Sie sind auf Seite 1von 12

Huawei Mini-shelter Solution

HUAWEI TECHNOLOGIES CO., LTD.


Content
Benefits·············································································································3
Footprint and energy saving···········································································································3

Modular configuration, flexible expansion······················································································4

All-in-one, Orderliness···················································································································4

Fast deployment, ROI improvement································································································5

Main specifications····························································································6
Typical scenario configuration············································································7
Typical application A - Mini-sized indoor macro site·········································································7

Typical application B - High integration solution for DBS site····························································8

Typical application C - Battery cabinet with independent cooling·····················································9

Typical application D - Outdoor cabinet for power system·····························································10

1 HUAWEI TECHNOLOGIES
Huawei Mini-shelter was developed for easing operators' pressure in site acquisition, meeting operators' requirements
for energy saving and flexible expansion. As an innovative installation solution for site equipment, it not only has a
large housing capability like traditional shelter, but also adopts independent compartment temperature control method
as outdoor cabinet. Because Mini-shelter has few limitations on application scenarios and can satisfy operators'
different requirements, it is gaining more and more popularity in modern site.

HUAWEI TECHNOLOGIES 2
Benefits
Footprint and energy saving
• Mini-size, decreasing 60% footprint, easing site acquisition pressure and decreasing deployment cost
• In non-high-temperature areas*, using independent temperature control method without A/C, reducing 50~80%
cooling power consumption
• In high-temperature areas*, adopting intelligent heat exchanger system, decreasing A/C running time, saving
energy 40~60%
• Independent cooling for battery, prolonging its lifespan 2~5 years

Door with HEX* Door with Door with HEX Door with TEC Door with direct Door with natural
HEX & TEC* & direct cooling cooling cooling

power

Minimum
Configuration of Mini-
configuration of
shelter equipment
traditional shelter
cabinet
1000W

70%
300W

50%
150W

Temperature
control mode
Air conditioner Heat exchanger 04 Heat exchanger 02

*Notes:
None-high-temperature area refers to the area where the total time of the temperature higher than 40oC is less than 12 days (288 h) in one year.
High-temperature area refers to the area where the total time of the temperature higher than 40oC is equal to or longer than 12 days (288 h) in one year.
TEC: Thermal electric Cooler
HEX: Heat Exchanger

3 HUAWEI TECHNOLOGIES
Modular configuration, flexible expansion
• Modular configuration. Providing series combinations by three basic function units, "equipment cabinet, auxiliary
cabinet, and storage battery cabinet"
• Easy configuration according to customer needs
• According different working temperature demands of different equipment, every cabinet has individual cooling
method
• Flexible expansion, and easily solves the management problems of co-site

Example of modular configuration, "equipment cabinet+auxiliary cabinet, +storage battery cabinet"

Side by side expansion

Back to back expansion

HUAWEI TECHNOLOGIES 4
All-in-one, Orderliness
• Large housing capability, minimizing the number of outdoor cabinet
• All-in-one. "Main equipment, temperature control equipment, power system, battery, ACDC, DCDU …"
• Simplifying the site design, making the site orderly

Fast deployment, ROI improvement


• Supporting installation in the factory and transportation as a whole
• Supporting shipment in components and onsite assembly
• Onsite assembly for a three-unit-combination takes about 2 hours by 4 persons
• Less civil engineering

crane lifting forklift moving On-site assembly

5 HUAWEI TECHNOLOGIES
Main Specifications
Technical Index Equipment Cabinet (1unit) Battery Cabinet (1unit) Auxiliary Cabinet (1unit)

Inner dimensions: 800×800×1800 mm


Dimensions (W×D×H)
Outside dimensions: Max 905×1085×2155mm (height: 200 mm-base included)

Typical temperature
Heat exchange TEC conditioner/direct cooling Natural dissipation
control mode

Deep cycle: 2 V single unit, 490 Ah


Telecom power, BBU,
Integration capability AGM: 2 V single unit, 400 Ah ACDB, ATS
monitoring
AGM: 12 V single unit, 600 Ah

TEC: 5-100%RH
Relative humidity Heat exchange: 5-100%RH 5-95%RH
Direct-cooling: 5-95%RH

IP protection IP55 IP55(TEC)/IP34(direct cooling) IP55

Weight (base, door, Minimum: 204kg Minimum: 212kg


177kg
and rack included) Maximum: 236kg Maximum: 220kg

Technical
Heat Exchanger TEC Direct cooling
Index

Maximum Maximum
Typical Power Maximum Power Typical Power Typical Power
Power Power
Consumption Consumption Consumption Consumption
Power Consumption Consumption
Consumption
HX02 110W 150W
310W 380W 48W 48W
HX04 215W 300W

Cooling HX02: 80W/K


190W 300W
Capacity HX04: 190W/K

Inner Equipments
700W 1000W
HX02 heat
Temperature ΔT* 10oC 12oC Inner temperature:
Conditioning ΔT: 2oC~3oC
Inner Equipments 15oC~30oC
Performance 1600W 2000W 2300W
HX04 heat
ΔT 10oC 13oC 14oC

*Notes:
ΔT=TI-TO
TI: Inner temperature
TO: Outer temperature

HUAWEI TECHNOLOGIES 6
Typical scenario configuration
Typical application A - Mini-sized indoor macro site

