DG Sizing

Load on DG during normal operation mode . 970KVA


Load on DG during conjested operation mode 1285KVA
Load on DG during fire operation mode 1244KVA
From the three operation mode
Maximum load= load during conjested operation mode. 1285KVA
Selected DG Rating 2*750KVA
DG Loading in %................................................................... 85.6%
Engine size
Maximum load in KVA.. 1285KVA
Load power factor 0.8
Selected Engine.. 2*600KW
Alternator size
(STAMFORD DG Data has been followed)
1.Maximum load in KVA.. 1285KVA
2.Let selected Alternator Base KVA rating 750KVA
(Refer Stamford DG data, frame size HC6Y)
3.NOs of DG selected.. 2 NOs
4.Total rating two nos DG in parallel.. 1500KVA



Checking of TVD during starting of largest size of motor
5.Transient voltage Dip
Xd=Transient Reactance of alternator Xd/(Xd+C)
C=Rated KVA of Alternator/Starting KVA 12%
6.Rating of largest size of motor = 180KW
7.Motor load in KVA considering 0.86pf of TVF motor =209.30KVA
8.Starting KVA of TVF 180kw motor
(considering starting KVA/Rated KVA=3 for star delta starter)=627.907
(1-7)
9.Base KVA load when the motor is started = 1075.7KVA
(9+8)
10. Starting KVA load when TVF motor is started =1703.60KVA
(4/10)
11.C-Rated KVA of Alternator/Starting KVA =0.88048KVA
12.Transient Voltage Dip(TVD) when TVF motor is started =11.99%
Since TVD 11.99% < 15%
TVD within safe value