8 OK Max zone temperature deviation 0.0 F Central Heati ng Coi l Si zi ng Data No central heating coil loads occurred during this calculation. Humi di fi er Si zi ng Data MaxsteamflowatJun1500 24.54 lb/hr AirflowRate 8976 CFM Air mass flow 34918.01 lb/hr Moisture gain .00070 lb/lb Suppl y Fan Si zi ng Data ActualmaxCFMatJun1500 9835 CFM StandardCFM 8502 CFM ActualmaxCFM/ft 3.09 CFM/ft Fan motor BHP n/a Fan motor kW 12.73 kW Outdoor Venti l ati on Ai r Data DesignairflowCFM 483 CFM CFM/ft 0.15 CFM/ft CFM/person 13.80 CFM/person Hourly Analysis Program v4.70 Page 1 of 12 Zone Sizing Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM Ai r System Informati on AirSystemName AHU-122 EquipmentClass CW AHU AirSystemType VAV Number of zones 8 Floor Area 3178.0 ft Location Najran, Saudi Arabia Si zi ng Cal cul ati on Informati on Zone and Space Sizing Method: ZoneCFM Peak zone sensible load SpaceCFM Individual peak space loads Calculation Months Jan to Dec Sizing Data Calculated Zone Si zi ng Data Maximum Design Minimum Time Maximum Zone Cooling Air Air of Heating Floor Sensible Flow Flow Peak Load Area Zone Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft) CFM/ft Zone 1 6.4 343 19 J un 1500 2.0 153.0 2.24 Zone 2 5.0 266 24 J ul 0000 0.7 71.0 3.74 Zone 3 44.0 2355 76 J un 1500 13.5 770.0 3.06 Zone 4 17.5 936 21 J un 1500 4.8 188.0 4.98 Zone 5 9.9 528 22 J un 1500 3.1 196.0 2.70 Zone 6 54.1 2898 108 J un 1500 17.9 1128.0 2.57 Zone 7 6.5 350 10 J un 1500 1.6 45.0 7.77 Zone 8 36.8 1973 203 J un 2200 10.9 627.0 3.15 Zone Termi nal Si zi ng Data No Zone Terminal Sizing Data required for this system. Space Loads and Ai rfl ows Cooling Time Air Heating Floor Zone Name / Sensible of Flow Load Area Space Space Name Mult. (MBH) Load (CFM) (MBH) (ft) CFM/ft Zone 1 5F-01-Bedroom 1 6.4 J un 1500 343 2.0 153.0 2.24 Zone 2 5F-01-Kitchen 1 5.0 J ul 0000 266 0.7 71.0 3.74 Zone 3 5F-01-Patient Room+Recp 1 44.0 J un 1500 2355 13.5 770.0 3.06 Zone 4 5F-02-Bedroom 1 17.5 J un 1500 936 4.8 188.0 4.98 Zone 5 5F-02-Master Bedroom 1 9.9 J un 1500 528 3.1 196.0 2.70 Zone 6 5F-02-Patient Room+Recp 1 54.1 J un 1500 2898 17.9 1128.0 2.57 Zone 7 5F-02-Storage 1 6.5 J un 1500 350 1.6 45.0 7.77 Zone 8 5F-06-Main Dining (Fem) 1 36.8 J un 2200 1973 10.9 627.0 3.15 Hourly Analysis Program v4.70 Page 2 of 12 Ventilation Sizing Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM 1. Summary VentilationSizingMethod ASHRAE Std 62.1-2010 DesignCondition Minimum flow (cooling) OccupantDiversity 1.000 UncorrectedVentilationAirflowRate 483 CFM SystemVentilationEfficiency 1.000 DesignVentilationAirflowRate 483 CFM 2. Space Ventilation Analysis Table Minimum Floor Required Time Required Air Required Uncorrected Space Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation Zone Name / Space Name Mult. (CFM) (ft) (CFM/ft) Occupancy (CFM/person) Effectiveness (CFM) (CFM) Efficiency Zone 1 5F-01-Bedroom 1 19 153.0 0.06 2.0 5.00 1.00 19 19 1.000 Zone 2 5F-01-Kitchen 1 24 71.0 0.12 2.0 7.50 1.00 24 24 1.000 Zone 3 5F-01-Patient Room+Recp 1 76 770.0 0.06 6.0 5.00 1.00 76 76 1.000 Zone 4 5F-02-Bedroom 1 21 188.0 0.06 2.0 5.00 1.00 21 21 1.000 Zone 5 5F-02-Master Bedroom 1 22 196.0 0.06 2.0 5.00 1.00 22 22 1.000 Zone 6 5F-02-Patient Room+Recp 1 108 1128.0 0.06 8.0 5.00 1.00 108 108 1.000 Zone 7 5F-02-Storage 1 10 45.0 0.12 1.0 5.00 1.00 10 10 1.000 Zone 8 5F-06-Main Dining (Fem) 1 203 627.0 0.18 12.0 7.50 1.00 203 203 1.000 Totals (incl. Space Multipliers) 483 483 1.000 Hourly Analysis Programv4.70 Page 3 of 12 Air System Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 105.0 F / 63.3 F HEATING OA DB / WB 44.7 F / 35.0 F Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 1019 ft 55739 - 1019 ft - - Wall Transmission 1614 ft 12385 - 1614 ft 9968 - Roof Transmission 3178 