Scenario •• In high-temperature areas, intelligent heat exchanger


•• Street site or rooftop site in large city, site acquisition is hard system saving energy 40-60%
•• Better grid, no electric time is less than 2 hours per day
•• Expecting Lower TCO
site configuration
Benefits
BTS equipment BTS3900
•• 2-unit-combination Mini-shelter cutting down
TRX configuration S4/4/4
60% footprint, decreasing the site acquisition and shelter Mini-shelter (2units)
deployment cost power system TP48300/A
•• In non-high-temperature areas, independent storage battery 150AH 12V AGM

temperature control method saving energy 50-80% backup time 4hours

Wiring Space(1U)

Wiring Space(4U)
Spare Space(9U)

EMUA(1U)
AC/DC(16U)
ACDB(4U)
TP48300/A

Wiring Space(4U)

DCDU-03A(1U)

Spare Space(5U)

BTS3900(21U)
TEC

150AH 150AH 150AH 150AH


12V 12V 12V 12V

Base

Configuration of non-high temperature environment

Wiring Space(1U)
Spare Space(1U)
Wiring Space(4U)
EPAC(2U)

ACDB(4U)

Air Return
Vent AC/DC(16U) Wiring Space(7U)
TP48300/A Heat
Exchanger

DCDU-03A(1U)
A/C Air Supply
Vent IDU(4U)
BTS3900(21U)
TEC

150AH 150AH 150AH 150AH


12V 12V 12V 12V

Base

Configuration of high temperature environment

7 HUAWEI TECHNOLOGIES
Typical application B - High integration solution for DBS site

Scenario
•• Off-grid or unreliable grid
•• Lots of auxiliary equipment, site acquisition is difficult
•• Expecting Lower OPEX
Benefits
•• 3-unit-combination Mini-shelter cutting down 40% footprint
•• High integration with BBU, battery, monitor, power system, environment control equipment, ACDC …
•• Independent temperature control method saving energy 50-80%, D.G-battery hybrid power saving fuel 50%

site configuration
BTS equipment DBS3900
TRX configuration S2/2/2
shelter Mini-shelter (3 units)
power system TP48300/A
storage battery 490Ah deep cycle battery
backup time 8hours
diesel generator 1pcs 8 KVA
controller IPS

Wiring Space(4U)

AC/DC(16U)
TP48300/A BAT

Heat Exchanger
Direct cooling or TEC
DCDU-03B(1U)
Spare Space(1U)
BBU(2U)
EMUA(1U)

Spare Space(10U) BAT

ACDB(4U)
Spare Space(1U)

Base

HUAWEI TECHNOLOGIES 8
Typical application C - Battery cabinet with independent cooling

Scenario
•• Traditional shelter with A/C (above 1000w) cooling
•• A/C start-temperature set at 20~25oC, high cooling energy consumption
Benefits
•• Providing independent cooling for battery with TEC(380w)
•• A/C start-temperature set at28~35oC, saving energy up to 70%
•• Supporting indoor assembly

Scenario
•• Outdoor site, outdoor BTS equipment
•• Ambient temperature has great influence on battery's life
Benefits
•• Providing direct cooling/TEC cooling for battery
•• Comparing with ordinary battery cabinet with natural cooling, Mini-shelter will prolong battery lifespan 2~5 years
•• Support onsite assembly, suit for rooftop site and mountain site, individual component weight≤50kg

BAT

BAT

Direct cooling or TEC


BAT

BAT

Base

9 HUAWEI TECHNOLOGIES
Typical application D - Outdoor cabinet for power system

Scenario Benefits
•• Outdoor site, outdoor BTS equipment •• Outdoor cabinet for power system with TP48300/A, offering
•• Outdoor power system with large capacity 30A or 50 A rectifier module, max capacity to 300A
•• Some other indoor equipment •• Providing 20U spare space for other equipments

Wiring Space(4U)

AC/DC(16U)
TP48300/A

Heat Exchanger

Spare Space(20U)

Base

Scenario Benefits
•• Outdoor site, outdoor BTS equipment •• Outdoor cabinet for power system with EPS4890,
•• Outdoor power system with small capacity max capacity to 90A
•• Some other indoor equipment •• Providing 32U spare space for other equipment

Wiring Space(3U)

TP4890(5U)

Heat Exchanger
Spare Space(13U)

TEC
150AH 150AH 150AH 150AH
12V 12V 12V 12V

150AH 150AH 150AH 150AH


12V 12V 12V 12V

Base

HUAWEI TECHNOLOGIES 10
Huawei
Mini-shelter
Solution

Copyright © Huawei Technologies Co., Ltd. 2009. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

Trademark Notice

, HUAWEI, and are trademarks or registered trademarks of Huawei Technologies Co., Ltd.
Other trademarks, product, service and company names mentioned are the property of their respective owners.

NO WARRANTY HUAWEI TECHNOLOGIES CO., LTD.


THE CONTENTS OF THIS MANUAL ARE PROVIDED “AS IS”. EXCEPT AS REQUIRED BY APPLICABLE LAWS, Huawei Industrial Base
NO WARRANTIES OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO, THE Bantian Longgang
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE MADE IN
Shenzhen 518129, P.R. China
RELATION TO THE ACCURACY, RELIABILITY OR CONTENTS OF THIS MANUAL.
Tel: +86-755-28780808
TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, IN NO CASE SHALL HUAWEI
Version No.: M3-308130299-20090722-C-1.0
TECHNOLOGIES CO., LTD BE LIABLE FOR ANY SPECIAL, INCIDENTAL, INDIRECT, OR CONSEQUENTIAL
DAMAGES, OR LOST PROFITS, BUSINESS, REVENUE, DATA, GOODWILL OR ANTICIPATED SAVINGS
ARISING OUT OF OR IN CONNECTION WITH THE USE OF THIS MANUAL. www.huawei.com