ft 22443 - 3178 ft 21713 - Window Transmission 1019 ft 15863 - 1019 ft 15465 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 129 ft 10119 - 129 ft 1958 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 3820 ft 5043 - 3820 ft 2865 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 6356 W 21686 - 0 0 - Task Lighting 850 W 2900 - 0 0 - Electric Equipment 1600 W 5459 - 0 0 - People 35 9010 7640 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 5500 5500 - 0 0 Safety Factor 5% / 5% 8307 657 5% 2598 0 >> Total Zone Loads - 174453 13797 - 54567 0 Zone Conditioning - 169631 13797 - -3155 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Return Fan Load 8976 CFM 0 - 508 CFM 0 - Ventilation Load 483 CFM 13440 -7968 483 CFM 1100 798 Supply Fan Load 8976 CFM 36978 - 508 CFM -673 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 5% 8723 - 5% 2728 - >> Total System Loads - 228772 5829 - 0 798 Central Cooling Coil - 228772 31710 - 0 0 Central Heating Coil - 0 - - 0 - Humidification Load - - -25881 - - 797 >> Total Conditioning - 228772 5829 - 0 797 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads Hourly Analysis Program v4.70 Page 4 of 12 Space Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 5F-01-Bedroom '' IN ZONE '' Zone 1 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 105.0 F / 63.3 F HEATING OA DB / WB 44.7 F / 35.0 F OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F Sensible Latent Sensible Latent SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 33 ft 1883 - 33 ft - - Wall Transmission 34 ft 274 - 34 ft 210 - Roof Transmission 153 ft 1080 - 153 ft 1045 - Window Transmission 33 ft 513 - 33 ft 500 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 0 ft 0 - 0 ft 0 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 258 ft 341 - 258 ft 194 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 306 W 1044 - 0 0 - Task Lighting 50 W 171 - 0 0 - Electric Equipment 100 W 341 - 0 0 - People 2 460 240 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 5% / 5% 305 12 5% 97 0 >> Total Zone Loads - 6412 252 - 2047 0 TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 5F-01-Bedroom '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr) NE EXPOSURE WALL 34 0.244 - 274 - 210 WINDOW 1 33 0.600 0.800 513 1883 500 H EXPOSURE ROOF 153 0.270 - 1080 - 1045 Hourly Analysis Program v4.70 Page 5 of 12 Space Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' 5F-01-Kitchen '' IN ZONE '' Zone 2 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 87.5 F / 57.2 F HEATING OA DB / WB 44.7 F / 35.0 F OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F Sensible Latent Sensible Latent SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 0 ft 0 - 0 ft - - Wall Transmission 0 ft 0 - 0 ft 0 - Roof Transmission 71 ft 821 - 71 ft 485 - Window Transmission 0 ft 0 - 0 ft 0 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 0 ft 0 - 0 ft 0 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 203 ft 162 - 203 ft 152 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 142 W 484 - 0 0 - Task Lighting 50 W 171 - 0 0 - Electric Equipment 300 W 1024 - 0 0 - People 2 560 540 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 1500 1500 - 0 0 Safety Factor 5% / 5% 236 102 5% 32 0 >> Total Zone Loads - 4958 2142 - 669 0 TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' 5F-01-Kitchen '' IN ZONE '' Zone 2 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr) H EXPOSURE ROOF 71 0.270 - 821 - 485 Hourly Analysis Program v4.70 Page 6 of 12 Space Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' 5F-01-Patient Room+Recp '' IN ZONE '' Zone 3 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 105.0 F / 63.3 F HEATING OA DB / WB 44.7 F / 35.0 F OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F Sensible Latent Sensible Latent SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 264 ft 15061 - 264 ft - - Wall Transmission 304 ft 2448 - 304 ft 1877 - Roof Transmission 770 ft 5438 - 770 ft 5261 - Window Transmission 264 ft 4103 - 264 ft 4000 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 65 ft 5060 - 65 ft 979 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 1018 ft 1344 - 1018 ft 764 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 1540 W 5254 - 0 0 - Task Lighting 200 W 682 - 0 0 - Electric Equipment 300 W 1024 - 0 0 - People 6 1470 1230 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 5% / 5% 2094 62 5% 644 0 >> Total Zone Loads - 43978 1292 - 13525 0 TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' 5F-01-Patient Room+Recp '' IN ZONE '' Zone 3 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr) NE EXPOSURE WALL 304 0.244 - 2448 - 1877 WINDOW 1 264 0.600 0.800 4103 15061 4000 DOOR GLASS 65 0.600 0.880 1004 4055 979 H EXPOSURE ROOF 770 0.270 - 5438 - 5261 Hourly Analysis Program v4.70 Page 7 of 12 Space Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' 5F-02-Bedroom '' IN ZONE '' Zone 4 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 105.0 F / 63.3 F HEATING OA DB / WB 44.7 F / 35.0 F OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F Sensible Latent Sensible Latent SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 165 ft 9413 - 165 ft - - Wall Transmission 103 ft 832 - 103 ft 638 - Roof Transmission 188 ft 1328 - 188 ft 1284 - Window Transmission 165 ft 2564 - 165 ft 2500 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 0 ft 0 - 0 ft 0 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 198 ft 261 - 198 ft 149 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 376 W 1283 - 0 0 - Task Lighting 50 W 171 - 0 0 - Electric Equipment 100 W 341 - 0 0 - People 2 460 240 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 5% / 5% 833 12 5% 229 0 >> Total Zone Loads - 17486 252 - 4799 0 TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' 5F-02-Bedroom '' IN ZONE '' Zone 4 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr) NE EXPOSURE WALL 103 0.244 - 832 - 638 WINDOW 1 165 0.600 0.800 2564 9413 2500 H EXPOSURE ROOF 188 0.270 - 1328 - 1284 Hourly Analysis Program v4.70 Page 8 of 12 Space Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' 5F-02-Master Bedroom '' IN ZONE '' Zone 5 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 105.0 F / 63.3 F HEATING OA DB / WB 44.7 F / 35.0 F OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F Sensible Latent Sensible Latent SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 66 ft 3765 - 66 ft - - Wall Transmission 88 ft 710 - 88 ft 544 - Roof Transmission 196 ft 1384 - 196 ft 1339 - Window Transmission 66 ft 1026 - 66 ft 1000 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 0 ft 0 - 0 ft 0 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 154 ft 203 - 154 ft 116 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 392 W 1337 - 0 0 - Task Lighting 50 W 171 - 0 0 - Electric Equipment 100 W 341 - 0 0 - People 2 460 240 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 5% / 5% 470 12 5% 150 0 >> Total Zone Loads - 9867 252 - 3149 0 TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' 5F-02-Master Bedroom '' IN ZONE '' Zone 5 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr) NE EXPOSURE WALL 88 0.244 - 710 - 544 WINDOW 1 66 0.600 0.800 1026 3765 1000 H EXPOSURE ROOF 196 0.270 - 1384 - 1339 Hourly Analysis Program v4.70 Page 9 of 12 Space Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' 5F-02-Patient Room+Recp '' IN ZONE '' Zone 6 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 105.0 F / 63.3 F HEATING OA DB / WB 44.7 F / 35.0 F OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F Sensible Latent Sensible Latent SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 296 ft 16944 - 296 ft - - Wall Transmission 411 ft 3310 - 411 ft 2538 - Roof Transmission 1128 ft 7966 - 1128 ft 7707 - Window Transmission 296 ft 4616 - 296 ft 4500 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 65 ft 5060 - 65 ft 979 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 1722 ft 2273 - 1722 ft 1292 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 2256 W 7697 - 0 0 - Task Lighting 200 W 682 - 0 0 - Electric Equipment 300 W 1024 - 0 0 - People 8 1960 1640 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 5% / 5% 2577 82 5% 851 0 >> Total Zone Loads - 54108 1722 - 17866 0 TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' 5F-02-Patient Room+Recp '' IN ZONE '' Zone 6 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr) NE EXPOSURE WALL 411 0.244 - 3310 - 2538 WINDOW 1 296 0.600 0.800 4616 16944 4500 DOOR GLASS 65 0.600 0.880 1004 4055 979 H EXPOSURE ROOF 1128 0.270 - 7966 - 7707 Hourly Analysis Program v4.70 Page 10 of 12 Space Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' 5F-02-Storage '' IN ZONE '' Zone 7 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 105.0 F / 63.3 F HEATING OA DB / WB 44.7 F / 35.0 F OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F Sensible Latent Sensible Latent SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 66 ft 3765 - 66 ft - - Wall Transmission 31 ft 251 - 31 ft 192 - Roof Transmission 45 ft 318 - 45 ft 307 - Window Transmission 66 ft 1026 - 66 ft 1000 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 0 ft 0 - 0 ft 0 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 75 ft 99 - 75 ft 56 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 90 W 307 - 0 0 - Task Lighting 50 W 171 - 0 0 - Electric Equipment 0 W 0 - 0 0 - People 1 280 270 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 5% / 5% 311 14 5% 78 0 >> Total Zone Loads - 6527 284 - 1634 0 TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' 5F-02-Storage '' IN ZONE '' Zone 7 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr) NE EXPOSURE WALL 31 0.244 - 251 - 192 WINDOW 1 66 0.600 0.800 1026 3765 1000 H EXPOSURE ROOF 45 0.270 - 318 - 307 Hourly Analysis Program v4.70 Page 11 of 12 Space Design Load Summary for AHU-122 Project Name: Najran Hospital (01 Sep 2014) 09/08/2014 Prepared by: ECHO ARCHITECTURE 04:14PM TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' 5F-06-Main Dining (Fem) '' IN ZONE '' Zone 8 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 89.6 F / 58.3 F HEATING OA DB / WB 44.7 F / 35.0 F OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F Sensible Latent Sensible Latent SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 129 ft 6976 - 129 ft - - Wall Transmission 643 ft 6292 - 643 ft 3968 - Roof Transmission 627 ft 6703 - 627 ft 4284 - Window Transmission 129 ft 1263 - 129 ft 1965 - Skylight Transmission 0 ft 0 - 0 ft 0 - Door Loads 0 ft 0 - 0 ft 0 - Floor Transmission 0 ft 0 - 0 ft 0 - Partitions 192 ft 172 - 192 ft 144 - Ceiling 0 ft 0 - 0 ft 0 - Overhead Lighting 1254 W 4279 - 0 0 - Task Lighting 200 W 682 - 0 0 - Electric Equipment 400 W 1365 - 0 0 - People 12 3360 3240 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 4000 4000 - 0 0 Safety Factor 5% / 5% 1755 362 5% 518 0 >> Total Zone Loads - 36846 7602 - 10878 0 TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' 5F-06-Main Dining (Fem) '' IN ZONE '' Zone 8 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr) NW EXPOSURE WALL 255 0.244 - 2551 - 1573 WINDOW 1 74 0.600 0.800 725 4885 1128 NE EXPOSURE WALL 388 0.244 - 3742 - 2395 WINDOW 1 55 0.600 0.800 538 2090 837 H EXPOSURE ROOF 627 0.270 - 6703 - 4284 Hourly Analysis Program v4.70 Page 12 of 12